Program features Example The time scheme below visualizes the operation of the sleep function. Motor speed td = Sleep delay (4024) t
Program features 155 Motor temperature measurement through the standard I/O This section describes the temperature measurement of one motor when the drive I/O terminals are used as the connection interface. Motor temperature can be measured using PT100 or PTC sensors connected to analog input and output. One sensor Motor Three sensors AI1 AI1 Motor GND T T T GND T AO AO GND 3.3 nF GND 3. Program features It is also possible to monitor motor temperature by connecting a PTC sensor and a thermistor relay between the +24 V DC voltage supply offered by the drive and a digital input. The figure below displays the connection. Par. 3501 = THERM(0) or THERM(1) Thermistor relay DI1…5 +24 V DC T Motor WARNING! According to IEC 664, the connection of the motor thermistor to the digital input requires double or reinforced insulation between motor live parts and the thermistor. Program features 157 Control of a mechanical brake The mechanical brake is used for holding the motor and driven machinery at zero speed when the drive is stopped, or not powered. Example The figure below shows a brake control application example. WARNING! Make sure that the machinery into which the drive with brake control function is integrated fulfills the personnel safety regulations. Program features Operation time scheme The time scheme below illustrates the operation of the brake control function. See also section State shifts on page 159. Program features 159 State shifts From any state (rising edge) 1) NO MODULATION 0/0/1 2) OPEN BRAKE 1/1/0 3) A RELEASE RFG INPUT 5) 1/1/0 4) RFG INPUT TO ZERO 1/1/1 7) 6) CLOSE BRAKE 8) State (Symbol NN 0/1/1 A RFG = Ramp function generator in the speed control loop (reference handling). 9) X/Y/Z ) - NN: State name - X/Y/Z: State outputs/operations X = 1 Open the brake. The relay output set to brake on/off control energizes. Y = 1 Forced start. Program features Settings Parameter 1401/1805 Additional information Mechanical brake activation through RO 1 / DO 1402/1403/1410 Mechanical brake activation through RO 2…4. With option MREL-01 only. Program features 161 Jogging The jogging function is typically used to control a cyclical movement of a machine section. One push button controls the drive through the whole cycle: When it is on, the drive starts, accelerates to a preset speed at a preset rate. When it is off, the drive decelerates to zero speed at a preset rate. The figure and table below describe the operation of the drive. Program features Note: The jogging speed overrides the constant speeds. Note: The jogging uses ramp stop even if parameter 2102 STOP FUNCTION selection is COAST. Note: The ramp shape time is set to zero during the jogging (ie linear ramp). Jogging function uses constant speed 7 as jogging speed and acceleration/deceleration ramp pair 2. It is also possible to activate jogging function 1 or 2 through fieldbus. Jogging function 1 uses constant speed 7 and jogging function 2 uses constant speed 6. Program features 163 Timed functions A variety of drive functions can be time controlled, eg start/stop and EXT1/EXT2 control. The drive offers • four start and stop times (START TIME 1…START TIME 4, STOP TIME 1…STOP TIME 4) • four start and stop days (START DAY 1…START DAY 4, STOP DAY 1…STOP DAY 4) • four timed functions for collecting the selected time periods 1…4 together (TIMED FUNC 1 SRC…TIMED FUNC 4 SRC) • booster time (an additional booster time connected to timed functions). Program features A parameter which is triggered by a timed function can be connected to only one timed function at a time. Program features 165 Settings Parameter 36 TIMED FUNCTIONS Additional information Timed functions settings 1001, 1002 1102 1201 Timed start/stop control Timed EXT1/EXT2 selection Timed constant speed 1 activation 1209 1401 Timed speed selection Timed function status indicated through relay output RO 1 1402/1403/1410 Timed function status indicated through relay output RO 2…4. With option MREL-01 only. Program features Diagnostics Actual signal 0166 Additional information Start/stop control pulse count Sequence programming The drive can be programmed to perform a sequence where the drive shifts typically through 1…8 states. User defines the operation rules for the whole sequence and for each state. The rules of a particular state are effective when the Sequence program is active and the program has entered the state. Program features 167 Parameter 1402/1403/1410 1501 1601 Additional information Sequence programming output through relay output RO 2…4. With option MREL-01 only. Program features State shifts Sequence programming ENABLE STATE 1 (par. 8420…8424) Go to state N (par 8426, 8427)* State N State N Go to state 4 (par 8445)* 0168 = 4 (State 4) Go to state 5 (par 8455)* 0168 = 5 (State 5) Go to state 6 (par 8465)* 0168 = 6 (State 6) Go to state 7 (par 8475)* STATE 7 (par. 8480…8484) Go to state N (par 8486, 8487)* State N 0168 = 3 (State 3) STATE 6 (par. 8470…8474) Go to state N (par 8476, 8477)* State N Go to state 3 (par 8435)* STATE 5 (par. Program features 169 Example 1 ST1 ST2 ST3 ST4 ST3 50 Hz 0 Hz -50 Hz DI1 DI2 Seq. start State change trigger Sequence programming is activated by digital input DI1. ST1: Drive is started in reverse direction with -50 Hz reference and 10 s ramp time. State 1 is active for 40 s. ST2: Drive is accelerated to 20 Hz with 60 s ramp time. State 2 is active for 120 s. ST3: Drive is accelerated to 25 Hz with 5 s ramp time. Program features ST1 Par. ST2 Setting Par. ST3 Setting Par. ST4 Setting Par. Program features 171 ST2: Drive is accelerated with AI1 + 15% (AI1 + 65% - 50%) reference and 1.5 s ramp time. State shifts to the next state when reference is reached. If reference is not reached within 2 s, state shifts to state 8 (error state). ST3: Drive is decelerated with AI1 + 10% (AI1 + 60% - 50%) reference and 0 s ramp time1). State shifts to the next state when reference is reached. If reference is not reached within 0.2 s, state shifts to state 8 (error state). Program features Parameter Setting Additional information 1002 EXT2 COMMANDS SEQ PROG Start, stop, direction commands for EXT2 1102 EXT1/EXT2 SEL EXT2 EXT2 activation 1106 REF2 SELECT AI1+SEQ PROG Sequence programming output as REF2 1201 CONST SPEED SEL NOT SEL Deactivation of constant speeds 1401 RELAY OUTPUT 1 SEQ PROG Relay output RO 1 control as defined by parameter 8423/…/8493 1601 RUN ENABLE NOT SEL Deactivation of Run enable 1805 DO SIGNAL SEQ PROG Digital output DO contro Program features 173 ST1 Par. ST2 Setting Par. Setting ST3 Par. Setting ST4 Par. Setting Additional information 8420 ST1 REF 50% SEL 8430 65% 8440 60% 8450 35% State reference 8421 ST1 COMMANDS START FRW 8431 START FRW 8441 START FRW 8451 START FRW Run, direction and stop commands 8422 ST1 RAMP -0.2 (ramp pair 2) 8432 1.5 s 8442 0 s 8452 1.5 s Acceleration/ deceleration ramp time 8443 AO=0 8453 AO=0 Relay, digital and analog output control 8444 0. Program features Safe torque off (STO) function See Appendix: Safe torque off (STO) on page 399. Actual signals and parameters 175 Actual signals and parameters What this chapter contains The chapter describes the actual signals and parameters and gives the fieldbus equivalent values for each signal/parameter. It also contains a table of the default values for the different macros. Terms and abbreviations Term Actual signal Def Parameter FbEq E U Definition Signal measured or calculated by the drive. Can be monitored by the user. No user setting possible. Groups 01…04 contain actual signals. Actual signals and parameters Fieldbus equivalent Example: If 2017 MAX TORQUE 1 (see page 217) is set from an external control system, an integer value of 1000 corresponds to 100.0%. All the read and sent values are limited to 16 bits (-32768…32767). Default values with different macros When application macro is changed (parameter 9902 APPLIC MACRO), the software updates the parameter values to their default values. The table below shows the parameter default values for different macros. Actual signals and parameters 177 1103 REF1 SELECT. That would mean a mismatched duplicate functionality for DI3 and DI4: either constant speed or acceleration and deceleration. The function that is not required must be disabled. In this case the constant speed selection must be disabled by setting parameter 1201 CONST SPEED SEL to NOT SEL or to values not related to DI3 and DI4. Remember to also check the default values of the selected macro when configuring the drive inputs. Actual signals and parameters Actual signals Actual signals No. Name/Value Description FbEq 01 OPERATING DATA Basic signals for monitoring the drive (read-only) 0101 SPEED & DIR Calculated motor speed in rpm. A negative value indicates 1 = 1 rpm reverse direction. Calculated motor speed in rpm 1 = 1 rpm Calculated drive output frequency in Hz. (Shown by default 1 = 0.1 Hz on the panel Output mode display.) 0102 SPEED 0103 OUTPUT FREQ 0104 CURRENT Measured motor current in A. Actual signals and parameters 179 Actual signals No. Name/Value Description FbEq 0129 PID 2 SETPNT Setpoint signal (reference) for the PID2 controller. Unit depends on parameter 4106 UNITS and 4107 UNIT SCALE settings. 0130 PID 1 FBK Feedback signal for the process PID1 controller. Unit depends on parameter 4006 UNITS, 4007 UNIT SCALE and 4027 PID 1 PARAM SET settings. 0131 PID 2 FBK 0132 PID 1 DEVIATION 0133 PID 2 DEVIATION Feedback signal for the PID2 controller. Actual signals and parameters Actual signals No. Name/Value 0147 MECH REVS 0148 Z PLS DETECTED Description FbEq Mechanical revolutions, ie the motor shaft revolutions 1=1 calculated by the encoder Encoder zero pulse detector. 0 = not detected, 1 = detected. 1 = 1 0150 CB TEMP Temperature of the drive control board in degrees Celsius (0.0…150.0 °C). 1 = 0. Actual signals and parameters 181 Actual signals No. Name/Value 0173 RO 2-4 STATUS Description Status of the relays in the MREL-01 relay output extension module. See MREL-01 relay output extension module user's manual (3AUA0000035974 [English]). Example: 100 = RO 2 is on, RO 3 and RO 4 are off. FbEq 0179 BRAKE Vector control: Torque value (0…180% of the motor nominal 1 = 0.1% TORQUE MEM torque) saved before the mechanical brake is taken in use. Actual signals and parameters Actual signals No. Name/Value 0306 FAULT WORD 2 Description Bit 14 = EXT FAULT 2 Bit 15 = EARTH FAULT A 16-bit data word. For the possible causes and remedies and fieldbus equivalents, see chapter Fault tracing on page 335. Bit 0 = UNDERLOAD Bit 1 = THERM FAIL Bit 2…3 = Reserved Bit 4 = CURR MEAS Bit 5 = SUPPLY PHASE Bit 6 = ENCODER ERR 0307 FAULT WORD 3 Bit 7 = OVERSPEED Bit 8…9 = Reserved Bit 10 = CONFIG FILE Bit 11 = SERIAL 1 ERR Bit 12 = EFB CON FILE. Actual signals and parameters 183 Actual signals No. Name/Value Description Bit 2 = UNDERVOLTAGE Bit 3 = DIR LOCK FbEq Bit 4 = IO COMM Bit 5 = AI1 LOSS Bit 6 = AI2 LOSS Bit 7 = PANEL LOSS Bit 8 = DEVICE OVERTEMP Bit 9 = MOTOR TEMP Bit 10 = UNDERLOAD Bit 11 = MOTOR STALL Bit 12 = AUTORESET Bit 13…15 = Reserved 0309 ALARM WORD A 16-bit data word. For the possible causes and remedies 2 and fieldbus equivalents, see chapter Fault tracing on page 335. Actual signals and parameters Actual signals No. Name/Value Description FbEq 0403 FAULT TIME 2 Time at which the latest fault occurred. 1=2s Format on the assistant control panel: Real time (hh:mm:ss) if the real time clock is operating. / Time elapsed after the power-on (hh:mm:ss minus the whole days stated by signal 0402 FAULT TIME 1) if real time clock is not used, or was not set. Actual signals and parameters 185 Parameters All parameters No. Name/Value Description Def/FbEq 10 START/STOP/DIR The sources for external start, stop and direction control 1001 EXT1 COMMANDS Defines the connections and the source for the start, stop DI1,2 and direction commands for external control location 1 (EXT1). Actual signals and parameters All parameters No. Name/Value KEYPAD DI1F,2R Description Start, stop and direction commands through control panel when EXT1 is active. To control the direction, parameter 1003 DIRECTION setting must be REQUEST. Start, stop and direction commands through digital inputs DI1 and DI2. Actual signals and parameters 187 All parameters No. Name/Value SEQ PROG 1002 EXT2 COMMANDS Description Start, stop and direction commands through Sequence programming. See parameter group 84 SEQUENCE PROG. Defines the connections and the source for the start, stop and direction commands for external control location 2 (EXT2). Def/FbEq 26 NOT SEL FORWARD See parameter 1001 EXT1 COMMANDS. Enables the control of rotation direction of the motor, or fixes REQUES the direction. Actual signals and parameters All parameters No. Name/Value EXT1 Def/FbEq 0 DI1 DI2 Description EXT1 active. The control signal sources are defined by parameters 1001 EXT1 COMMANDS and 1103 REF1 SELECT. Digital input DI1. 