6 - Power supply CP-E 24/5.0 | Data sheet
Technical data
Data at T
a
= 25 °C, U
in
= 230 V AC and rated values, unless otherwise indicated
Input circuits
Supply circuits
Rated input voltage U
in
L,N 115 / 230 V AC
auto select
Input voltage range AC 90-132 V, 180-264 V
DC 210-375 V
Frequency range AC 47-63 Hz
Typical input current at 115 V AC 2.2 A
at 230 V AC 0.83 A
Typical power consumption 140 W
Inrush current limiting at 115 V AC 24 A (max. 5 ms)
at 230 V AC 48 A (max. 5 ms)
Discharge current input / output 0.25 mA
input / PE 3.5 mA
Power failure buffering time at 115 V AC min. 25 ms
at 230 V AC min. 30 ms
Internal input fuse 3.15 A slow-acting / 250 V AC
Power factor correction (PFC) yes, passive, 0.7
User interface
Indication of operational states
Output voltage OUTPUT OK: green LED
V: output voltage OK
OUTPUT LOW: red LED
V: output voltage too low
Output circuit
Rated output voltage L+, L+, L-, L- 24 V DC
Tolerance of the output voltage 0...+1 %
Adjustment range of the output voltage 22.5-28.5 V DC
Rated output power 120 W
Rated output current I
r
T
a
≤ 60 °C 5 A
Derating of the output current 60 °C < T
a
≤ 70 °C 2.5 %/°C
Signalling contact for output voltage OK 13-14 solid-state (max. 60 V DC, 0.3 A)
Minimum fuse rating to achieve short-circuit protection 13-14 ≥ 60 V DC, ≤ 0.3 A fast-acting
Maximum deviation with load change statical ±1 % (single mode)
±5 % (parallel mode)
change of output voltage within the
input voltage range
±0.5 %
Control time < 2 ms
Starting time after applying
the supply voltage
at I
r
max. 1 s
with 3500 µF max. 1.5 s
Rise time at I
r
max. 150 ms
with 3500 µF max. 500 ms
Fall time max. 150 ms
Residual ripple and switching peaks BW = 20 MHz 50 mV
Parallel connection configurable, to increase power, up to 3 devices,
min. 0.1 I
r
– max. 0.9 I
r
Series connection yes, to increase voltage, max. 2 devices
Resistance to reverse feed max. 35 V DC