Specifications
Publication 1747-UM011G-EN-P - June 2008
158 Troubleshooting
• Power status indicator is 
on
• RS232 status indicator is 
off
• FLT status indicator is off 
or flashing
• Status of Run; Force; 
DH-485, DH+, or ENET; 
or Batt status indicators 
do not matter
The processor is 
not transmitting
Channel is 
configured for 
DH-485 mode.
Check communication parameters of channel configuration. 
Also, refer to your programming software documentation.
RS232/DF1 
parameters are set 
up improperly.
Check the following communication parameters of programmer 
and channel configuration.
1. communication rate - programmer and processor 
communication rates must match
2. DF1 node addresses (default is 1 for half-duplex, and 9 for 
full-duplex) - programmer and processor addresses must be 
different
3. error checking
4. number of data bits
Hardware problem. 1. Check cable connections.
2. Check cable pinouts. Also, see appendix C for RS-232 
pinouts.
• Power status indicator is 
on
• FLT status indicator is on
• Status of all other status 
indicators do not matter
A fatal error has 
occurred
Excessive noise or 
a faulty processor.
1. Cycle power to obtain flashing FLT status indicator and 
default program.
2. Examine the error code following the power cycle. Take 
appropriate action.
3. Reload the program.
4. Contact your local Rockwell Automation representative if the 
error persists.
SLC 5/03. SLC 4/04, and SLC 5/05 Communication Errors
If the status indicators 
indicate
The following 
error exists
Probable Cause Recommended Action