Compatibility Sheet

3
Starters
3.12 Low Voltage Products & Systems
1SXU000023C0202 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Starter selection by motor horsepower & voltage
Maximum UL/CSA ratings, three phase
NOTE: For motors with RPM greater or less than 1800 RPM, check full load amp rating on motor nameplate to ensure proper overload protection.
For AF50 – AF 300 starters, consult factory.
1 For AF400 - AF750 only.
CAUTION: The above ratings are based on average motor FLA. Actual FLA
on the motor nameplate should be used for overload relay setting.
Motor horsepower
Open
Complete starter
Starter components
3-phase, 1800 RPM 1
Contactors Overload relays
200V 230V 460V 575V Catalog number
List
price
Catalog number
List
price
Catalog number
List
price
1/4 11-2C A9-30-10-84 TA25DU0.4 (0.25 – .4)
$ 63
1/4, 1/3 1/3 11-2D A9-30-10-84 TA25DU0.63 (0.4 – .63)
1/2 11-2E A9-30-10-84 TA25DU1.0 (0.63 – 1.0)
1/2 3/4 11-2F A9-30-10-84 TA25DU1.4 (1.0 – 1.4)
3/4 11-2G A9-30-10-84 TA25DU1.8 (1.3 – 1.8)
1/2 1 1.5 11-2H
$ 165
A9-30-10-84
$ 78
TA25DU2.4 (1.7 – 2.4)
1/2 1.5 2 11-2J A9-30-10-84 TA25DU3.1 (2.2 – 3.1)
3/4 3/4 2 11-2K A9-30-10-84 TA25DU4.0 (2.8 – 4.0)
1 3 11-2L A9-30-10-84 TA25DU5.0 (3.5 – 5.0)
1 1.5 3 5 11-2M A9-30-10-84 TA25DU6.5 (4.5 – 6.5)
2 2 5 11-2N A9-30-10-84 TA25DU8.5 (6.0 – 8.5)
7.5 11-2P A9-30-10-84 TA25DU11 (7.5 – 11)
3 3 7.5 10 21-2Q 171 A12-30-10-84 84 TA25DU14 (10 – 14)
5 5 10 15 31-2R 200 A16-30-10-84 102 TA25DU19 (13 – 19)
7.5 15 20 41-2S
294
A26-30-10-84
183
TA25DU25 (18 – 25)
7.5 10 20 25 41-2T A26-30-10-84 TA25DU32 (24 – 32)
10 10 51-2B
365 A30-30-10-84 252
TA42DU32 (22 – 32)
TA42DU42 (29 – 42)
78 25 30 51-2C
10 15 30 40 61-2C 423 A40-30-10-84 297 TA42DU42 (29 – 42)
15 40 50 71-2D
458
A50-30-11-84
330
TA75DU52 (36 – 52)
102
20 71-2E A50-30-11-84 TA75DU63 (45 – 63)
20 81-2F
522
A63-30-11-84
372
50 60 81-2F A63-30-11-84 TA75DU80 (60 – 80)
25 30 60 75 91-2F 563 A75-30-11-84 413
30 40 75 100 A1-2B 765 A110-30-11-84 480 TA110DU110 (80 – 110) 165
40 B1-2C
1,315 A145-30-11-84 825
TA200DU135 (100 – 135)
225 50 100 125 B1-2D TA200DU150 (110 – 150)
50 60 125 150 C1-2E 1,730 A185-30-11-84 1,290 TA200DU175 (130 – 175)
60 75 150 200 D1-2E3 2,422 A210-30-11-84 1,635
E320DU320 (105-320) 77575 100 200 250 E1-2E3 3,027 A260-30-11-84 1,815
100 250 300 F1-2E3 3,177 A300-30-11-84 1,875
125 125, 150 350 400 G1-70E5 4,125 AF400-30-11-70 3,120
E500DU500 (170 – 500) 865
150 200 400 500 H1-70E5 9,375 AF460-30-11-70 4,425
200 250 500 600 T1-70E8 12,400 AF580-30-11-70 6,900
E800DU800 (270 – 800) 950
250 300 600 700 U1-70E8 13,350 AF750-30-11-70 7,200
Coil voltage selection
All AC operated catalog numbers include a 120VAC coil. To select other coil
voltages, substitute the code from the Coil Voltage Selection Chart for the two
digits after the last dash in the catalog number.
Ex.: A 240V coil is required for an A75 starter: 91-4F
D.C. operated starters
If DC operation is required, consult factory.
Factory modifications
See page 3.3
Discount schedule AA [OA] – A9 - A110
AEA [OC] – A145 - AF1650
Coil voltage selection – A9 - A300
Hz
Contactor
type
Volts
24 110 120 208 220 240 440 480 500 600
60 A 1 2 3 4 5 6 7
50 A 1 2 4 7
Coil voltage selection – AF400 - AF750 1
Hz
Contactor
type
Volts
100 - 250 250 - 500
50/60 AF 70 71
Control transformer voltage selection chart
Hz
Volts
Type 200-208/120 240/120 460 – 480/120 575 – 600/120
50/60
A/AF A B C D
Type 200-208/24 240/24 460 – 480/24 575 – 600/24
A/AF E F G H

Summary of content (1 pages)