0 = EXT1, 1 = EXT2. See selection DI1. DI3 DI4 DI5 See selection DI1. See selection DI1. See selection DI1. 3 4 5 EXT2 EXT2 active. The control signal sources are defined by parameters 1002 EXT2 COMMANDS and 1106 REF2 SELECT. Actual signals and parameters 189 All parameters No. Name/Value AI1/JOYST Description Def/FbEq Analog input AI1 as joystick. The minimum input signal runs 3 the motor at the maximum reference in the reverse direction, the maximum input at the maximum reference in the forward direction. Minimum and maximum references are defined by parameters 1104 REF1 MIN and 1105 REF1 MAX. Note: Parameter 1003 DIRECTION must be set to REQUEST. Speed ref (REF1) par. Actual signals and parameters All parameters No. Name/Value Description Def/FbEq DI3U,4D(RNC) Digital input DI3: Reference increase. Digital input DI4: 11 Reference decrease. Stop command resets the reference to zero. The reference is not saved if the control source is changed (from EXT1 to EXT2, from EXT2 to EXT1 or from LOC to REM). Parameter 2205 ACCELER TIME 2 defines the rate of the reference change. DI3U,4D(NC) Digital input DI3: Reference increase. Digital input DI4: Reference decrease. Actual signals and parameters 191 All parameters No. Name/Value Description Def/FbEq 0.0…500.0 Hz / Minimum value in rpm. Hz if parameter 9904 MOTOR CTRL 1 = 0.1 Hz 0…30000 rpm MODE setting is SCALAR: FREQ. / 1 rpm Example: Analog input AI1 is selected as the reference source (value of parameter 1103 is AI1). Actual signals and parameters All parameters No. Name/Value Description KEYPAD(RNC) See parameter 1103 REF1 SELECT. KEYPAD(NC) See parameter 1103 REF1 SELECT. Def/FbEq 20 21 DI4U,5D DI4U,5D(NC) FREQ INPUT See parameter 1103 REF1 SELECT. See parameter 1103 REF1 SELECT. See parameter 1103 REF1 SELECT. 30 31 32 SEQ PROG AI1+SEQ PROG See parameter 1103 REF1 SELECT. See parameter 1103 REF1 SELECT. 33 34 See parameter 1103 REF1 SELECT. 35 Defines the minimum value for external reference REF2. Actual signals and parameters 193 All parameters No. Name/Value DI1,2 Description Constant speed selection through digital inputs DI1 and DI2.1 = DI active, 0 = DI inactive. Def/FbEq 7 DI1 DI2 Operation 0 0 No constant speed 1 0 Speed defined by par. 1202 CONST SPEED 1 0 1 Speed defined by par. 1203 CONST SPEED 2 1 1 Speed defined by par. 1204 CONST SPEED 3 DI2,3 See selection DI1,2. 8 DI3,4 DI4,5 DI1,2,3 See selection DI1,2. 9 See selection DI1,2. Actual signals and parameters All parameters No. Name/Value DI3(INV) DI4(INV) DI5(INV) DI1,2(INV) Description Speed defined by parameter 1202 CONST SPEED 1 is activated through inverted digital input DI3. 0 = active, 1 = inactive. Speed defined by parameter 1202 CONST SPEED 1 is activated through inverted digital input DI4. 0 = active, 1 = inactive. Def/FbEq -3 -4 Speed defined by parameter 1202 CONST SPEED 1 is -5 activated through inverted digital input DI5. 0 = active, 1 = inactive. Actual signals and parameters 195 All parameters No. Name/Value 1205 CONST SPEED 4 Description Defines constant speed (or drive output frequency) 4. 0.0…500.0 Hz / Speed in rpm. Output frequency in Hz if parameter 9904 0…30000 rpm MOTOR CTRL MODE setting is SCALAR: FREQ. 1206 CONST Defines constant speed (or drive output frequency) 5. SPEED 5 0.0…500.0 Hz / Speed in rpm. Output frequency in Hz if parameter 9904 0…30000 rpm MOTOR CTRL MODE setting is SCALAR: FREQ. Actual signals and parameters All parameters No. Name/Value 1209 TIMED MODE SEL EXT/CS1/2/3 Description Def/FbEq Selects timed function activated speed. Timed function can CS1/2/3/4 be used to change between the external reference and constant speeds when parameter 1201 CONST SPEED SEL selection is TIMED FUNC 1 … TIMED FUNC 4 or TIMED FUN1&2. When parameter 1201 CONST SPEED SEL = TIMED 1 FUNC 1 … TIMED FUNC 4, this timed function selects an external speed reference or constant speed. Actual signals and parameters 197 All parameters No. Name/Value CS1/2/3/4 Description When parameter 1201 CONST SPEED SEL = TIMED FUNC 1 … TIMED FUNC 4, this timed function selects a constant speed. 1 = timed function active, 0 = timed function inactive. Def/FbEq 2 Timed function 1…4 Operation 0 Speed defined by parameter 1202 CONST SPEED 1 1 Speed defined by parameter 1203 CONST SPEED 2 When parameter 1201 CONST SPEED SEL = TIMED FUN1&2, timed functions 1 and 2 select a constant speed. Actual signals and parameters All parameters No. Name/Value Description Def/FbEq 1302 MAXIMUM AI1 Defines the maximum %-value that corresponds to 100.0% maximum mA/(V) signal for analog input AI1. When used as a reference, the value corresponds to the reference maximum setting. 0…20 mA = 0…100% 4…20 mA = 20…100% -10…10 mA = -50…50% Example: If AI1 is selected as the source for external reference REF1, this value corresponds to the value of parameter 1105 REF1 MAX. -100.0…100. Actual signals and parameters 199 All parameters No. Name/Value Description Def/FbEq 14 RELAY OUTPUTS Status information indicated through relay output, and relay operating delays. Note: Relay outputs 2…4 are available only if the MREL-01 relay output extension module is connected to the drive. See MREL-01 relay output extension module user's manual (3AUA0000035974 [English]). Actual signals and parameters All parameters No. Name/Value Description OVERVOLTAG Alarm/Fault by overvoltage protection function E Def/FbEq 22 DRIVE TEMP Alarm/Fault by drive overtemperature protection function UNDERVOLTA Alarm/Fault by undervoltage protection function GE AI1 LOSS Analog input AI1 signal is lost. 23 24 25 AI2 LOSS Analog input AI2 signal is lost. 26 MOTOR TEMP Alarm/Fault by motor overtemperature protection function. 27 See parameter 3005 MOT THERM PROT. Actual signals and parameters 201 All parameters No. Name/Value Description TIMED FUNC 3 Timed function 3 is active. See parameter group 36 TIMED FUNCTIONS. TIMED FUNC 4 Timed function 4 is active. See parameter group 36 TIMED FUNCTIONS. M.TRIG FAN Cooling fan running time counter is triggered. See parameter group 29 MAINTENANCE TRIG. M.TRIG REV Revolutions counter is triggered. See parameter group 29 MAINTENANCE TRIG. Def/FbEq 39 M.TRIG RUN Run time counter is triggered. Actual signals and parameters All parameters No. Name/Value 1406 RO 2 ON DELAY Description See parameter 1404 RO 1 ON DELAY. Def/FbEq 0.0 s 1407 RO 2 OFF DELAY 1408 RO 3 ON DELAY See parameter 1405 RO 1 OFF DELAY. 0.0 s See parameter 1404 RO 1 ON DELAY. 0.0 s 1409 RO 3 OFF DELAY 1410 RELAY OUTPUT 4 See parameter 1405 RO 1 OFF DELAY. 0.0 s 1413 RO 4 ON DELAY 1414 RO 4 OFF DELAY 15 ANALOG OUTPUTS See parameter 1401 RELAY OUTPUT 1. Actual signals and parameters 203 All parameters No. Name/Value 1505 MAXIMUM AO1 0.0…20.0 mA 1506 FILTER AO1 0.0…10.0 s 16 SYSTEM CONTROLS 1601 RUN ENABLE NOT SEL DI1 DI2 DI3 DI4 DI5 COMM DI1(INV) Description Def/FbEq Defines the maximum value for the analog output signal AO. 20.0 mA See the figure for parameter 1502 AO1 CONTENT MIN. Maximum value 1= 0.1 mA Defines the filter time constant for analog output AO, ie the 0.1 s time within which 63% of a step change is reached. Actual signals and parameters All parameters No. Name/Value NOT SAVED 1603 PASS CODE Description Parameter changes from the control panel are not stored into the permanent memory. To store changed parameter values, set parameter 1607 PARAM SAVE value to SAVE…. Def/FbEq 2 Selects the pass code for the parameter lock (see parameter 1602 PARAMETER LOCK). 0 0…65535 Pass code. Setting 358 opens the lock. The value reverts back to 0 automatically. Actual signals and parameters 205 All parameters No. Name/Value 1605 USER PAR SET CHG NOT SEL DI1 DI2 DI3 DI4 DI5 DI1,2 Description Enables the change of the User parameter set through a digital input. See parameter 9902 APPLIC MACRO. The change is only allowed when the drive is stopped. During the change, the drive will not start. Note: Always save the User parameter set with parameter 9902 after changing any parameter setting, or reperforming the motor identification. Actual signals and parameters All parameters No. Name/Value DI4(INV) DI1,2(INV) Description Def/FbEq See selection DI1(INV). -4 User parameter set selection through inverted digital inputs -7 DI1 and DI2. 1 = DI inactive, 0 =DI active. DI1 1 0 1 DI2 1 1 0 User parameter set User parameter set 1 User parameter set 2 User parameter set 3 DI2,3(INV) See selection DI1,2. -8 DI3,4(INV) See selection DI1,2. -9 See selection DI1,2. Actual signals and parameters 207 All parameters No. Name/Value SAVE… 1608 START ENABLE 1 Description Saving in progress Selects the source for the Start enable 1 signal. Def/FbEq 1 NOT SEL Note: Functionality of the Start enable signal is different from the Run enable signal. Example: External damper control application using Start enable and Run enable. Motor can start only after the damper is fully open. Actual signals and parameters All parameters No. Name/Value COMM Description Def/FbEq Fieldbus interface as the source for the inverted Start 7 enable (Start disable) signal, ie control word 0302 FB CMD WORD 2 bit 18 (bit 19 for Start enable 2). The control word is sent by the fieldbus controller through the fieldbus adapter or embedded fieldbus (Modbus) to the drive. For the control word bits, see section DCU communication profile on page 320. Note: This setting applies only for the DCU profile. Actual signals and parameters 209 All parameters No. Name/Value AUTO ON 18 FREQ IN & TRAN OUT 1801 FREQ INPUT MIN 1802 1803 1804 1805 1806 1807 Description Def/FbEq Automatic fan control. The fan is switched on when the drive 0 is modulating. After the drive has stopped, the fan stays on until the temperature of the drive has dropped below 55 °C. The fan then remains switched off until either the drive is started or the temperature increases above 65 °C. Actual signals and parameters All parameters No. Name/Value 1809 FO CONTENT MIN Description Def/FbEq Defines the minimum frequency output FO signal value. Signal is selected with parameter 1808 FO CONTENT SEL. FO minimum and maximum correspond to 1811 MINIMUM FO and 1812 MAXIMUM FO settings as follows: FO FO 1812 1812 1811 1811 1809 x…x 1810 FO CONTENT MAX x…x 1811 MINIMUM FO 10…16000 Hz 1812 MAXIMUM FO 10…16000 Hz 1813 FILTER FO 0.0…10. Actual signals and parameters 211 All parameters No. Name/Value DI1 DI2 Description Def/FbEq Timer start through digital input DI1. Timer start on the rising 1 edge of digital input DI1. Note: Timer start is not possible when reset is active (parameter 1903 TIMER RESET). See selection DI1. 2 DI3 DI4 DI5 See selection DI1. See selection DI1. See selection DI1. START External start signal, eg start signal through fieldbus 1903 TIMER RESET Selects the source for the timer reset signal. Actual signals and parameters All parameters No. Name/Value DI5 ENABLED 1905 COUNTER LIMIT 0…65535 1906 COUNTER INPUT Description See selection DI1. Counter enabled Def/FbEq 5 6 Defines the counter limit. 1000 Limit value 1=1 Selects the input signal source for the counter. PLS IN(DI 5) PLS IN(DI 5) Digital input DI5 pulses. When a pulse is detected, the counter value increases by 1. ENC W/O DIR Encoder pulse edges. Actual signals and parameters 213 All parameters No. Name/Value RESET 1908 COUNTER RES VAL 0…65535 1909 COUNT DIVIDER Description Reset enabled Defines the value for the counter after reset. Def/FbEq 9 0 Counter value Defines the divider for the pulse counter. 1=1 0 0…12 1910 COUNT DIRECTION DI1(INV) Pulse counter divider N. Every 2N bit is counted. Defines the source for the counter direction selection. 1=1 UP Counter direction selection through inverted digital input DI1. Actual signals and parameters All parameters No. Name/Value DI1 DI2 Description Def/FbEq Start/stop command through digital input DI1. 1 When parameter 1001 EXT1 COMMANDS value is COUNTER STOP: 1 = start. Stop when counter limit defined by parameter 1905 COUNTER LIMIT has been exceeded. When parameter 1001 value is COUNTER START: 1 = stop. Start when counter limit defined by parameter 1905 has been exceeded. See selection DI1. 