Specifications

6
SLC 500 Programmable Controllers and I/O Modules
SLC 500 Common Specifications
The following specifications apply to all SLC 500 modular components unless noted.
Description Specification
Temperature Operating: 0˚C to +60˚C (+32˚F to +140˚F)
Storage: -40˚C to +85˚C (-40˚F to +185˚F)
Humidity 5 to 95% without condensation
Vibration Operating: 1.0G at 5 to 2000 Hz
Non-operating: 2.5Gs at 5 to 2000 Hz
Shock Operating: (all modules except relay contact) 30.0Gs (3 pulses, 11 ms)
Operating: (relay contact modules 1746-OWx and 1746-IOx combo) 10.0Gs (3 pulses, 11 ms)
Non-operating: 50.0Gs (3 pulses, 11 ms)
Free Fall (drop test) Portable, 2.268 kg (5 lbs) or less at 0.762 m (30 in.) (six drops)
Portable, 2.268 kg (5 lbs) or more at 0.1016 m (4 in.) (three flat drops)
Noise Immunity NEMA Standard ICS 2-230
Electromagnetic Showering Arc: 1.5 KV (Industry Standard - NEMA ICS 2-230/NEMA ICS 3-304)
Compatibility Surge Withstand Capability: 3 KV (Industry Standard - IEEE Std. 472-1974/ANSI C37.90/90A-1974)
Fast Transient Burst (impulse): 2 KV for 1746 power supplies, 1 KV for 1746 I/O and communication lines
over 10m (32.84 ft.), 5 ns rise time
Electrostatic Discharge (ESD): 15 KV, 100 pF/1.5KW model
Radiated Electromagnetic Susceptibility:
5W walkie-talkie at 464.5 MHz and 153.05 MHz
Safety Dielectric Withstand: 1500V ac
(Industry Standard - UL 508, CSA C22.2 No. 142)
Isolation between Communication Circuits: 500V dc
Isolation between Backplane and I/O: 1500V ac
Flammability and Electrical Ignition: UL94V-0
Certification •CSA certified
(when product or •UL listed
packaging is marked) •CUL listed
•Class I, Groups A, B, C or D, Division 2
•CE compliant for all applicable directives