Instruction Manual
62 
penetrate the roof external to the unit itself. 
The drain line should be pitched away from 
the unit at least 1/8 inch per foot. On longer 
runs an  air  break  should  be  used to  ensure 
proper drainage. 
Draw-through  cooling  coils  will  have  a 
negative static pressure in the drain pan area. 
This will cause an un-trapped drain to back 
up  due  to  air  being  pulled  up  through  the 
condensate drain piping. 
Condensate drain trapping and piping should 
conform to all applicable governing codes. 
Heating Coils 
One or two row hot water and steam heating 
and preheating coils can be factory installed. 
All valve controls for heating operation are 
field supplied and field installed. Hot water 
and steam coil connections are spun copper 
tube. 
Water  coils  should  not  be  subjected  to 
entering  air  temperatures  below  38°F  to 
prevent  coil  freeze-up.  If  air  temperature 
across the  coil  is  going to  be  below this 
value, use  a glycol  solution  to  match the 
coldest air expected. 
Table 20 - Steam Coil Connection Sizes 
Model (RN-) 
Steam Coil 
Connection Size 
006-140 
2 1/8” 
Table 21 - Hot Water Coil Connection Sizes 
Model (RN-) 
Hot Water Coil 
Connection Size 
006, 007, 008, 009, 010, 
011, 013, 015 
1 3/8” 
016, 018, 020, 025, 030 
1 5/8” 
026, 031, 040, 050, 060, 
070 
2 1/8” 
(standard)/ 
1 3/8” (preheat 
coil) 
055, 065, 075, 090, 105, 
120, 130, 140 
2 1/8” 
Chilled Water Coil 
Four or six row chilled  water cooling coils 
can  be  factory  installed.  All  valve  controls 
for cooling operation are field supplied and 
field  installed. Chilled  water  coil 
connections are spun copper tube. 
Table 22 - Chilled Water Coil Connection 
Sizes 
Model (RN-) 
Chilled Water 
Coil Connection 
Size 
006, 007, 008, 009, 010, 
011, 013, 015 
1 5/8” 
016, 018, 020, 025, 030 
2 1/8” 
026, 031, 040 
2 5/8” 
050, 055, 060, 065, 070, 
075, 090, 105, 120, 130, 
140 
2 1/8” 
Unit should not be operated without a 
p-trap. Failure to install a p-trap may 
result  in  overflow  of  condensate 
water into the unit. 
   CAUTION  
Piping  shall  be  in  accordance  with 
national  and  local  codes.  Pressure 
limiting devices,  backflow preventers 
and all other safety requirements are 
the sole responsibility of the installing 
contractor. 
   WARNING 