DEFRA Stove Installation and User Guide For stoves ranges: Aarrow DEFRA Signature DEFRA Ecoburn DEFRA Solution DEFRA PLEASE RETAIN THIS GUIDE FOR FUTURE REFERENCE BK575 EN 13240:2001+ Amd.
More than 20 years experience has been put into the development of our stoves to ensure ultimate performance and years of trouble free use and enjoyment. Every detail of the stove has been carefully designed and engineered which is why we are so confident in the reliability of our products. Should you have any questions about our stoves that are not covered by this manual, please contact the Arada retailer in your area, or call our technical support department on 08448 567181 .
INSTALLAITON INSTRUCTIONS HEARTH AIR FOR COMBUSTION The stove should be installed on a floor with adequate load bearing capacity. If the existing construction does not meet this prerequisite, suitable measures (e.g. load distributing plate) should be taken to achieve it. All stoves require ventilation to burn safely and correctly.
INSTALLATION INSTRUCTIONS sealed with fire cement. Note : The flue pipe must be fitted inside the outlet spigot. Failure to do so could result in the spillage of condensation running down the flue, (see fig.1c) FIREBOX LINER PANELS Arada DEFRA stove uses firebox liner panels at both sides of the stove. The throat plate is not supported by these liners, however the throat plate must be installed before the liners can be fitted, and the liners removed before the throat plate can be removed.
INSTALLATION INSTRUCTIONS All images below are cut-away for clarity 1. Insert throat plate assembly into the fire box and manoeuvre so that the throat plate drops into the landing plate cutouts. 2. Raise the throat plate assembly vertically out of the landing slots ensuring the front edge remains behind the front edge of the air wash lip, see fig 4. 3.
INSTALLATION INSTRUCTIONS in good operating condition. Check the existing flue is in good condition with suitable access for collection and removal of debris. If the flue size is more than 225mm (9”) diameter or 200mm (8”) X 200mm (8”) square, a suitable lining of 150mm (6”) diameter should be fitted. Approved Document J 2010 allows for the use of a 5” liner / flue for wood burning when a stove that is DEFRA exempt is installed.
USER GUIDE FUEL TYPES Paper The most efficient use of this appliance is with the fire door(s) closed at all times, apart from re-fuelling (when alight) or cleaning (when cold). Paper will burn successfully. Burn dry paper only or chimney damage will occur. Never leave the appliance unattended for an extended length of time with the door(s) open. Please contact Arada Ltd for further details and advice on the use of other fuels.
USER GUIDE Important reminders for the user. 1. Take care to insure against blocking or obstructing the permanent air ventilator fitted to supply combustion air for the appliance. 2. Do not install an extractor fan in the same room as the appliance or a room adjoining the same room. If the installer considers this unavoidable refer to Approved Document J Section 1, Paragraphs 1.20 & 1.
USER GUIDE WARNING : Properly installed, with a suitable flue or chimney, operated and maintained correctly, this appliance will not emit fumes into the dwelling. over firing. Occasional fumes when de-ashing and re-fuelling may occur. However, persistent fume emission is potentially dangerous and must be investigated by a HETAS registered installer. Call the Fire Service—Dial 999 or 112 Immediately close all air inlets to the appliance, to reduce the air supply to the stove.
USER GUIDE Multi Purpose Operating Tool Air Controls Your stove is supplied with a multi purpose operating tool, used for adjusting the air inlet controls and the removal of the ash pan Our DEFRA stoves have one air inlet control for easy operation. Emptying the Ash pan Your stove is supplied with a unique ash pan. To empty or remove the ash pan, open the fire door(s), fit the fork end of the operating tool into the ash pan slots and remove from the ash pit chamber.
USER GUIDE Images of a Generic Stove Wood burning air control position Solid fuel burning air control position Fully Closed Fully Closed Fully Open Fully Open DEFRA Stove Installation and User Guide 11
Technical Information Height to centre of rear flue Depth from back to centre of top flue Code Minimum Distance to kW Flue Net Combustibles mm Output Height Width Depth Diameter Efficiency Rear Side AARROW 5SC B 1 - 4.5 526 391 410 5” 80.3% 400 350 462mm 98mm ECB5SCF 1 - 4.5 526 391 410 5” 80.3% 400 350 462mm 98mm SIGN5SCF 1 - 4.5 526 391 410 5” 80.3% 400 350 462mm 98mm SOL5SC-S2 1 - 4.5 526 391 410 5” 80.