2 DI3 DI4 DI5 See selection DI1. See selection DI1. See selection DI1. Actual signals and parameters 215 All parameters No. Name/Value 2005 OVERVOLT CTRL DISABLE ENABLE Description Def/FbEq Activates or deactivates the overvoltage control of the ENABLE intermediate DC link. Fast braking of a high inertia load causes the voltage to rise to the overvoltage control limit. To prevent the DC voltage from exceeding the limit, the overvoltage controller automatically decreases the braking torque. Actual signals and parameters All parameters No. Name/Value 2008 MAXIMUM FREQ 0.0…600.0 Hz 2013 MIN TORQUE SEL MIN TORQUE 1 DI1 Description Defines the maximum limit for the drive output frequency. Maximum frequency Selects the minimum torque limit for the drive. Value defined by parameter 2015 MIN TORQUE 1 Def/FbEq E: 50.0 Hz U: 60.0 Hz 1 = 0.1 Hz MIN TORQUE 1 0 Digital input DI1. 0 = parameter 2015 MIN TORQUE 1 value. 1 = parameter 2016 MIN TORQUE 2 value. See selection DI1. Actual signals and parameters 217 All parameters No. Name/Value COMM EXT2 DI1(INV) Description Def/FbEq Fieldbus interface as the source for the torque limit 1/2 7 selection, ie control word 0301 FB CMD WORD 1 bit 15. The control word is sent by the fieldbus controller through the fieldbus adapter or embedded fieldbus (Modbus) to the drive. For the control word bits, see section DCU communication profile on page 320. Actual signals and parameters All parameters No. Name/Value 2021 MAX SPEED SEL Description Maximum speed source for torque control Def/FbEq PAR 2002 PAR 2002 EXT REF 1 21 START/STOP 2101 START FUNCTION Value of parameter 2002 MAXIMUM SPEED Value of signal 0111 EXTERNAL REF 1 Start and stop modes of the motor Selects the motor starting method. 0 1 AUTO DC MAGN AUTO The drive starts the motor instantly from zero frequency if 1 parameter 9904 MOTOR CTRL MODE setting is SCALAR: FREQ. Actual signals and parameters 219 All parameters No. Name/Value Description Def/FbEq TORQ BOOST Torque boost should be selected if a high break-away 4 torque is required. Used only when parameter 9904 MOTOR CTRL MODE setting is SCALAR: FREQ. The drive pre-magnetizes the motor with DC current before the start. The pre-magnetizing time is defined by parameter 2103 DC MAGN TIME. Torque boost is applied at start. Actual signals and parameters All parameters No. Name/Value Description Def/FbEq SPEED COMP Speed compensation is used for constant distance braking if 4 FWD the direction of rotation is forward. Speed difference (between used speed and maximum speed) is compensated by running the drive with current speed before the motor is stopped along a ramp. See section Acceleration and deceleration ramps on page 139. If the direction of rotation is reverse, the drive is stopped along a ramp. Actual signals and parameters 221 All parameters No. Name/Value DC HOLD Description Def/FbEq DC hold function active. DC hold is not possible if parameter 1 9904 MOTOR CTRL MODE setting is SCALAR: FREQ. When both the reference and the motor speed drop below the value of parameter 2105 DC HOLD SPEED, the drive will stop generating sinusoidal current and start to inject DC into the motor. The current is set by parameter 2106 DC CURR REF. Actual signals and parameters All parameters No. Name/Value Description 2108 START INHIBIT Sets the Start inhibit function on or off. If the drive is not actively started and running, the Start inhibit function ignores a pending start command in any of the following situations and a new start command is required: Def/FbEq OFF • a fault is reset. • Run enable signal activates while the start command is active. See parameter 1601 RUN ENABLE. • control mode changes from local to remote. Actual signals and parameters 223 All parameters No. Name/Value 2112 ZERO SPEED DELAY Description Def/FbEq Defines the delay for the Zero speed delay function. The 0.0 = function is useful in applications where a smooth and quick NOT SEL restarting is essential. During the delay the drive knows accurately the rotor position. No Zero speed delay With Zero speed delay Speed Speed Speed controller switched off: Motor coasts to stop. Zero speed t Speed controller remains live. Actual signals and parameters All parameters No. Name/Value COMM Description Def/FbEq Fieldbus interface as the source for ramp pair 1/2 selection, 7 ie control word 0301 FB CMD WORD 1 bit 10. The control word is sent by the fieldbus controller through the fieldbus adapter or embedded fieldbus (Modbus) to the drive. For the control word bits, see section DCU communication profile on page 320. Note: This setting applies only for the DCU profile. Actual signals and parameters 225 All parameters No. Name/Value 2203 DECELER TIME 1 Description Def/FbEq Defines the deceleration time 1, ie the time required for the 5.0 s speed to change from the value defined by parameter 2008 MAXIMUM FREQ (in scalar control) / 2002 MAXIMUM SPEED (in vector control) to zero. The control mode is selected by parameter 9904 MOTOR CTRL MODE. • If the speed reference decreases slower than the set deceleration rate, the motor speed will follow the reference signal. Actual signals and parameters All parameters No. Name/Value 2205 ACCELER TIME 2 0.0…1800.0 s 2206 DECELER TIME 2 Description Def/FbEq Defines the acceleration time 2, ie the time required for the 60.0 s speed to change from zero to the speed defined by parameter 2008 MAXIMUM FREQ (in scalar control) / 2002 MAXIMUM SPEED (in vector control). The control mode is selected by parameter 9904 MOTOR CTRL MODE. See parameter 2202 ACCELER TIME 1. Acceleration time 2 is used also as jogging acceleration time. Actual signals and parameters 227 All parameters No. Name/Value DI1(INV) DI2(INV) DI3(INV) Description Inverted digital input DI1. 0 = ramp input is forced to zero. Ramp output will ramp to zero according to the used ramp time. See selection DI1(INV). See selection DI1(INV). -2 -3 DI4(INV) DI5(INV) See selection DI1(INV). See selection DI1(INV). -4 -5 23 SPEED CONTROL 2301 PROP GAIN Def/FbEq -1 Speed controller variables. See section Speed controller tuning on page 142. Actual signals and parameters All parameters No. Name/Value Description Def/FbEq 2302 INTEGRATION Defines an integration time for the speed controller. The 0.50 s TIME integration time defines the rate at which the controller output changes when the error value is constant. The shorter the integration time, the faster the continuous error value is corrected. Too short an integration time makes the control unstable. Actual signals and parameters 229 All parameters No. Name/Value 2303 DERIVATION TIME Description Def/FbEq Defines the derivation time for the speed controller. 0 ms Derivative action boosts the controller output if the error value changes. The longer the derivation time, the more the speed controller output is boosted during the change. If the derivation time is set to zero, the controller works as a PI controller, otherwise as a PID controller. Actual signals and parameters All parameters No. Name/Value Description Def/FbEq 2304 ACC Defines the derivation time for acceleration/(deceleration) 0.00 s COMPENSATI compensation. In order to compensate inertia during ON acceleration, a derivative of the reference is added to the output of the speed controller. The principle of a derivative action is described for parameter 2303 DERIVATION TIME. Actual signals and parameters 231 All parameters No. Name/Value 2402 TORQ RAMP DOWN Description Defines the torque reference ramp down time, ie the minimum time for the reference to decrease from the nominal motor torque to zero. 0.00…120.00 s Time 25 CRITICAL Speed bands within which the drive is not allowed to SPEEDS operate. 2501 CRIT SPEED Activates/deactivates the critical speeds function. The SEL critical speed function avoids specific speed ranges. Actual signals and parameters All parameters No. Name/Value Description 2506 CRIT SPEED 3 See parameter 2502 CRIT SPEED 1 LO. LO 0.0…500.0 Hz / See parameter 2502. 0…30000 rpm 2507 CRIT SPEED 3 See parameter 2503 CRIT SPEED 1 HI. HI 0.0…500.0 Hz / See parameter 2503. 0…30000 rpm 26 MOTOR CONTROL 2601 FLUX OPT ENABLE OFF ON 2602 FLUX BRAKING OFF ON Def/FbEq 0.0 Hz / 1 rpm 1 = 0.1 Hz / 1 rpm 0.0 Hz / 1 rpm 1 = 0.1 Hz / 1 rpm Motor control variables Activates/deactivates the flux optimization function. Actual signals and parameters 233 All parameters No. Name/Value 2603 IR COMP VOLT Description Def/FbEq Defines the output voltage boost at zero speed (IR Type compensation). The function is useful in applications with a dependent high break-away torque when vector control cannot be applied. To prevent overheating, set IR compensation voltage as low as possible. Note: The function can be used only when parameter 9904 MOTOR CTRL MODE setting is SCALAR: FREQ. The figure below illustrates the IR compensation. Actual signals and parameters All parameters No. Name/Value 2606 SWITCHING FREQ Description Defines the switching frequency of the drive. Higher switching frequency results in lower acoustic noise. In multimotor systems, do not change the switching frequency from the default value. See also parameter 2607 SWITCH FREQ CTRL and section Switching frequency derating, I2N on page 360. Actual signals and parameters 235 All parameters No. Name/Value ON (LOAD) Description Def/FbEq The drive is started with 4 kHz switching frequency to gain 2 maximum output during the start. After start-up, the switching frequency is controlled towards the selected value (parameter 2607 SWITCH FREQ CTRL) if the output current or the temperature allows. This selection provides adaptive switching frequency control. Adaptation decreases the output performance in some cases. Actual signals and parameters All parameters No. Name/Value 2610 USER DEFINED U1 Def/FbEq 19% of UN 2611 1=1V 10.0 Hz 2612 2613 2614 Description Defines the first voltage point of the custom U/f curve at the frequency defined by parameter 2611 USER DEFINED F1. See section Custom U/f ratio on page 141. 0…120% of UN V Voltage USER Defines the first frequency point of the custom U/f curve. DEFINED F1 0.0…500. Actual signals and parameters 237 All parameters No. Name/Value 2621 SMOOTH START Description Def/FbEq Selects the forced current vector rotation mode at low NO speeds. When the smooth start mode is selected, the rate of acceleration is limited by the acceleration and deceleration ramp times (parameters 2202 and 2203). If the process driven by the permanent magnet motor has high inertia, slow ramp times are recommended. Can be used for permanent magnet motors only. Actual signals and parameters All parameters No. Name/Value 2904 REVOLUTION ACT Description Defines the actual value for the motor revolution counter. When parameter 2903 REVOLUTION TRIG has been set to a non zero value, the counter starts. When the actual value of the counter exceeds the value defined by parameter 2903, a maintenance notice is displayed on the panel. 0…65535 Mrev Millions of revolutions. Parameter is reset by setting it to zero. Actual signals and parameters 239 All parameters No. Name/Value FAULT CONST SP 7 Description Def/FbEq The drive trips on fault AI1 LOSS (0007) / AI2 LOSS (0008) 1 and the motor coasts to stop. Fault limit is defined by parameter 3021 AI1 FAULT LIMIT / 3022 AI2 FAULT LIMIT. The drive generates alarm AI1 LOSS (2006) / AI2 LOSS 2 (2007) and sets the speed to the value defined by parameter 1208 CONST SPEED 7. Alarm limit is defined by parameter 3021 AI1 FAULT LIMIT / 3022 AI2 FAULT LIMIT. Actual signals and parameters All parameters No. Name/Value DI2 DI3 Description See selection DI1. See selection DI1. Def/FbEq 2 3 DI4 DI5 DI1(INV) 4 5 -1 DI2(INV) See selection DI1. See selection DI1. External fault indication through inverted digital input DI1. 