Instruction Manual
87 
Evaporator Coil (6-25 and 30 ton) 
Removal 
Evacuate refrigerant from the systems. 
Remove  the TXV  bulbs  from the  suction 
lines. Disconnect the suction and liquid line 
copper connections to the evaporator coil. 
Figure 45 - Evaporator Coil Access 
Remove the screws attaching the filter rack 
to the evaporator coil blank-off panels at the 
door opening and along the top of the coil. 
Remove the screws attaching the filter rack 
to  the  back  wall.  Angle  filter  rack  away 
from coil so it fits through the door opening. 
It may be  necessary to  remove economizer 
damper assembly. 
Remove screws attaching access side, back, 
and  top  blank-off  panels  to  the  evaporator 
coil and the unit. 
Angle the coil so that it fits through the door 
opening. 
Remove the evaporator coil. 
Reinstallation 
Install the coil in the unit drain pan. There 
should  be  about  a  1/4”  gap  between  the 
upstream side of the coil and the back of the 
drain pan. 
Secure the coil to the back wall of the unit 
with the blank-off panel. Attach the top and 
access side blank-off panels to the coil. 
Attach  the  filter  rack  to  the  back,  top,  and 
access side coil blank-off panels upstream of 
the  coil.  Reinstall  economizer  damper 
assembly if necessary. 
Connect  the  suction  and  liquid  copper 
connections to the evaporator coil. Reinstall 
the TXV bulbs on the suction lines. 
Evacuate the  refrigerant  systems.  Weigh in 
the nameplate refrigerant charge. 
See Adjusting Refrigerant Charge section to 
check for proper sub-cooling and superheat 
of the refrigerant systems. 
Brazed Plate Heat Exchanger Cleaning 
Because  of  a  normally  high  degree  of 
turbulence in brazed plate heat exchangers, 
for  many  applications  the  heat  exchanger 
channels are self cleaning. For applications 
that are not self cleaning (i.e. hard water at 
high  temperatures,  etc.)  or  applications 
where additional  cleaning is desired,  it is 
possible  to  clean  the  brazed  plate  heat 
exchanger by circulating a cleaning liquid. 
Use a tank with  weak acid, 5% phosphoric 
acid  (H3PO4)  or,  if  the  exchanger  is 
frequently  cleaned,  5%  oxalic  acid 
(H2C2O4).  Pump  the  cleaning  liquid 
through  the  exchanger.  For  optimum 
cleaning,  the  cleaning  solution  flow  rate 
should  be  a  minimum  of  1.5  times  the 
Electric  shock  hazard.  Shut  off  all 
electrical  power  to  the  unit  to  avoid 
shock  hazard  or  injury  from  rotating 
parts. 
   WARNING 










