USING NM7000 RMM SOFTWARE WITH LEASED LINE CONNECTION
Applies to USRobotics Courier Dual Standard V.34+ modems
5.28.1 Definitions
Local modem The modem attached to the PC running
NM7000 RMM software.
Remote modem The modem attached to the NM7000
cabinet.
5.28.2 Configuring the remote modem
1.
Set DIP switches on the remote modem
.
Switch 1 must be set to the DTR ALWAYS ON position.
Switch 4 must be set to the ON position - Do not echo offline commands
Switch 5 must be set to the AUTO ANSWER ON RING position.
The remaining switches should be left in their factory default positions.
2.
Connecting the modem to the cabinet
.
The remote modem must be connected to Remote Port 2 on the connection interface
board in the ILS cabinet.
3. Configure remote modem init string.
With a PC running NM7000 RMM software, log in with MASTER access on the Local Port.
Select «Modem configuration» from the ILS menu.
Set the Remote port 2 modem configuration as follows (all ‘0’ letters are zeroes):
Figure 5-60 ILS port settings for leased-line connections
4.
Initializing the remote modem
.
Pressing the «Send init» button in the ILS modem settings window makes the ILS send the
initialization string on the port selected in the port list.
The ILS will also send the these init strings when the ILS is powered on.
5.28.3 Configuring the local modem
1. All modem DIP switches should be left in their factory default positions.