Operation 
Unit  operations  should  be  controlled  with 
thermostat,  or unit  controller,  never  at  the 
main  power  supply,  except  for  servicing, 
emergency,  or  complete  shutdown  of  the 
unit. 
Thermostat Operation 
Heating 
Thermostat system switch - "Heat" 
Thermostat fan switch - "Auto" or "On" 
Thermostat temperature set to desired point. 
Cooling 
Thermostat system switch - "Cool" 
Thermostat fan switch - "Auto" or "On" 
Thermostat temperature set to desired point. 
Air Circulation 
Thermostat system switch - "Off" 
Thermostat fan switch - "Auto" or "On" 
No change of the thermostat temperature. 
With  these  settings,  the  supply blower will 
run continuously but the supply air will not 
be heated, cooled, or dehumidified. 
System Off 
Thermostat system switch - "Off" 
Thermostat fan switch - "Auto" 
No change of the thermostat temperature. 
With these settings the system is shut down, 
with the exception of control system power. 
Night and Weekend Unoccupied Operation 
To  reduce  the  operating  time  of  the  unit 
when the space is unoccupied, such as nights 
and  weekends,  it  is  recommended  that  the 
temperature  setting  be  raised  about  5°F 
while unoccupied during the cooling season 
and lowered about 10°F  during  the  heating 
season. 
Packaged DX Cooling Operation and 
Control 
When a call for cooling (G and Y1, Y2, etc.) 
is  made  the  supply  blower  motors  and 
compressors will energize. 
Gas Heater Operation 
When  heat  (G  and  W1,  W2, etc.) is  called 
for  the  combustion  motor  starts  and  the 
ignition  control  is  energized.  The  control 
sends  24 VAC  to  the  main  gas  valve and 
high voltage to the igniter. If a burner flame 
has  been  detected  within  10  seconds,  the 
spark  is  extinguished  and  the  flame 
continues. If a flame has not been  detected 
after  10  seconds,  the  gas  valve  closes,  the 
spark  ceases  and  the  induced  draft  blower 
continues to purge the heat exchanger. After 
45 seconds of purge, the ignition system will 
attempt to light the burners again. Should no 
flame be detected  after  3 tries,  the  ignition 
control  will  lock  out  the  system.  Power  to 
the ignition control must be cycled to reset 
the heater control. 
On  a  fault  the  gas  train  is  shut  down  by  a 
main limit located in the heat exchanger area 
or  by  an  auxiliary  limit  mounted  in  the 
supply fan compartment. 
COMPRESSOR CYCLING 
5 MINUTE MINIMUM OFF TIME 
To  prevent  motor  overheating 
compressors  must  cycle  off  for  a 
minimum of 5 minutes. 
5 MINUTE MINIMUM ON TIME 
To  maintain  the  proper  oil  level 
compressors  must  cycle  on  for  a 
minimum of 5 minutes. 
The  cycle  rate  must  not  exceed  6 
starts per hour. 
   WARNING 