0: Fault trip on EXT FAULT 1 (0014). Motor coasts to stop. 1: No external fault. See selection DI1(INV). DI3(INV) DI4(INV) DI5(INV) See selection DI1(INV). See selection DI1(INV). See selection DI1(INV). Actual signals and parameters 241 All parameters No. Name/Value 3007 MOT LOAD CURVE Description Def/FbEq Defines the load curve together with parameters 3008 100% ZERO SPEED LOAD and 3009 BREAK POINT FREQ. With the default value 100%, motor overload protection is functioning when the constant current exceeds 127% of the parameter 9906 MOTOR NOM CURR value. Actual signals and parameters All parameters No. Name/Value Description Def/FbEq 3009 BREAK POINT Defines the load curve together with parameters 3007 MOT 35 Hz FREQ LOAD CURVE and 3008 ZERO SPEED LOAD. Example: Thermal protection trip times when parameters 3006…3008 have default values. IO = Output current IN = Nominal motor current fO = Output frequency fBRK = Break point frequency A = Trip time IO/IN A 3.5 3.0 60 s 2.5 90 s 2.0 180 s 300 s 1.5 600 s ∞ 1.0 0.5 fO/fBRK 0 0 1…250 Hz 0. Actual signals and parameters 243 All parameters No. Name/Value 3010 STALL FUNCTION Description Selects how the drive reacts to a motor stall condition. The protection wakes up if the drive has operated in a stall region (see the figure below) longer than the time set by parameter 3012 STALL TIME. Def/FbEq NOT SEL In vector control the user defined limit = 2017 MAX TORQUE 1 / 2018 MAX TORQUE 2 (applies for positive and negative torques). In scalar control the user defined limit = 2003 MAX CURRENT. Actual signals and parameters All parameters No. Name/Value FAULT Def/FbEq 1 ALARM 3014 UNDERLOAD TIME Description The drive trips on fault UNDERLOAD (0017) and the motor coasts to stop. Note: Set parameter value to FAULT only after the drive ID run is performed! If FAULT is selected, the drive may generate an UNDERLOAD fault during ID run. The drive generates alarm UNDERLOAD (2011). Defines the time limit for the underload function. See parameter 3013 UNDERLOAD FUNC. Actual signals and parameters 245 All parameters No. Name/Value Description Def/FbEq 3017 EARTH FAULT Selects how the drive reacts when an earth (ground) fault is ENABLE detected in the motor or the motor cable. Note: Disabling earth (ground) fault may void the warranty. DISABLE ENABLE START ONLY 3018 COMM FAULT FUNC NOT SEL FAULT CONST SP 7 LAST SPEED 3019 COMM FAULT TIME 0.0…600.0 s 3021 AI1 FAULT LIMIT No action The drive trips on fault EARTH FAULT (0016) when the earth fault is detected during run. Actual signals and parameters All parameters No. Name/Value Description 3023 WIRING FAULT Selects how the drive reacts when incorrect input power and motor cable connection is detected (ie the input power cable is connected to the motor connection of the drive). Note: Disabling wiring fault (ground fault) may void the warranty. DISABLE No action ENABLE The drive trips on fault OUTP WIRING (0035). Actual signals and parameters 247 All parameters No. Name/Value 0…5 3102 TRIAL TIME Description Number of the automatic resets Defines the time for the automatic fault reset function. See parameter 3101 NR OF TRIALS. 1.0…600.0 s 3103 DELAY TIME Time 1 = 0.1 s Defines the time that the drive will wait after a fault before 0.0 s attempting an automatic reset. See parameter 3101 NR OF TRIALS. If delay time is set to zero, the drive resets immediately. 0.0…120. Actual signals and parameters All parameters No. Name/Value 32 SUPERVISION 3201 SUPERV 1 PARAM Description Signal supervision. Supervision status can be monitored with relay or transistor output. See parameter groups 14 RELAY OUTPUTS and 18 FREQ IN & TRAN OUT. Selects the first supervised signal. Supervision limits are defined by parameters 3202 SUPERV 1 LIM LO and 3203 SUPERV 1 LIM HI. Example 1: If 3202 SUPERV 1 LIM LO < 3203 SUPERV 1 LIM HI Case A = 1401 RELAY OUTPUT 1 value is set to SUPRV1 OVER. Actual signals and parameters 249 All parameters No. Name/Value Description Example 2: If 3202 SUPERV 1 LIM LO > 3203 SUPERV 1 LIM HI Def/FbEq The lower limit 3203 SUPERV 1 LIM HI remains active until the supervised signal exceeds the higher limit 3202 SUPERV 1 LIM LO, making it the active limit. The new limit remains active until the supervised signal drops below the lower limit 3203 SUPERV 1 LIM HI, making it the active limit. Case A = 1401 RELAY OUTPUT 1 value is set to SUPRV1 OVER. Actual signals and parameters All parameters No. Name/Value Description 3205 SUPERV 2 LIM Defines the low limit for the second supervised signal LO selected by parameter 3204 SUPERV 2 PARAM. Supervision wakes up if the value is below the limit. x…x Setting range depends on parameter 3204 setting. 3206 SUPERV 2 LIM Defines the high limit for the second supervised signal HI selected by parameter 3204 SUPERV 2 PARAM. Supervision wakes up if the value is above the limit. Actual signals and parameters 251 All parameters No. Name/Value 0000…FFFF hex 34 PANEL DISPLAY 3401 SIGNAL1 PARAM Description Eg 400E hex Def/FbEq Selection of actual signals to be displayed on the panel Selects the first signal to be displayed on the control panel in the Output mode. Assistant control panel LOC 0137 0138 0139 3404 3405 15.0Hz 15.0 Hz 3.7 A 17.3 % DIR 0 = NOT SELECTED 101…180 3402 SIGNAL1 MIN 103 00:00 MENU Parameter index in group 01 OPERATING DATA. Eg 102 = 1 = 1 0102 SPEED. Actual signals and parameters All parameters No. Name/Value Description 3404 OUTPUT1 DSP Defines the format for the displayed signal (selected by FORM parameter 3401 SIGNAL1 PARAM). +/-0 Signed/Unsigned value. Unit is selected by parameter 3405 OUTPUT1 UNIT. +/-0.0 Example: PI (3.14159) +/-0.00 +/-0.000 +0 +0.0 +0.00 +0.000 BAR METER DIRECT 3404 value +/-0 +/-0.0 +/-0.00 +/-0.000 +0 +0.0 +0.00 +0.000 Display +3 + 3.1 + 3.14 + 3.142 3 3.1 3.14 3. Actual signals and parameters 253 All parameters No. Actual signals and parameters All parameters No. Actual signals and parameters 255 All parameters No. Name/Value 3409 SIGNAL2 MIN Description Defines the minimum value for the signal selected by parameter 3408 SIGNAL2 PARAM. See parameter 3402 SIGNAL1 MIN. x…x Setting range depends on parameter 3408 setting. 3410 SIGNAL2 MAX Defines the maximum value for the signal selected by parameter 3408 SIGNAL2 PARAM. See parameter 3402 SIGNAL1 MIN. x…x Setting range depends on parameter 3408 setting. Actual signals and parameters All parameters No. Name/Value Description 3420 OUTPUT3 MIN Sets the minimum display value for the signal selected by parameter 3415 SIGNAL3 PARAM. See parameter 3402 SIGNAL1 MIN. x…x Setting range depends on parameter 3415 SIGNAL3 PARAM setting. 3421 OUTPUT3 Sets the maximum display value for the signal selected by MAX parameter 3415 SIGNAL3 PARAM. See parameter 3402 SIGNAL1 MIN. x…x Setting range depends on parameter 3415 setting. Actual signals and parameters 257 All parameters No. Name/Value PTC Description Def/FbEq The function is active. The temperature is supervised using 4 one PTC sensor. Analog output AO feeds constant current through the sensor. The resistance of the sensor increases sharply as the motor temperature rises over the PTC reference temperature (Tref), as does the voltage over the resistor. The temperature measurement function reads the voltage through analog input AI1/2 and converts it into ohms. Actual signals and parameters All parameters No. Name/Value DI3 DI4 DI5 3503 ALARM LIMIT x…x 3504 FAULT LIMIT Description Digital input DI3. Used when parameter 3501 SENSOR TYPE value is set to THERM(0)/THERM(1). Digital input DI4. Used when parameter 3501 SENSOR TYPE value is set to THERM(0)/THERM(1). Digital input DI5. Used when parameter 3501 SENSOR TYPE value is set to THERM(0)/THERM(1). Defines the alarm limit for motor temperature measurement. Actual signals and parameters 259 All parameters No. Name/Value Description 3602 START TIME 1 Defines the daily start time 1. The time can be changed in 2-second steps. 00:00:00… hours:minutes:seconds. 23:59:58 Example: If parameter value is set to 07:00:00, timed function 1 is activated at 7:00 (7 a.m). Def/FbEq 00:00:00 3603 STOP TIME 1 00:00:00 00:00:00… 23:59:58 3604 START DAY 1 MONDAY TUESDAY WEDNESDAY Defines the daily stop time 1. The time can be changed in 2-second steps. Actual signals and parameters All parameters No. Name/Value 3616 START DAY 4 3617 STOP DAY 4 3622 BOOSTER SEL NOT SEL DI1 DI2 DI3 DI4 DI5 DI1(INV) DI2(INV) DI3(INV) DI4(INV) DI5(INV) 3623 BOOSTER TIME 00:00:00… 23:59:58 Description See parameter 3603 STOP TIME 1. See parameter 3604 START DAY 1. Def/FbEq See parameter 3604 START DAY 1. See parameter 3605 STOP DAY 1. See parameter 3605 STOP DAY 1. Selects the source for the booster activation signal. Actual signals and parameters 261 All parameters No. Actual signals and parameters All parameters No. Name/Value Description Def/FbEq 4002 INTEGRATION Defines the integration time for the process PID1 controller. 60.0 s TIME The integration time defines the rate at which the controller output changes when the error value is constant. The shorter the integration time, the faster the continuous error value is corrected. Too short an integration time makes the control unstable. Actual signals and parameters 263 All parameters No. Name/Value 4003 DERIVATION TIME Description Def/FbEq Defines the derivation time for the process PID controller. 0.0 s Derivative action boosts the controller output if the error value changes. The longer the derivation time, the more the speed controller output is boosted during the change. If the derivation time is set to zero, the controller works as a PI controller, otherwise as a PID controller. Actual signals and parameters All parameters No. Name/Value 0…4 Description Example: PI (3.141593) 4007 value 0 1 2 3 4 4008 0% VALUE Def/FbEq 1=1 Entry 00003 00031 00314 03142 31416 Display 3 3.1 3.14 3.142 3.1416 Defines together with parameter 4009 100% VALUE the scaling applied to the PID controller’s actual values. Units (4006) Scale (4007) 0. Actual signals and parameters 265 All parameters No. Name/Value DI3U,4D(NC) AI1+AI2 AI1*AI2 AI1-AI2 AI1/AI2 INTERNAL DI4U,5D(NC) FREQ INPUT SEQ PROG OUT 4011 INTERNAL SETPNT x…x 4012 SETPOINT MIN Description Digital input DI3: Reference increase. Digital input DI4: Reference decrease. The program stores the active reference (not reset by a stop command). The reference is not saved if the control source is changed from EXT1 to EXT2, from EXT2 to EXT1 or from LOC to REM. Actual signals and parameters All parameters No. Name/Value 4014 FBK SEL Description Def/FbEq Selects the process actual value (feedback signal) for the ACT1 process PID controller: The sources for the variables ACT1 and ACT2 are further defined by parameters 4016 ACT1 INPUT and 4017 ACT2 INPUT. Actual signals and parameters 267 All parameters No. Name/Value 4018 ACT1 MINIMUM Description Sets the minimum value for ACT1. Scales the source signal used as the actual value ACT1 (defined by parameter 4016 ACT1 INPUT). For parameter 4016 values 6 (COMM ACT 1) and 7 (COMM ACT 2) scaling is not done. Par 4016 1 2 3 4 5 Source Analog input 1 Analog input 2 Current Torque Power Source min. 1301 MINIMUM AI1 1304 MINIMUM AI2 0 -2 · nominal torque -2 · nominal power Def/FbEq 0% Source max. Actual signals and parameters All parameters No. Name/Value DI1 Description Def/FbEq The function is activated/deactivated through digital input 1 DI1.1 = activation, 0 = deactivation. The internal sleep criteria set by parameters 4023 PID SLEEP LEVEL and 4025 WAKE-UP DEV are not effective. The sleep start and stop delay parameters 4024 PID SLEEP DELAY and 4026 WAKE-UP DELAY are effective. DI2 DI3 See selection DI1. See selection DI1. 2 3 DI4 DI5 INTERNAL See selection DI1. See selection DI1. Actual signals and parameters 269 All parameters No. Name/Value 4023 PID SLEEP LEVEL Description Defines the start limit for the sleep function. If the motor speed is below a set level (4023) longer than the sleep delay (4024), the drive shifts to the sleeping mode: The motor is stopped and the control panel shows alarm message PID SLEEP (2018). Parameter 4022 SLEEP SELECTION must be set to INTERNAL. Wake-up delay (4026) PID process feedback PID ref Def/FbEq 0. Actual signals and parameters All parameters No. Name/Value Description Def/FbEq 4025 WAKE-UP DEV Defines the wake-up deviation for the sleep function. The 0 drive wakes up if the process actual value deviation from the PID reference value exceeds the set wake-up deviation (4025) longer than the wake-up delay (4026). Wake-up level depends on parameter 4005 ERROR VALUE INV settings. If parameter 4005 is set to 0: Wake-up level = PID reference (4010) - Wake-up deviation (4025). Actual signals and parameters 271 All parameters No. Name/Value DI2(INV) DI3(INV) Description See selection DI1(INV). See selection DI1(INV). Def/FbEq -2 -3 DI4(INV) DI5(INV) See selection DI1(INV). See selection DI1(INV). -4 -5 41 PROCESS PID SET 2 4101 4102 4103 4104 4105 4106 4107 4108 4109 4110 Process PID (PID1) control parameter set 2. See section PID control on page 149. GAIN See parameter 4001 GAIN. INTEGRATION See parameter 4002 INTEGRATION TIME. Actual signals and parameters All parameters No. Name/Value 4125 WAKE-UP DEV 4126 WAKE-UP DELAY 42 EXT / TRIM PID Description See parameter 4025 WAKE-UP DEV. See parameter 4026 WAKE-UP DELAY. 4204 PID DERIV FILTER 4205 ERROR VALUE INV See parameter 4004 PID DERIV FILTER. 4206 4207 4208 4209 4210 See parameter 4006 UNITS. See parameter 4007 UNIT SCALE. See parameter 4008 0% VALUE. See parameter 4009 100% VALUE. See parameter 4010 SET POINT SEL. Def/FbEq External/Trim PID (PID2) control. Actual signals and parameters 273 All parameters No. Name/Value DI3 DI4 Description See selection DI1. See selection DI1. Def/FbEq 3 4 DI5 DRIVE RUN ON See selection DI1. Activation at drive start. Start (drive running) = active. Activation at drive power-up. Power-up (drive powered) = active. 