Instruction Manual
76 
Before Charging 
Unit  being  charged  must  be  at  or  near  full 
load conditions before adjusting the charge. 
Units equipped with hot gas reheat must be 
charged  with  the  hot  gas  reheat  valves 
closed while the unit is in cooling mode to 
get  the  proper  charge.  After  charging,  unit 
should  be  operated  in  reheat 
(dehumidification)  mode  to  check  for 
correct operation. 
Units  equipped  with  heat  pump  options 
should be charged in heating mode to get the 
proper  charge. After charging,  unit should 
be  operated in  cooling mode  to check  for 
correct  charge.    Charge  may  need  to  be 
adjusted  for  cooling  mode.    If  adjustments 
are made in the cooling mode heating mode 
must be rerun to verify proper operation. 
After adding or removing charge the system 
must be allowed to stabilize, typically 10-15 
minutes,  before  making  any  other 
adjustments. 
The type of unit  and options  determine  the 
ranges for liquid sub-cooling and evaporator 
superheat. Refer  to the table  below when 
determining the proper sub-cooling. 
Checking Liquid Sub-Cooling 
Measure the temperature of the liquid line as 
it leaves the condenser coil. 
Read  the  gauge  pressure at  the  liquid  line 
close to the point where the temperature was 
taken. You must use liquid line pressure as it 
will  vary  from  discharge  pressure  due  to 
condenser coil pressure drop. 
Convert the pressure obtained to a saturated 
temperature using the appropriate refrigerant 
temperature-pressure chart. 
Subtract  the  measured  liquid  line 
temperature  from  the  saturated  temperature 
to determine the liquid sub-cooling. 
Compare calculated sub-cooling to the table 
below  for  the  appropriate  unit  type  and 
options. 
Checking Evaporator Superheat 
Measure the temperature of the suction line 
close to the compressor. 
Read gauge pressure at the suction line close 
to the compressor. 
Convert the pressure obtained to a saturated 
temperature using the appropriate refrigerant 
temperature-pressure chart. 
Subtract the saturated temperature from the 
measured  suction  line  temperature  to 
determine the evaporator superheat. 
Compare calculated superheat to the table 
below  for  the  appropriate  unit  type  and 
options. 
The  Clean Air  Act  of  1990  bans  the 
intentional  venting  of  refrigerant 
(CFC’s  and  HCFC’s)  as  of  July  1, 
1992. Approved methods of recovery, 
recycling  or  reclaiming  must  be 
followed.  Fines  and/or  incarceration 
may be levied for non-compliance. 
   CAUTION  










