Constant attention Protection, selectivity and savings: ABB’s mission for your hom Protecting the electrical system is an essential step to ensure safety and comfort to its users, as well as the correct economical and functional operation of the devices it supplies.
Protection aims at minimizing risks for people and devices due to abnormal conditions or faults that impair the electrical parameters of the installation and of the loads. In this context, an adequate coordination between the various protection devices (normally located on the sections of the system or on specific components) and an appropriate degree of selectivity enable to provide total safety of the installation.
2
Miniature circuit-breakers S 200 Plus of range 2/6 Technical features table 2/8 Ordering information 2/12 Technical details 2/19 Overall dimensions 2/25 System pro M compact ® | 2CSC 400 031 D0202 2/5 2
MCB S 200.
2 Contact position indication All System pro M compact® MCBs are suited with a contact position indication (CPI) on the toggle. You can easily identify, if the MCB is in the ON or the OFF position – easy and safe maintenance work is possible. Approvals printed on the dome S 200 and S 200 M MCBs comply to IEC/EN 60898 and IEC/EN 60947 and carry all relevant approval marks for each market and segment they are destined to. The certification markings are also printed on the dome of the MCB.
Technical features table for miniature circuit-breakers S 200 Series 2 General Data Standards Poles Tripping characteristics Rated current In A Rated frequency f Hz Rated insulation voltage U i acc. to IEC/EN 60664-1 V Overvoltage category Pollution degree Data acc. to IEC/EN 60898-1 Rated operational voltage U n V Max. power frequency recovery voltage (U max) V Min.
2CSC400031F0001 2CSC400031F0001 2 S 200 S 200 M IEC/EN 60898-1, IEC/EN 60947-2 UL 1077, CSA 22.2 No. 235 IEC/EN 60898-1, IEC/EN 60947-2 - 1P, 2P, 3P, 4P, 1P+N, 3P+N B, C 6…40 A 50 / 60 Hz 250 V AC (phase to groud), 500 V AC (phase to phase) III 3 1P: 230/400 V AC; 1P+N: 230 V AC ; 2...4P: 400 V AC; 3P+N: 400 V AC 1P: 253 V AC; 1P+N: 253 V AC; 2P: 440 V AC; 3...4P: 440 V AC; 3P+N: 440 V AC; 1P: 72 V DC; 2P: 125 V DC 12 V AC - 12 V DC 6 kA 10 kA 3 4 kV (test voltage 6.
Technical features table for miniature circuit-breakers S 200 Series 2 Mechanical Data Housing Toggle Contact position indication Protection degree acc. to EN 60529 Mechanical endurance ops. Shock resistance acc. to IEC/EN 60068-2-27 Vibration resistance acc. to IEC/EN 60068-2-6 Environmental conditions (damp heat cyclic) acc.
2CSC400031F0001 2CSC400031F0001 S 200 2 S 200 M Insulation group I, RAL 7035 Insulation group II, black, sealable Marking on toggle (I ON / 0 OFF) IP20*, IP40 in enclosure with cover 20,000 ops. 30 g - 3 shocks - 11 ms 5g - 20 cycles at 5…150…5 Hz with load 0.8 In 28 cycles with 55°C/90-96% and 25°C/95-100% -25 … +55°C -40 … +70°C Failsafe bi-directional cylinder-lift terminal 25 mm2 / 25 mm2 18 - 4 AWG - 10 mm2 / 10 mm2 18 - 8 AWG - 2.8 Nm 25 in-Ibs. - No. 2 Pozidrive On DIN rail 35 mm acc.
Ordering Information MCB S 200 Series - B characteristic 2CSC400031F0002 The S 200 miniature circuit breaker is perfectly suitable for protecting lighting and power socket circuits that can be frequently found in residential areas. ABB used its years of experience with miniature circuit breaker to create this product by combining the optimum features for residential use alone.
2CSC400031F0005 N.
2CSC400031F0002 Ordering Information MCB S 200 Series - C characteristic 2 N.
2CSC400031F0005 N.
2CSC400031F0002 Ordering Information MCB S 200 M Series - C characteristic 2 N.
2CSC400031F0005 N.
2CSC400031F0002 Ordering Information MCB S 200 M Series - B characteristic 2 N.
Technical details Tripping diagrams B characteristic C characteristic 2 acc. to IEC/EN 60898-1 In = 6 ... 40 A S200 / S200 M acc. to IEC/EN 60898-1 In = 6 ...
Technical details Internal resistances and power losses of the Miniature Circuit-Breakers 2 Rated current Device series B, C In A mΩ Internal resistances per pole in m Ω Power losses per pole in W W 6 55 2.0 8 15 1.0 10 13.3 1.3 13 13.3 2.3 16 7.0 1.8 20 6.25 2.5 25 5.0 3.2 32 3.6 3.7 40 3.0 4.8 Internal resistances are subject to application-specific and environment-specific conditions and are therefore to be considered as typical values. Tripping characteristics acc.
Influence of ambient temperature The thermal trips are calibrated for an ambient temerpature 30 °C for B- and C-characteristic. In the case of temperatures deviating from these values the tripp values: - are reduced in case of higher temperatures; - are increased in case of lower temperatures. The electronic tripping is not dependent on temperature 2 Derating of load capability of MCBs Max.
Technical details Coordination tables Fuse gG, gL - MCB S 200, S 200 M 2 240 V Supply s. Load s. Characteristic S200, S200 M B S200, S200 M Fuse gG, gL In [A] C 6 63 10...20 100 25...32 100 40 125 50...63 160 3...4 20 6 40 8 63 10...20 100 25...32 100 40 125 50...63 160 MCB - MCB @ 240 V Supply s. Load s. Char.
Short circuit selectivity MCBs 2 Load side Supply side S 700 fuse Char. E/K gG Icu [kA] S 200 C 6 25 In [A] 16 20 25 35 40 50 63 80 100 16 20 25 35 50 63 80 100 m 2 >15 >15 >15 >15 >15 >15 >15 >15 >15 1 1.2 4 >15 >15 >15 >15 >15 3 10 10 10 10 10 10 10 8 8 0.3 0.7 1.2 4.6 6 6 6 6 4 10 10 10 10 10 10 10 8 8 0.3 0.6 0.9 2.8 6 6 6 6 6 10 10 10 10 10 10 10 8 8 0.2 0.5 0.8 2 3.3 5.
Technical details Maximum permissible earth-fault loop impedance ZS at U0 = 230 V~ 2 Impedance Zs at U0 = 230 V AC 1 to ensure compliance with the operation conditions pursuant to IEC 60364-4. Operating time < 0.4 s; at 400 V~ < 0.2 s and at > 400 V~ < 0.1 s The instantaneous release of the MCB ensures an operating time of ≤ 0.1 s (TN system). Determined according to DIN VDE 0100-520 sheet 2:2002-11(source impedance = 300 mΩ, c = 0.95 and conductor temperature 70 °C = factor 0.8).
Overall dimensions S 200, S 200 M 69 44 17.5 35 52.5 70.5 45 85 2 17.5 6.