5 7 8 TIMED FUNC 1 Activation by a timed function. Timed function 1 active = PID 9 control active. See parameter group 36 TIMED FUNCTIONS. TIMED FUNC 2 See selection TIMED FUNC 1. Actual signals and parameters All parameters No. Name/Value 4233 TRIM SELECTION SPEED/FREQ TORQUE 43 MECH BRK CONTROL 4301 BRAKE OPEN DLY 0.00…2.50 s 4302 BRAKE OPEN LVL 0.0…180.0% 4303 BRAKE CLOSE LVL 0.0…100.0% 4304 FORCED OPEN LVL Description Selects whether the trimming is used for correcting the speed or torque reference. See section Reference trimming on page 129. Speed reference trimming Torque reference trimming (only for REF2 (%)) Control of a mechanical brake. Actual signals and parameters 275 All parameters No. Name/Value 0 = NOT SEL 0…10000 ms 4306 RUNTIME FREQ LVL Description magnetizing time. If parameter value is set to zero, the function is disabled. Defines the brake close speed. When frequency falls below the set level during run, the brake is closed. The brake is reopened when the requirements set by parameters 4301…4305 are met. Def/FbEq 1 = 1 ms 0.0 = NOT SEL 0.0 = NOT SEL Value in percent of the maximum frequency (in scalar 1 = 0.1% 0.0…100. Actual signals and parameters All parameters No. Name/Value 51 EXT COMM MODULE Description Def/FbEq The parameters need to be adjusted only when a fieldbus adapter module (optional) is installed and activated by parameter 9802 COMM PROT SEL. For more details on the parameters, refer to the manual of the fieldbus module and chapter Fieldbus control with fieldbus adapter on page 325. These parameter settings will remain the same even though the macro is changed. Actual signals and parameters 277 All parameters No. Name/Value TIME OUT CONFIG ERROR Description Def/FbEq A time-out has occurred in the communication between the 2 adapter and the drive. Adapter configuration error: The major or minor revision 3 code of the common program revision in the fieldbus adapter module is not the revision required by the module (see parameter 5132 FBA CPI FW REV) or mapping file upload has failed more than three times. OFF-LINE ON-LINE RESET Adapter is off-line. Actual signals and parameters All parameters No. Name/Value 8 EVEN 1 8 ODD 1 5204 OK MESSAGES 0…65535 5205 PARITY ERRORS 0…65535 Description 8 data bits, even parity indication bit, one stop bit 8 data bits, odd parity indication bit, one stop bit Def/FbEq 2 3 Number of valid messages received by the drive. During normal operation, this number increases constantly. Number of messages Number of characters with a parity error received from the Modbus link. Actual signals and parameters 279 All parameters No. Name/Value 8 NONE 2 8 EVEN 1 Description No parity bit, two stop bits, 8 data bits Even parity indication bit, one stop bit, 8 data bits Def/FbEq 1 2 Odd parity indication bit, one stop bit, 8 data bits Selects the communication profile. See section Communication profiles on page 315. Actual signals and parameters All parameters No. Name/Value 5318 EFB PAR 18 0…65535 5319 EFB PAR 19 0000…FFFF hex Description For Modbus: Sets an additional delay before the drive begins transmitting response to the master request. Delay in milliseconds ABB drives profile (ABB DRV LIM or ABB DRV FULL) Control word. Read only copy of the fieldbus Control word. ABB drives profile (ABB DRV LIM or ABB DRV FULL) Status word. Read only copy of the fieldbus Status word. Actual signals and parameters 281 All parameters No. Name/Value 1…6 Description Control and status data words 5501 setting 1 2 3 4 5 6 101…9999 5502 FBA DATA OUT 2 … … 5510 FBA DATA OUT 10 84 SEQUENCE PROG 8401 SEQ PROG ENABLE DISABLED EXT2 EXT1 EXT1&EXT2 ALWAYS Def/FbEq Data word Control word REF1 REF2 Status word Actual value 1 Actual value 2 Drive parameter See 5501 FBA DATA OUT 1. … See 5501 FBA DATA OUT 1. Sequence programming. See section Sequence programming on page 166. Actual signals and parameters All parameters No. Name/Value 8402 SEQ PROG START DI1(INV) DI2(INV) DI3(INV) DI4(INV) DI5(INV) NOT SEL DI1 Description Selects the source for the Sequence programming activation signal. When Sequence programming is activated, the programming starts from the previously used state. If Sequence programming activation signal is lost, the Sequence programming is stopped and all timers and outputs (RO/TO/AO) are set to zero. Actual signals and parameters 283 All parameters No. Name/Value DI1(INV) DI2(INV) Description Def/FbEq Pause signal through inverted digital input DI1. 0 = active, 1 -1 = inactive. See selection DI1(INV). -2 DI3(INV) DI4(INV) DI5(INV) See selection DI1(INV). See selection DI1(INV). See selection DI1(INV). -3 -4 -5 NOT SEL DI1 No pause signal Pause signal through digital input DI1. 1 = active, 0 = inactive. See selection DI1. See selection DI1. Actual signals and parameters All parameters No. Name/Value STATE 5 STATE 6 Description State is forced to state 5. State is forced to state 6. Def/FbEq 5 6 7 8 NOT SEL DI1(INV) State is forced to state 7. State is forced to state 8. Defines the source for the logic value 1. Logic value 1 is compared to logic value 2 as defined by parameter 8407 SEQ LOGIC OPER 1. Logic operation values are used in state transitions. See parameter 8425 ST1 TRIG TO ST 2 / 8426 ST1 TRIG TO ST N selection LOGIC VAL. Actual signals and parameters 285 All parameters No. Name/Value NOT SEL AND OR XOR 8408 SEQ LOGIC VAL 2 Description Logic value 1 (no logic comparison) Logic function: AND Def/FbEq 0 1 Logic function: OR Logic function: XOR See parameter 8406 SEQ LOGIC VAL 1. 2 3 NOT SEL NOT SEL See parameter 8406. Selects the operation between logic value 3 and the result of the first logic operation defined by parameter 8407 SEQ LOGIC OPER 1. Actual signals and parameters All parameters No. Name/Value ST1 TO N Description From state 1 to state n. State n is defined by parameter 8427 ST1 STATE N. From state 2 to state n. State n is defined by parameter 8427 ST1 STATE N. From state 3 to state n. State n is defined by parameter 8427 ST1 STATE N. From state 4 to state n. State n is defined by parameter 8427 ST1 STATE N. Def/FbEq 9 ST5 TO N From state 5 to state n. State n is defined by parameter 8427 ST1 STATE N. Actual signals and parameters 287 All parameters No. Name/Value STATE 7 STATE 8 SEQ PROG RST 8420 ST1 REF SEL COMM AI1/AI2 AI1-AI2 AI1*AI2 AI1+AI2 DI4U,5D DI3U,4D Description Reset during state transition to state 7. Counter is reset, when the state has been reached. Reset during state transition to state 8. Counter is reset, when the state has been reached. Reset signal source defined by parameter 8404 SEQ PROG RESET Selects the source for the Sequence programming state 1 reference. Actual signals and parameters All parameters No. Name/Value DRIVE STOP START FRW START REV 8422 ST1 RAMP -0.2/-0.1/ 0.0…1800.0 s 8423 ST1 OUT CONTROL Description Drive coast or ramps to stop depending on parameter 2102 STOP FUNCTION setting. Direction or rotation is fixed to forward. If the drive is not already running, it is started according to parameter 2101 START FUNCTION settings. Direction or rotation is fixed to reverse. Actual signals and parameters 289 All parameters No. Name/Value AO=0 0.1…100.0% Description Def/FbEq Analog output value is set to zero. Relay and transistor 0.0 outputs are frozen to the previously set value. Value written to signal 0170 SEQ PROG AO VAL. Value can be connected to control analog output AO by setting parameter 1501 AO1 CONTENT SEL value to 170 (ie signal 0170 SEQ PROG AO VAL). AO value is frozen to this value until it is zeroed. 8424 ST1 CHANGE DLY Defines the delay time for state 1. Actual signals and parameters All parameters No. Name/Value Description AI1LO1 ORDI5 State change when AI1 value < par. 8412 SEQ VAL 1 LOW value or when DI5 is active. AI2HI1 ORDI5 State change when AI2 value > par. 8411 SEQ VAL 1 HIGH value or when DI5 is active. AI 1 LOW 2 State change when AI1 value < par. 8414 SEQ VAL 2 LOW value. AI 1 HIGH 2 State change when AI1 value > par. 8413 SEQ VAL 2 HIGH value. Def/FbEq 12 13 14 15 AI 2 LOW 2 State change when AI2 value < par. Actual signals and parameters 291 All parameters No. Name/Value Description AI2LO2 ORDLY State change when AI2 value < par. 8414 SEQ VAL 2 LOW value or after delay time defined by parameter 8424 ST1 CHANGE DLY has elapsed. SUPRV1 Logic value according to supervision parameters OVER 3201…3203. See parameter group 32 SUPERVISION. SUPRV2 Logic value according to supervision parameters OVER 3204…3206. See parameter group 32 SUPERVISION. SUPRV3 Logic value according to supervision parameters OVER 3207…3209. Actual signals and parameters All parameters No. Name/Value AT SETPOINT AI1 L1 & DI5 AI2 L2 & DI5 AI1 H1 & DI5 AI2 H2 & DI5 Description State change when drive output frequency/speed equals the reference value (= is within tolerance limits, ie the error is less than or equal to 1% of the maximum reference). State change when AI1 value < par. 8412 SEQ VAL 1 LOW and when DI5 is active. State change when AI2 value < par. 8414 SEQ VAL 2 LOW value and when DI5 is active. Actual signals and parameters 293 All parameters No. Name/Value COMM VAL1 #2 Description 0135 COMM VALUE 1 bit 2. 1 = state change. Def/FbEq 72 COMM VAL1 #3 COMM VAL1 #4 0135 COMM VALUE 1 bit 3. 1 = state change. 73 0135 COMM VALUE 1 bit 4. 1 = state change. 74 COMM VAL1 #5 COMM VAL1 #6 COMM VAL1 #7 0135 COMM VALUE 1 bit 5. 1 = state change. 75 0135 COMM VALUE 1 bit 6. 1 = state change. 76 0135 COMM VALUE 1 bit 7. 1 = state change. Actual signals and parameters All parameters No. Name/Value 98 OPTIONS 9802 COMM PROT SEL Description External serial communication activation Activates the external serial communication and selects the interface. NOT SEL No communication STD MODBUS Embedded fieldbus. Interface: EIA-485 provided by optional FMBA-01 Modbus adapter connected to drive terminal X3. See chapter Fieldbus control with embedded fieldbus on page 301. Actual signals and parameters 295 All parameters No. Actual signals and parameters All parameters No. Name/Value Description 9903 MOTOR TYPE Selects the motor type. Cannot be changed while the drive is running. AM PMSM Asynchronous motor. Three-phase AC voltage-supplied induction motor with squirrel cage rotor. Permanent magnet motor. Three-phase AC voltagesupplied synchronous motor with permanent magnet rotor and sinusoidal back emf voltage. 9904 MOTOR CTRL Selects the motor control mode. Actual signals and parameters 297 All parameters No. Name/Value 9905 MOTOR NOM VOLT Description Defines the nominal motor voltage. For asynchronous motors, must be equal to the value on the motor rating plate. For permanent magnet motors, the nominal voltage is the back emf voltage at nominal speed. If the voltage is given as voltage per rpm, eg 60 V per 1000 rpm, the voltage for 3000 rpm nominal speed is 3 · 60 V = 180 V. Actual signals and parameters All parameters No. Name/Value 9910 ID RUN OFF/IDMAGN ON Description Def/FbEq This parameter controls a self-calibration process called the OFF/IDM AGN Motor ID run. During this process, the drive operates the motor and makes measurements to identify motor characteristics and create a model used for internal calculations. 