User`s manual

146 Serial communications
ACH550-01 User's Manual
BACnet-specific communication parameters
5309 EFB STATUS 0…7
Contains the status of the EFB protocol.
0 =
IDLE EFB protocol is configured, but not receiving any messages.
1 =
EXECUT INIT EFB protocol is initializing.
2 =
TIME OUT – A time-out has occurred in the communication between
the network master and the EFB protocol.
3 =
CONFIG ERROR – EFB protocol has a configuration error.
4 =
OFF-LINE EFB protocol is receiving messages that are NOT
addressed to this drive.
5 = ON-LINE – EFB protocol is receiving messages that are addressed to
this drive.
6 =
RESET EFB protocol is performing a hardware reset.
7 =
LISTEN ONLYEFB protocol is in listen-only mode.
5318 EFB PAR 18 0…65535
For Modbus only: Slave response delay. Sets additional delay in
milliseconds before the drive begins transmitting response to the
master request.
5310 EFB PAR 10 0…65535
Sets the BACnet MS/TP response turn-around time, in milliseconds.
5311 EFB PAR 11 0…65535
Sets, together with parameter 5317
EFB PAR 17, BACnet instance IDs:
For the range 1 to 65535: This parameter sets the ID directly (5317
must be 0). For example, the following values set the ID to 49134:
5311 = 49134 and 5317 = 0.
For IDs > 65535: The ID equals parameter 5311’s value plus 10000
times parameter 5317’s value. For example, the following values set
the ID to 71234: 5311 = 1234 and 5317 = 7.
5312 EFB PAR 12 0…65535
Sets the BACnet Device Object Max Info Frames property.
5313 EFB PAR 13 0…65535
Sets the BACnet Device Object Max Master property.
5316 EFB PAR 16 0…65535
Indicates the count of MS/TP tokens passed to this drive.
5317 EFB PAR 17 0…65535
Works with parameter 5311 to set BACnet instance IDs. See parameter
5311.
Code Description Range