User`s manual

350 Parameter listing and descriptions
ACH550-01 User's Manual
HVAC
default Supply fan Return fan
Cooling
tower fan Condenser
Booster
pump
Parameter
name
Par.
index
123456
34 PANEL
SIGNAL 1
PARAM 3401
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
DISPLAY
SIGNAL 1 MIN 3402 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz
SIGNAL 1
MAX
3403 500.0 Hz 500.0 Hz 500.0 Hz 500.0 Hz 500.0 Hz 500.0 Hz
OUTPUT 1
DSP FORM 3404 DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT
OUTPUT 1
UNIT
3405%%%%%%
OUTPUT 1
MIN 3406 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
OUTPUT 1
MAX
3407 1000.0% 1000.0% 1000.0% 1000.0% 1000.0% 1000.0%
SIGNAL 2
PARAM
3408 CURRENT CURRENT CURRENT CURRENT CURRENT CURRENT
SIGNAL 2 MIN 3409 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A
SIGNAL 2
MAX
3410------
OUTPUT 2
DSP FORM 3411 DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT
OUTPUT 2
UNIT
3412AAAAAA
OUTPUT 2
MIN
3413 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A
OUTPUT 2
MAX3414------
SIGNAL 3
PARAM
3415 AI1 AI1 AI1 AI1 AI1 AI1
SIGNAL 3 MIN 3416 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
SIGNAL 3
MAX
3417 100.0% 100.0% 100.0% 100.0% 100.0% 100.0%
OUTPUT 3
DSP FORM
3418 DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT
OUTPUT 3
UNIT3419VVVVVV
OUTPUT 3
MIN
3420 0.0 V 0.0 V 0.0 V 0.0 V 0.0 V 0.0 V
OUTPUT 3
MAX
3421 10.0 V 10.0 V 10.0 V 10.0 V 10.0 V 10.0 V
35 MOTOR
SENSOR
TYPE
3501 NONE NONE NONE NONE NONE NONE
TEMP
MEAS
INPUT
SELECTION
3502 AI1 AI1 AI1 AI1 AI1 AI1
ALARM LIMIT 3503
110 °C /
1500 ohm /
0
110 °C /
1500 ohm /
0
110 °C /
1500 ohm /
0
110 °C /
1500 ohm /
0
110 °C /
1500 ohm /
0
110 °C /
1500 ohm /
0
FAULT LIMIT 3504
130 °C /
4000 ohm /
0
130 °C /
4000 ohm /
0
130 °C /
4000 ohm /
0
130 °C /
4000 ohm /
0
130 °C /
4000 ohm /
0
130 °C /
4000 ohm /
0