0 The Motor ID run process is not run. Identification magnetization is performed, depending on parameter 9904 MOTOR CTRL MODE. Actual signals and parameters 299 All parameters No. Name/Value Description 9913 MOTOR POLE Calculated motor pole pair number (calculation is based on PAIRS parameter 9907 MOTOR NOM FREQ and 9908 MOTOR NOM SPEED values). Read-only 9914 PHASE Inverts two phases in the motor cable. This changes the INVERSION direction of the motor rotation without having to exchange the positions of two motor cable phase conductors at the drive output terminals or at the motor connection box. Actual signals and parameters Fieldbus control with embedded fieldbus 301 Fieldbus control with embedded fieldbus What this chapter contains The chapter describes how the drive can be controlled by external devices over a communication network using embedded fieldbus. System overview The drive can be connected to an external control system through a fieldbus adapter or embedded fieldbus. For fieldbus adapter control, see chapter Fieldbus control with fieldbus adapter on page 325. The embedded fieldbus supports Modbus RTU protocol. Fieldbus control with embedded fieldbus Fieldbus controller Fieldbus Other devices Drive RS-232 1) panel connector X3 FMBA-01 Modbus adapter EIA-485 1) X1 Data flow Control word (CW) References Status word (SW) Actual values Parameter R/W requests/responses 1) Embedded fieldbus (Modbus) connection is either RS-232 or EIA-485. Fieldbus control with embedded fieldbus 303 Setting up communication through the embedded Modbus Before configuring the drive for fieldbus control, the FMBA-01 Modbus adapter (if used) must be mechanically and electrically installed according to the instructions given in section Attach the optional fieldbus module on page 35, and the module manual. The communication through the fieldbus link is initialized by setting parameter 9802 COMM PROT SEL to STD MODBUS or MODBUS RS232. Fieldbus control with embedded fieldbus Drive control parameters After the Modbus communication has been set up, the drive control parameters listed in the table below should be checked and adjusted when necessary. The Setting for fieldbus control column gives the value to use when the Modbus interface is the desired source or destination for that particular signal. The Function/Information column gives a description of the parameter. Fieldbus control with embedded fieldbus 305 Parameter Setting for Function/Information fieldbus control Modbus register address OUTPUT SIGNAL SOURCE SELECTION 1401 RELAY COMM Enables relay output RO control by OUTPUT 1 COMM(-1) signal 0134 COMM RO WORD. 1501 AO1 135 Directs the contents of the fieldbus CONTENT reference 0135 COMM VALUE 1 to SEL analog output AO. Fieldbus control with embedded fieldbus Parameter Setting for Function/Information fieldbus control 2209 RAMP INPUT 0 COMM Modbus register address Ramp input to zero through 0301 FB 40001 CMD WORD 1 bit 13 (RAMP_IN_0); bit 6 with the ABB drives profile 5319 EFB PAR 19 bit 6 (RAMP_IN_ ZERO) 40031 bit 13 COMMUNICATION FAULT FUNCTIONS 3018 COMM NOT SEL Determines the drive action in case FAULT FUNC FAULT the fieldbus communication is lost. CONST SP 7 LAST SPEED 3019 COMM 0. Fieldbus control with embedded fieldbus 307 Fieldbus control interface The communication between a fieldbus system and the drive consists of 16-bit input and output data words (with the ABB drives profile) and 32-bit input and output words (with the DCU profile). Control word and Status word The Control word (CW) is the principal means of controlling the drive from a fieldbus system. The Control word is sent by the fieldbus controller to the drive. Fieldbus control with embedded fieldbus Fieldbus references Reference selection and correction Fieldbus reference (called COMM in signal selection contexts) is selected by setting a reference selection parameter – 1103 REF1 SELECT or 1106 REF2 SELECT – to COMM, COMM+AI1 or COMM*AI1. When parameter 1103 or 1106 is set to COMM, the fieldbus reference is forwarded as such without correction. Fieldbus control with embedded fieldbus 309 Setting When COMM > 0 COMM COMM(%) · (AI(%) / 50%) · (MAX-MIN) + *AI1 MIN Corrected reference (rpm) Max. limit 1500 AI = 100% When COMM < 0 COMM(%) · (AI(%) / 50%) · (MAX-MIN) MIN COMM REF (%) Min. limit -100 -50 0 AI = 0% AI = 50% -750 750 0 0 0 AI = 0% 50 100 Min. limit COMM REF (%) AI = 50% AI = 100% Max. limit -1500 Corrected reference (rpm) Corrected reference (rpm) COMM REF (%) 1500 Ma.x limit 1200 Min. Fieldbus control with embedded fieldbus Fieldbus reference scaling Fieldbus references REF1 and REF2 are scaled for the ABB drives profile as shown in the following table. Note: Any correction of the reference (see section Reference selection and correction on page 310) is applied before scaling. Reference Range Reference type Speed or frequency REF1 -32767 … +32767 REF2 -32767 Speed or … frequency +32767 Torque PID reference Scaling Remarks -20000 = -(par. 1105) 0=0 +20000 = (par. Fieldbus control with embedded fieldbus 311 Reference handling The control of rotation direction is configured for each control location (EXT1 and EXT2) using the parameters in group 10 START/STOP/DIR. Fieldbus references are bipolar, ie they can be negative or positive. The following diagrams illustrate how group 10 parameters and the sign of the fieldbus reference interact to produce the reference REF1/REF2. Direction determined by the sign of COMM Par. Fieldbus control with embedded fieldbus Modbus mapping The following Modbus function codes are supported by the drive. Function Code Additional information hex (dec) Read Multiple 03 (03) Reads the contents of registers in a slave device. Holding Parameter sets, control, status and reference values are mapped Registers as holding registers. Fieldbus control with embedded fieldbus 313 group number, while the tens and ones correspond to the parameter number within a group. The register addresses that do not correspond with drive parameters are invalid. If there is an attempt to read or write invalid addresses, the Modbus interface returns an exception code to the controller. See Exception codes on page 314. The following table gives information on the contents of the Modbus addresses 40001…40012 and 40031…40034. Fieldbus control with embedded fieldbus Function codes Supported function codes for the holding 4xxxx register: Code hex (dec) 03 (03) 06 (06) 10 (16) 17 (23) Function name Additional information Read 4X Register Reads the binary contents of registers (4X references) in a slave device. Preset single 4X Presets a value into a single register (4X reference). When register broadcast, the function presets the same register reference in all attached slaves. Fieldbus control with embedded fieldbus 315 Communication profiles The embedded fieldbus supports three communication profiles: • DCU communication profile (DCU PROFILE) • ABB drives limited communication profile (ABB DRV LIM) • ABB drives full communication profile (ABB DRV FULL). The DCU profile extends the control and status interface to 32 bits, and it is the internal interface between the main drive application and the embedded fieldbus environment. Fieldbus control with embedded fieldbus Control word The table below and the state diagram on page 319 describe the Control word content for the ABB drives profile. The upper case boldface text refers to the states shown in the diagram. Bit ABB drives profile Control word, parameter 5319 EFB PAR 19 Name Value Comments 0 OFF1 CONTROL 1 0 1 OFF2 CONTROL 1 0 2 OFF3 CONTROL 1 0 3 4 5 6 7 Continue operation (OFF3 inactive). Emergency stop, drive stops within time defined by par. 2208. Fieldbus control with embedded fieldbus 317 ABB drives profile Control word, parameter 5319 EFB PAR 19 Bit 10 11 Name Value Comments Note: Bit 10 is supported only by ABB DRV FULL. REMOTE_CMD 1 Fieldbus control enabled. (ABB DRV FULL) 0 / 0 or reference =/ 0: Retain last Control word Control word = and reference. Control word = 0 and reference = 0: Fieldbus control enabled. Reference and deceleration/acceleration ramp are locked. EXT CTRL LOC 1 Select external control location EXT2. Effective if par. Fieldbus control with embedded fieldbus ABB drives profile (EFB) Status word, parameter 5320 EFB PAR 20 Bit Name Value STATE/Description (Correspond to states/boxes in the state diagram) 8 AT_SETPOINT 1 OPERATING. Actual value equals reference value (= is within tolerance limits, ie in speed control the difference between the output speed and the speed reference is less than or equal to 4/1%* of the nominal motor speed). Fieldbus control with embedded fieldbus 319 State diagram The state diagram below describes the start-stop function of Control word (CW) and Status word (SW) bits for the ABB drives profile. Fieldbus control with embedded fieldbus DCU communication profile Because the DCU profile extends the control and status interface to 32 bits, two different signals are needed for both the control words (0301 and 0302) and status words (0303 and 0304). Control words The following tables describe the Control word content for the DCU profile. Fieldbus control with embedded fieldbus 321 DCU profile Control word, parameter 0301 FB CMD WORD 1 Bit Name Value Information 12 RAMP_HOLD 1 0 Halt ramping (Ramp function generator output held). No operation 13 RAMP_IN_0 14 1 0 REQ_LOCALLOC 1 Force ramp input to zero. No operation Enable local lock. Entering the local control mode is disabled (LOC/REM key of the panel). 15 0 1 TORQLIM2 0 Bit 16 17 18 No operation Use minimum/maximum torque limit 2 (defined by parameters 2016 and 2018). Fieldbus control with embedded fieldbus DCU profile Control word, parameter 0302 FB CMD WORD 2 Bit 28 Name REF_AVE Value 1 Information Average speed reference request. This is an internal control bit. Only for supervision. No operation 0 29 LINK_ON 1 30 0 REQ_STARTINH 1 0 31 Reserved Master detected on fieldbus link. This is an internal control bit. Only for supervision. Fieldbus link is down. Fieldbus control with embedded fieldbus 323 DCU profile Status word, parameter 0303 FB STS WORD 1 Bit Name Value Status 12 PANEL_LOCAL 1 0 Control is in control panel (or PC tool) local mode. Control is not in control panel local mode. 13 FIELDBUS_LOCAL 14 EXT2_ACT 1 0 1 Control is in fieldbus local mode Control is not in fieldbus local mode. Control is in EXT2 mode. FAULT 0 1 Control is in EXT1 mode. Drive is in a fault state. 0 Drive is not in a fault state. Fieldbus control with embedded fieldbus Fieldbus control with fieldbus adapter 325 Fieldbus control with fieldbus adapter What this chapter contains The chapter describes how the drive can be controlled by external devices over a communication network through fieldbus adapter. System overview The drive can be connected to an external control system through a fieldbus adapter or embedded fieldbus. For embedded fieldbus control, see chapter Fieldbus control with embedded fieldbus on page 301. Fieldbus adapter is connected to drive terminal X3. Fieldbus control with fieldbus adapter Fieldbus controller Drive Fieldbus Other devices X3 Fieldbus adapter Data flow Control word (CW) References Status word (SW) Actual values Parameter R/W requests/responses Process I/O (cyclic) Service messages (acyclic) The drive can be set to receive all of its control information through the fieldbus interface, or the control can be distributed between the fieldbus interface and other available sources, eg digital and analog inputs. Fieldbus control with fieldbus adapter 327 Setting up communication through a fieldbus adapter module Before configuring the drive for fieldbus control, the adapter module must be mechanically and electrically installed according to the instructions given in section Attach the optional fieldbus module on page 35, and the module manual. The communication between the drive and the fieldbus adapter module is activated by setting parameter 9802 COMM PROT SEL to EXT FBA. Fieldbus control with fieldbus adapter The new settings will take effect when the drive is next powered up, or when parameter 5127 FBA PAR REFRESH is activated. Drive control parameters After the fieldbus communication has been set up, the drive control parameters listed in the table below should be checked and adjusted where necessary. The Setting for fieldbus control column gives the value to use when the fieldbus interface is the desired source or destination for that particular signal. Fieldbus control with fieldbus adapter 329 Parameter Setting for fieldbus control Function/Information 1604 FAULT RESET SEL COMM 1606 LOCAL LOCK COMM 1607 DONE SAVE… Selects the fieldbus interface as the source for the fault reset signal. Selects the fieldbus interface as the source for the local lock signal. Saves parameter value changes (including those made through fieldbus control) to the permanent memory. Fieldbus control with fieldbus adapter Fieldbus control interface The communication between a fieldbus system and the drive consists of 16-bit input and output data words. The drive supports at the maximum the use of 10 data words in each direction. Data transformed from the drive to the fieldbus controller is defined by parameter group 54 FBA DATA IN and data transformed from the fieldbus controller to the drive is defined by parameter group 55 FBA DATA OUT. Fieldbus control with fieldbus adapter 331 References References (REF) are 16-bit signed integers. A negative reference (indicating reversed direction of rotation) is formed by calculating the two’s complement from the corresponding positive reference value. The contents of each reference word can be used as speed or frequency reference. Actual values Actual values (ACT) are 16-bit words containing information on selected operations of the drive. Fieldbus control with fieldbus adapter Fieldbus references Reference