Installation manual
Arley Wood & Multifuel Stoves 23
INSTALLATION
PLAN VIEW OF REGISTER PLATE AND
CLEARANCES FOR NON INSULATED
FLUES
TYPICAL METAL INSULATED CHIMNEY SYSTEM
TO BE INSTALLED TO THE CHIMNEY MANUFACTURERS INSTRUCTIONS IN COMPLIANCE
WITH BUILDING REGULATIONS AND
BS7566 PTS 1-4
A is minimum clearance for non-insulated flue =
1.5 x D to a non-combustible surface/material
or
3 x D to combustible surface/material