Specifications 161
Standard DC Input Filter Settings (Inputs 4 and higher)
Nominal Filter Setting (ms) ON Delay (ms) OFF Delay (ms) Maximum Frequency (Hz)
50% Duty Cycle
Minimum Maximum Minimum Maximum
0.500 0.090 0.500 0.020 0.500 1.0 kHz
1.000 0.500 1.000 0.400 1.000 0.5 kHz
2.000 1.100 2.000 1.300 2.000 250 Hz
4.000 2.800 4.000 2.700 4.000 125 Hz
8.000
(1)
5.800 8.000 5.300 8.000 63 Hz
16.000 11.000 16.000 10.000 16.000 31 Hz
(1) This is the default setting.
Relay Contact Ratings
Maximum Volts Amperes Amperes
Continuous
(1)
Volt-Amperes
Make Break Make Break
240V AC 15.0 A 1.5 A
5.0 A
(2)
/3.0 A
3600 VA 360 VA
120V AC 30.0 A 3.0 A
5.0 A
(2)
/3.0 A
3600 VA 360 VA
125V DC
0.22 A
(3)
1.0 A 28 VA
24V DC
1.2 A
(3)
2.0 A
(1) 5.0 A for UL 508
3. 0A for UL 1604, Class 1, Division 2, Hazardous Locations, Groups A, B, C, D
(2) 3.0 A above 40 °C.(104 °F)
(3) For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by
the applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 14V, the
make/break ratings for relay contacts cannot exceed 2A.
ATTENTION
Do not exceed the “Current per group common” specification.