selection and correction Fieldbus reference (called COMM in signal selection contexts) is selected by setting a reference selection parameter – 1103 REF1 SELECT or 1106 REF2 SELECT – to COMM, COMM+AI1 or COMM*AI1. When parameter 1103 or 1106 is set to COMM, the fieldbus reference is forwarded as such without correction. Fieldbus control with fieldbus adapter 333 Setting COMM *AI1 When COMM > 0 rpm (COMM/1000) · (AI(%) / 50%) Corrected reference (rpm) Max. limit 1500 AI = 100% When COMM < 0 rpm (COMM/1000) · (AI(%) / 50%) COMM -1500000 -750000 REF Min. limit AI = 0% 0 AI = 50% -750 750 0 0 0 AI = 0% 750000 1500000 Min. limit Max. limit AI = 50% AI = 100% -1500 COMM REF Corrected reference (rpm) Corrected reference (rpm) COMM -1500000 REF 1500 Ma.x limit 1200 Min. Fieldbus control with fieldbus adapter Fieldbus reference scaling Fieldbus references REF1 and REF2 are scaled for the DCU profile as shown in the following table. Note: Any correction of the reference (see section Reference selection and correction on page 332) is applied before scaling. Reference Range Scaling Remarks REF1 Reference type -214783648 Speed or … frequency +214783647 1000 = 1 rpm / 1 Hz Final reference limited by 1104/1105. Fault tracing 335 Fault tracing What this chapter contains The chapter tells how to reset faults and view fault history. It also lists all alarm and fault messages including the possible cause and corrective actions. Safety WARNING! Only qualified electricians are allowed to maintain the drive. Read the safety instructions in chapter Safety on page 17 before you work on the drive. Alarm and fault indications Fault is indicated with a red LED. See section LEDs on page 356. Fault tracing parameter 1604 FAULT RESET SEL. When the fault has been removed, the motor can be restarted. Fault history When a fault is detected, it is stored in the fault history. The latest faults are stored together with the time stamp. Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT 1 and 0413 PREVIOUS FAULT 2 store the most recent faults. Parameters 0404…0409 show drive operation data at the time the latest fault occurred. Fault tracing 337 Alarm messages generated by the drive CODE ALARM CAUSE WHAT TO DO 2001 OVERCURRENT Output current limit controller is active. 0308 bit 0 (programmable fault function 1610) Check motor load. Check acceleration time (2202 and 2205). Check motor and motor cable (including phasing). Check ambient conditions. Load capacity decreases if installation site ambient temperature exceeds 40 °C. See section Derating on page 359. 2002 OVERVOLTAGE DC overvoltage controller is active. Fault tracing CODE ALARM CAUSE WHAT TO DO 2008 PANEL LOSS 0308 bit 7 (programmable fault function 3002) Control panel selected as active control location for drive has ceased communicating. Check panel connection. Check fault function parameters. Check control panel connector. Refit control panel in mounting platform. Fault tracing 339 CODE ALARM CAUSE WHAT TO DO 2021 START ENABLE 1 MISSING 0309 bit 4 No Start enable 1 signal received Check parameter 1608 START ENABLE 1 settings. Check digital input connections. Check fieldbus communication settings. 2022 START ENABLE 2 MISSING 0309 bit 5 No Start enable 2 signal received Check parameter 1609 START ENABLE 2 settings. Check digital input connections. Check fieldbus communication settings. Fault tracing CODE ALARM CAUSE WHAT TO DO 2035 STO (Safe torque off) requested and it functions correctly. Parameter 3025 STO OPERATION is set to react with alarm. If this was not expected reaction to safety circuit interruption, check cabling of safety circuit connected to STO terminals X1C. If different reaction is required, change value of parameter 3025 STO OPERATION. Note: Start signal must be reset (toggled to 0) if STO has been used while drive has been running. Fault tracing 341 Alarms generated by the basic control panel The basic control panel indicates control panel alarms with a code, A5xxx. ALARM CODE CAUSE WHAT TO DO 5001 Drive is not responding. Check panel connection. 5002 Incompatible communication profile Contact your local ABB representative. 5010 Corrupted panel parameter Retry parameter upload. backup file Retry parameter download. 5011 Drive is controlled from another source. Change drive control to local control mode. Fault tracing ALARM CODE CAUSE WHAT TO DO 5029 Memory is not ready. Retry. 5030 Invalid request Contact your local ABB representative. 5031 Drive is not ready for operation, eg due to low DC voltage. Check input power supply. 5032 Parameter error Contact your local ABB representative. 5040 Parameter download error. Selected parameter set is not in current parameter backup file. Perform upload function before download. 5041 Parameter backup file does not fit into memory. Fault tracing 343 ALARM CODE CAUSE WHAT TO DO 5087 Parameter download from source to destination drive has failed because parameter sets are incompatible. Check that source and destination drive information are same. See parameters in group 33 INFORMATION. 5088 Operation has failed because of drive memory error. Contact your local ABB representative. 5089 Download has failed because of CRC error. Contact your local ABB representative. 5090 Download has failed because of data processing error. Fault tracing Fault messages generated by the drive CODE FAULT CAUSE WHAT TO DO 0001 OVERCURRENT (2310) 0305 bit 0 Output current has exceeded trip level. Check motor load. Check acceleration time (2202 and 2205). Check motor and motor cable (including phasing). Check ambient conditions. Load capacity decreases if installation site ambient temperature exceeds 40 °C. See section Derating on page 359. 0002 DC OVERVOLT (3210) 0305 bit 1 Excessive intermediate circuit DC voltage. Fault tracing 345 CODE FAULT CAUSE 0009 Motor temperature is Check motor ratings, load and cooling. too high (or appears to Check start-up data. be too high) due to Check fault function parameters. excessive load, insufficient motor power, inadequate cooling or incorrect start-up data. MOT OVERTEMP (4310) 0305 bit 8 (programmable fault function 3005…3009 / 3504) WHAT TO DO Measured motor temperature has exceeded fault limit set by parameter 3504 FAULT LIMIT. Check value of fault limit. Fault tracing CODE FAULT CAUSE WHAT TO DO 0015 EXT FAULT 2 External fault 2 (9001) 0305 bit 14 (programmable fault function 3004) Check external devices for faults. Check parameter 3004 EXTERNAL FAULT 2 setting. 0016 EARTH FAULT Drive has detected earth (ground) fault in (2330) motor or motor cable. 0305 bit 15 (programmable fault function 3017) Check motor. Check motor cable. Motor cable length must not exceed maximum specifications. See section Motor connection data on page 367. Fault tracing 347 CODE FAULT CAUSE WHAT TO DO 0024 OVERSPEED (7310) 0306 bit 7 Motor is turning faster than highest allowed speed due to incorrectly set minimum/maximum speed, insufficient braking torque or changes in load when using torque reference. Operating range limits are set by parameters 2001 MINIMUM SPEED and 2002 MAXIMUM SPEED (in vector control) or 2007 MINIMUM FREQ and 2008 MAXIMUM FREQ (in scalar control). Check minimum/maximum frequency settings. Check adequacy of motor braking torque. Fault tracing CODE FAULT CAUSE WHAT TO DO 0035 OUTP WIRING (FF95) 0306 bit 15 (programmable fault function 3023) Incorrect input power Check input power connections. and motor cable connection (ie input power cable is connected to drive motor connection). Fault can be erroneously declared if drive is faulty or input power is delta grounded system and motor cable capacitance is large. 0036 INCOMPATIBLE SW (630F) 0307 bit 3 Loaded software is not Contact your local ABB compatible. representative. Fault tracing 349 CODE FAULT 0101 SERF CORRUPT (FF55) 0307 bit 14 0103 SERF MACRO (FF55) 0307 bit 14 0201 DSP T1 OVERLOAD (6100) 0307 bit 13 CAUSE WHAT TO DO Drive internal error Write down fault code and contact your local ABB representative. Fault tracing CODE FAULT CAUSE WHAT TO DO 1004 PAR AO SCALE (6320) 0307 bit 15 Incorrect analog output Check parameter group 15 ANALOG AO signal scaling OUTPUTS settings. Check that following applies: • 1504 MINIMUM AO1 < 1505 MAXIMUM AO1. 1005 PAR PCU 2 (6320) 0307 bit 15 Incorrect motor nominal power setting Check parameter 9909 MOTOR NOM POWER setting. Following must apply: • 1.1 < (9906 MOTOR NOM CURR · 9905 MOTOR NOM VOLT · 1.73 / PN) < 3. Fault tracing 351 CODE FAULT CAUSE WHAT TO DO 1017 Only two of the following can be used simultaneously: MTAC-01 encoder module, frequency input signal or frequency output signal. Fault tracing Embedded fieldbus faults Embedded fieldbus faults can be traced by monitoring group 53 EFB PROTOCOL parameters. See also fault/alarm SERIAL 1 ERR (0028). No master device If there is no master device on line, parameter 5306 EFB OK MESSAGES and 5307 EFB CRC ERRORS values remain unchanged. What to do: • Check that the network master is connected and properly configured. • Check the cable connection. Maintenance and hardware diagnostics 353 Maintenance and hardware diagnostics What this chapter contains The chapter contains preventive maintenance instructions and LED indicator descriptions. Maintenance intervals If installed in an appropriate environment, the drive requires very little maintenance. The table lists the routine maintenance intervals recommended by ABB. Maintenance and hardware diagnostics Cooling fan The drive’s cooling fan has a life span of minimum 25 000 operating hours. The actual life span depends on the drive usage and ambient temperature. Automatic fan on/off control increases the life span (see parameter 1612 FAN CONTROL). When the assistant control panel is in use, the Notice handler assistant informs when the definable value of the operating hour counter is reached (see parameter 2901 COOLING FAN TRIG). Maintenance and hardware diagnostics 355 7. Install the new fan holder including the fan in reverse order. 7 8. Restore power. Capacitors Reforming the capacitors The capacitors must be reformed if the drive has been stored for a year. See section Type designation label on page 28 for how to find out the manufacturing time from the serial number. Maintenance and hardware diagnostics Control panel Cleaning the control panel Use a soft damp cloth to clean the control panel. Avoid harsh cleaners which could scratch the display window. Changing the battery in the assistant control panel A battery is only used in assistant control panels that have the clock function available and enabled. The battery keeps the clock operating in memory during power interruptions. The expected life for the battery is greater than ten years. Technical data 357 Technical data What this chapter contains The chapter contains the technical specifications of the drive, eg ratings, sizes and technical requirements as well as provisions for fulfilling the requirements for CE and other marks. Technical data Ratings Type Input Output ACS355I1N I1N (480 V) I2N I2,1 min/10 min 2) I2max x = E/U 1) A A A A A 1-phase UN = 200…240 V (200, 208, 220, 230, 240 V) 01x-02A4-2 6.1 2.4 3.6 4.2 kW hp 0.37 0.5 R0 01x-04A7-2 01x-06A7-2 01x-07A5-2 8.2 11.7 13.1 0.75 1.1 1.5 1 1.5 2 R1 R1 R2 01x-09A8-2 21.0 9.8 14.7 3-phase UN = 200…240 V (200, 208, 220, 230, 240 V) 03x-02A4-2 4.3 2.4 3.6 17.2 2.2 3 R2 4.2 0.37 0.5 R0 03x-03A5-2 03x-04A7-2 03x-06A7-2 6.1 7.6 11.8 - 3.5 4.7 6.7 5.3 7. Technical data 359 Definitions Input I1N I1N (480 V) Output I2N I2,1 min/10 min I2max PN R0…R4 continuous rms input current (for dimensioning cables and fuses) continuous rms input current (for dimensioning cables and fuses) for drives with 480 V input voltage continuous rms current. 