used as  concentrated  chemicals can cause 
corrosion.  Never  use  hydrochloric  acid 
(muriatic acid) or chlorine as it will corrode 
stainless steel. 
NOTE:  Ball  valves  should  be  installed  in 
the condenser water supply and return lines 
for unit isolation and water flow balancing. 
All manual flow valves should be of the ball 
valve  design.  Globe  or gate  valves  should 
not be used due to high pressure drops and 
poor throttling characteristics. 
Pressure  and  temperature  ports  are 
recommended  in  condenser  water  supply 
and return lines for system balancing. These 
openings should  be  5  to  10  pipe  diameters 
from  the  unit  water  connections.  To  allow 
for  mixing  and  temperature  stabilization, 
wells  in  the  water  piping  should  extend  at 
least ½ pipe diameter into the pipe. 
Piping systems should not exceed 10 ft/sec 
fluid velocity to ensure tube wall integrity 
and reduce noise. 
Condensate Drain Piping 
6-25 and 30 ton units are equipped with one 
condensate  drain  pan  connection,  on  the 
right side of the unit, and are furnished with 
a p-trap for field installation. 26 and 31-140 
ton units are equipped with two condensate 
drain connections, one on the left side of the 
unit and one on the right side of the unit, and 
are  furnished  with  two  p-traps  for  field 
installation. 
All  drain  connections  must  be  used  and 
individually  trapped  to ensure a  minimum 
amount  of condensate accumulation in  the 
drain pans. ABS type cement should be used 
to join the drain pipe connections. 
Drainage  of  condensate  directly  onto  the 
roof may be acceptable in certain areas, refer 
to  local  codes.  If  condensate  is  to  drain 
directly  onto  the  roof  a  small  drip  pad 
should be placed below the drain to protect 
the roof from possible damage. 
If  condensate  is  piped  into  the  building 
drainage  system,  the  drain  pipe  should 
Each  heat  exchanger  is  equipped 
with  a  refrigerant  pressure  relief 
device  to  relieve  pressure  should 
excessive  condensing  pressures 
(>675  psig)  occur.  Codes  may 
require  installing  contractor  to 
connect  and  route  relief  piping 
outdoors. The relief valve has  a 5/8” 
male flare outlet connection. 
   CAUTION  
Installing contractor is responsible for 
properly  sizing  and  installing  water 
system  components.  Improper  fluid 
flow  due  to  valves,  piping,  or 
improper  pump  operation  may result 
in  unacceptable  unit  operation  and 
void warranty. 
   CAUTION  
PVC  (Polyvinyl  Chloride)  and  CPVC 
(Chlorinated  Polyvinyl  Chloride)  are 
vulnerable  to  attack  by  certain 
chemicals.  Polyolester  (POE)  oils 
used  with  R-410A  and  other 
refrigerants,  even  in  trace  amounts, 
in a PVC or CPVC piping system will 
result in stress cracking of the piping 
and  fittings  and  complete  piping 
system failure. 