Cut Sheet

6 - Pluggable interface relays CR-P | Data sheet
Technical data
Input circuit - Supply circuit A1-A2
Rated con-
trol supply
voltage U
s
Rated
frequency
Make
voltage
(at 20 °C)
Maxium
voltage
(at 55 °C)
Break
voltage
Rated power Coil
resistance
(at 20 °C)
Tolerance of
coil
resistance
DC coils 12 V DC - 8.4 V DC 30.6 V DC 0.1 U
s
0.4-0.48 W 360 Ω 10 %
24 V DC - 16.8 V DC 61.2 V DC 0.1 U
s
0.4-0.48 W 1440 Ω 10 %
48 V DC - 33.6 V DC 122.4 V DC 0.1 U
s
0.4-0.48 W 5700 Ω 10 %
110 V DC - 77.0 V DC 280.0 V DC 0.1 U
s
0.4-0.48 W 25200 Ω 10 %
AC Coils 24 V AC 50/60 Hz 19.2 V AC 28.8 V AC 0.15 U
s
0.75 VA 400 Ω 10 %
48 V AC 50/60 Hz 38.4 V AC 57.6 V AC 0.15 U
s
0.75 VA 1550 Ω 10 %
110 V AC 50/60 Hz 88.0 V AC 132.0 V AC 0.15 U
s
0.75 VA 8900 Ω 10 %
120 V AC 50/60 Hz 96.0 V AC 144.0 V AC 0.15 U
s
0.75 VA 10200 Ω 10 %
230 V AC 50/60 Hz 184.0 V AC 276.0 V AC 0.15 U
s
0.75 VA 38500 Ω 10 %
Output circuits
Type CR-P...1 CR-P...2
Output circuit(s) - Relay contact(s) 11-12/14 11-12/14,
21-22/24
Kind of output Relay, 1 c/o (SPDT)
contact
Relay, 2 c/o (SPDT)
contacts
Contact material AgNi AgNi
AgNi/Au 5 µm
Rated operational voltage U
e
(IEC/EN 60947-1) 250 V
Minimum switching voltage 5 V
Maximum switching voltage 300 V DC / 440 V AC
Minimum switching current 5 mA (AgNi), 2 mA (AgNi/Au)
Rated free air thermal current I
th
16 A 8 A
Rated operational current (IEC/EN 60947-5-1) AC-12 (resistive) 230 V 16 A 8 A
AC-15 (inductive) 230 V 1.5 A 1.5 A
AC-15 (inductive) 120 V 3 A 3 A
DC-12 (resistive) 24 V 16 A 8 A
DC-13 (inductive) 24 V 2.5 A 2 A
DC-13 (inductive) 120 V 0.22 A 0.22 A
DC-13 (inductive) 250 V 0.1 A 0.1 A
AC rating *
(UL 508; NEMA ICS-5)
Utilization category (pilot duty)
(Contact rating code designation)
B300
Max. rated operational voltage
300 V AC
Max. continuous thermal current
at utilization category
5 A
Max. making / breaking apparent
power at utilization category
3600 / 360 VA
Utilization category (resistive)
(CSA22.2 No.14....)
16 A, 250 V AC 8 A, 250 V AC
DC rating *
(UL 508; NEMA ICS-5)
Utilization category (pilot duty)
(Contact rating code designation)
R300
Max. rated operational voltage 300 V DC
Max. continuous thermal current
at utilization category
1 A
Max. making / breaking apparent
power at utilization category
28 VA
Utilization category (resistive)
(CSA22.2 No.14....)
- 10 A, 24 V DC
Maximum making (inrush) current 30 A 15 A
Minimum switching power 0.3 W (AgNi), 0.05 W (AgNi/Au)