Instruction Manual
93 
pattern  according  to  the  capacity  demand 
signal of  the system. The  following table 
shows  the  linear  relationship  between  the 
demand  signal  and  compressor  capacity 
modulation.  The  compressor  controller 
protects  the  compressor  against  high 
discharge temperature. Refer to Appendix B 
for  the  relationship  between  thermistor 
temperature readings and resistance values. 
Table 28 - Demand Signal vs. Compressor Capacity Modulation 
Demand 
Signal (VDC) 
Loaded % 
Unloaded % 
Time Loaded 
Time 
Unloaded 
% Compressor 
Capacity 
1.00 
Off 
Off 
Off 
Off 
0% 
1.44 
10% 
90% 
1.5 sec 
13.5 sec 
10% 
3.00 
50% 
50% 
7.5 sec 
7.5 sec 
50% 
4.20 
80% 
20% 
12 sec 
3 sec 
80% 
5.00 
100% 
0% 
15 sec 
0 sec 
100% 
Figure 50 - Compressor Controller Flash Code Details 
Filter Replacement 
Monthly  air  filter  inspection  is  required  to 
maintain optimum unit efficiency. 
It is strongly recommended that filter media 
be  replaced  monthly.  Filters  are  located 
upstream of the evaporator coil in the filter 
and  economizer  section.  Open  access  door 
and pull filters straight out to inspect all of 
the  filters.  Replace  filters  with  the  size 
indicated  on  each  filter  or  as  shown  in  the 
tables  below.  Arrow  on  the  replacement 
Electric  shock  hazard.  Shut  off  all 
electrical  power  to  the  unit  to  avoid 
shock  hazard  or  injury  from  rotating 
parts. 
   WARNING 