50% overload is allowed for one minute every ten minutes. maximum (50% overload) current allowed for one minute every ten minutes maximum output current. Technical data Altitude derating, I2N In altitudes 1000…2000 m (3300…6600 ft) above sea level, the derating is 1% for every 100 m (330 ft). For 3-phase 200 V drives, the maximum altitude is 3000 m (9800 ft) above sea level. In altitudes 2000…3000 m (6600…9800 ft), the derating is 2% for every 100 m (330 ft). Switching frequency derating, I2N The drive derates itself automatically when parameter 2607 SWITCH FREQ CTRL = 1 (ON). Technical data 361 Power cable sizes and fuses Cable dimensioning for rated currents (I1N) is shown in the table below together with the corresponding fuse types for short-circuit protection of the input power cable. The rated fuse currents given in the table are the maximums for the mentioned fuse types. If smaller fuse ratings are used, check that the fuse rms current rating is larger than the rated I1N current given in section Ratings on page 358. Technical data Type ACS355- Fuses Size of copper conductor in cablings UL Class Supply Motor PE Brake T (600 V) (U1, V1, W1) (U2, V2, W2) (BRK+, BRK-) x = E/U A A mm2 AWG mm2 AWG mm2 AWG mm2 AWG 3-phase UN = 380…480 V (380, 400, 415, 440, 460, 480 V) 03x-01A2-4 10 10 2.5 14 0.75 18 2.5 14 2.5 14 03x-01A9-4 10 10 2.5 14 0.75 18 2.5 14 2.5 14 03x-02A4-4 10 10 2.5 14 0.75 18 2.5 14 2.5 14 03x-03A3-4 10 10 2.5 12 0.75 18 2.5 12 2.5 12 03x-04A1-4 16 15 2.5 12 0.75 18 2.5 12 2.5 12 03x-05A6-4 16 15 2. Technical data 363 Dimensions, weights and free space requirements Dimensions and weights Frame size Dimensions and weights H1 IP20 (cabinet) / UL open H3 W H2 D Weight R0 mm 169 in 6.65 mm 202 in 7.95 mm 239 in 9.41 mm 70 in 2.76 mm 161 in 6.34 kg 1.2 lb 2.6 R1 R2 R3 169 169 169 6.65 6.65 6.65 202 202 202 7.95 7.95 7.95 239 239 236 9.41 9.41 9.29 70 105 169 2.76 4.13 6.65 161 165 169 6.34 6.50 6.65 1.2 1.7 2.9 2.6 3.7 6.4 R4 181 7.13 202 7.95 244 9.61 260 10. Technical data Losses, cooling data and noise Losses and cooling data Frame size R0 has natural convection cooling. Frame sizes R1…R4 are provided with an internal fan. The air flow direction is from bottom to top. The table below specifies the heat dissipation in the main circuit at nominal load and in the control circuit with minimum load (I/O and panel not in use) and maximum load (all digital inputs in the on state and the panel, fieldbus and fan in use). Technical data 365 Type Heat dissipation ACS355x = E/U Main circuit Rated /1N and /2N W Air flow Control circuit Min Max W W 3-phase UN = 380…480 V (380, 400, 415, 440, 460, 480 V) 03x-01A2-4 11 6.6 24.4 m3/h ft3/min - - 03x-01A9-4 03x-02A4-4 03x-03A3-4 16 21 31 6.6 9.8 9.8 24.4 28.7 28.7 13 13 8 8 03x-04A1-4 03x-05A6-4 03x-07A3-4 40 61 74 9.8 9.8 14.1 28.7 28.7 32.7 13 19 24 8 11 14 03x-08A8-4 03x-12A5-4 03x-15A6-4 94 130 173 14.1 12.0 12.0 32.7 31.2 31. Technical data Terminal and lead-through data for the power cables Frame size Max. cable diameter for NEMA 1 U1, V1, W1, BRK+ and U2, V2, W2 BRK- U1, V1, W1, U2, V2, W2, PE BRK+ and BRKTerminal size Tightening Clamp size Tightening torque torque R0 mm 16 in 0.63 mm 16 in 0.63 mm2 4.0/6.0 R1 R2 R3 16 16 29 0.63 0.63 1.14 16 16 16 0.63 0.63 0.63 4.0/6.0 4.0/6.0 10.0/16.0 10 10 6 0.8 0.8 1.7 7 7 15 25 25 25 3 3 3 1.2 1.2 1.2 11 11 11 R4 35 1.38 29 1.14 25.0/35.0 2 2. Technical data 367 Electric power network specification Voltage (U1) 200/208/220/230/240 V AC 1-phase for 200 V AC drives 200/208/220/230/240 V AC 3-phase for 200 V AC drives 380/400/415/440/460/480 V AC 3-phase for 400 V AC drives ±10% variation from converter nominal voltage is allowed as default. Short-circuit capacity Maximum allowed prospective short-circuit current at the input power connection as defined in IEC 60439-1 and UL 508C is 100 kA. Technical data EMC compatibility and motor cable length To comply with the European EMC Directive (standard IEC/EN 61800-3), use the following maximum motor cable lengths for 4 kHz switching frequency. Technical data 369 Control connection data Analog inputs X1A: 2 and 5 (AI1 and AI2) Voltage signal, unipolar bipolar Current signal, unipolar bipolar Potentiometer reference value (X1A: 4) Resolution Accuracy 0 (2)…10 V, Rin = 675 kohm -10…10 V, Rin = 675 kohm 0 (4)…20 mA, Rin = 100 ohm -20…20 mA, Rin = 100 ohm 10 V ± 1%, max. 10 mA, R < 10 kohm 0.1% ±2% Analog output X1A: 7 (AO) 0 (4)…20 mA, load < 500 ohm Auxiliary voltage X1A: 9 24 V DC ± 10%, max. Technical data Brake resistor connection Short-circuit protection The brake resistor output is conditionally short-circuit proof by (IEC 61800-5-1, IEC/EN 61800-5-1 and UL 508C. For correct fuse selection, contact IEC 60439-1, UL 508C) your local ABB representative. Rated conditional short-circuit current as defined in IEC 60439-1 and the Short-circuit test current by UL 508C is 100 kA. Common DC connection Maximum power through common DC connection is equal to the drive nominal power. Technical data 371 Ambient conditions Environmental limits for the drive are given below. The drive is to be used in a heated indoor controlled environment. Operation Storage Transportation installed for in the protective in the protective stationary use package package Installation site altitude 0…2000 m (6600 ft) above sea level (above 1000 m [3300 ft], see section Derating on page 359) Air temperature -10 … +50 °C -40 … +70 °C ±2% -40 … +70 °C ±2% (14 … 122 °F). Technical data Materials Drive enclosure Package Disposal • PC/ABS 2 mm, PC+10%GF 2.5…3 mm and PA66+25%GF 1.5 mm, all in color NCS 1502-Y (RAL 9002 / PMS 420 C) • hot-dip zinc coated steel sheet 1.5 mm, thickness of coating 20 micrometers • extruded aluminium AlSi. Corrugated cardboard. The drive contains raw materials that should be recycled to preserve energy and natural resources. The package materials are environmentally compatible and recyclable. All metal parts can be recycled. Technical data 373 CE marking The CE mark is attached to the drive to verify that the drive follows the provisions of the European Low Voltage and EMC Directives. Compliance with the European EMC Directive The EMC Directive defines the requirements for immunity and emissions of electrical equipment used within the European Union. The EMC product standard (EN 61800-3:2004) covers requirements stated for drives. See section Compliance with EN 61800-3:2004 on page 373. Technical data 1. The optional EMC filter is selected according to the ABB documentation and installed as specified in the EMC filter manual. 2. The motor and control cables are selected as specified in this manual. 3. The drive is installed according to the instructions given in this manual. 4. For the maximum motor cable length with 4 kHz switching frequency, see page 368. Technical data 375 Note: It is not allowed to install a drive with the internal EMC filter connected on IT (ungrounded) systems. The supply network becomes connected to ground potential through the EMC filter capacitors which may cause danger or damage the drive. Note: It is not allowed to install a drive with the internal EMC filter connected on a corner-grounded TN system as this would damage the drive. UL marking See the type designation label for the valid markings of your drive. Technical data C-Tick marking See the type designation label for the valid markings of your drive. C-Tick marking is required in Australia and New Zealand. A C-Tick mark is attached to the drive to verify compliance with the relevant standard (IEC 61800-3:2004 – Adjustable speed electrical power drive systems – Part 3: EMC product standard including specific test methods), mandated by the Trans-Tasman Electromagnetic Compatibility Scheme. Technical data 377 Patent protection in the USA This product is protected by one or more of the following US patents: 4,920,306 5,654,624 6,175,256 6,313,599 6,552,510 6,859,374 6,972,976 7,034,510 7,084,604 7,215,099 7,274,573 7,372,696 7,515,447 D512,026 D548,183S 5,301,085 5,799,805 6,184,740 6,316,896 6,597,148 6,922,883 6,977,449 7,036,223 7,098,623 7,221,152 7,279,802 7,388,765 7,560,894 D512,696 D573,090S Other patents pending. Technical data Dimension drawings 379 Dimension drawings Dimension drawings of the ACS355 are shown below. The dimensions are given in millimeters and [inches]. Dimension drawings Frame sizes R0 and R1, IP20 (cabinet installation) / UL open Frame sizes R0 and R1, IP20 (cabinet installation) / UL open 3AUA0000067784-A Extension modules add 26 mm (1.02 in) to the depth measure. 1) 1) R1 and R0 are identical except for the fan at the top of R1. Dimension drawings 381 Frame sizes R0 and R1, IP20 / NEMA 1 Frame sizes R0 and R1, IP20 / NEMA 1 3AUA0000067785-A Extension modules add 26 mm (1.02 in) to the depth measure. 1) 1) R1 and R0 are identical except for the fan at the top of R1. Frame size R2, IP20 (cabinet installation) / UL open Extension modules add 26 mm (1.02 in) to the depth measure. Frame size R2, IP20 / NEMA 1 Extension modules add 26 mm (1.02 in) to the depth measure. Frame size R3, IP20 (cabinet installation) / UL open Extension modules add 26 mm (1.02 in) to the depth measure. Frame size R3, IP20 / NEMA 1 Extension modules add 26 mm (1.02 in) to the depth measure. Frame size R4, IP20 (cabinet installation) / UL open Extension modules add 26 mm (1.02 in) to the depth measure. Frame size R4, IP20 / NEMA 1 Extension modules add 26 mm (1.02 in) to the depth measure. Dimension drawings Appendix: Resistor braking 389 Appendix: Resistor braking What this chapter contains The chapter tells how to select the brake resistor and cables, protect the system, connect the brake resistor and enable resistor braking. Planning the braking system Selecting the brake resistor ACS355 drives have an internal brake chopper as standard equipment. The brake resistor is selected using the table and equations presented in this section. 1. Appendix: Resistor braking Equations for selecting the resistor: Eq. 1. UN = 200…240 V: R = 150000 PRmax UN = 380…415 V: R = 450000 PRmax UN = 415…480 V: R = 615000 PRmax ton PRmax PRave T Eq. 2. ERpulse = PRmax · ton Eq. 3. PRave = PRmax · where R PRmax PRave ERpulse ton T ton T For conversion, use 1 hp = 746 W. Appendix: Resistor braking 391 Type Rmin Rmax PBRmax Selection table by resistor type ACS355- CBR-V / CBT-H x = E/U 1) ohm ohm kW hp 160 210 260 460 660 560 3-phase UN = 380…480 V (380, 400, 415, 440, 460, 480 V) 03x-01A2-4 200 1180 0.37 0.5 Braking time 2) s 90 03x-01A9-4 03x-02A4-4 03x-03A3-4 175 165 150 800 590 400 0.55 0.75 1.1 0.75 1 1.5 90 60 37 03x-04A1-4 03x-05A6-4 03x-07A3-4 130 100 70 300 200 150 1.5 2.2 3. Appendix: Resistor braking Placing the brake resistor Install all resistors in a place where they will cool. WARNING! The materials near the brake resistor must be non-flammable. The surface temperature of the resistor is high. Air flowing from the resistor is of hundreds of degrees Celsius. Protect the resistor against contact. Appendix: Extension modules 393 Appendix: Extension modules What this chapter contains The appendix describes common features and mechanical installation of the optional extension modules for the ACS355: MPOW-01 auxiliary power module, MTAC-01 pulse encoder interface module and MREL-01 output relay module. The appendix also describes specific features and electrical installation for the MPOW-01; for information on the MTAC-01 and MREL-01, refer to the corresponding user’s manual. Appendix: Extension modules Generic extension module layout Grounding stand-off Panel port adapter Installation Checking the delivery The option package contains: • extension module • grounding stand-off with an M3 × 12 screw • panel port adapter (fixed to the MPOW-01 module at the factory). Installing the extension module WARNING! Follow the safety instructions given in chapter Safety on page 17. To install the extension module: 1. If not already off, remove input power from the drive. 2. Appendix: Extension modules 395 6. Ground the extension module by inserting the screw removed from the drive in the top left corner of the extension module. Tighten the screw using a torque of 0.8 N·m (7 lbf·in). Note: Correct insertion and tightening of the screw is essential for fulfilling the EMC requirements and proper operation of the extension module. 7. Install the control panel or panel cover on the extension module. 8. Electrical installation is module-specific. Appendix: Extension modules Technical data Dimensions Extension module dimensions are shown in the figure below. 64 [2.52] 45 [1.79] 118 [4.63] 70 [2.77] Generic extension module specifications • Enclosure degree of protection: IP20 • All materials are UL/CSA-approved. • When used with ACS355 drives, the extension modules comply with EMC standard EN/IEC 61800-3:2004 for electromagnetic compatibility and EN/IEC 61800-5-1:2005 for electrical safety requirements. Appendix: Extension modules 397 MPOW-01 auxiliary power module Description The MPOW-01 auxiliary power module is used in installations where the drive's control part is required to be powered during network failures and maintenance interruptions. The MPOW-01 provides auxiliary voltages to the control panel, fieldbus and I/O. Appendix: Extension modules Technical data Specifications • Input voltage: +24 V DC or 24 V AC ± 10% • Maximum load 1200 mA rms • Power losses with maximum load 6 W • Designed lifetime of the MPOW-01 module is 50 000 hours in the specified ambient conditions of the drive (see section Ambient conditions on page 371). Appendix: Safe torque off (STO) 399 Appendix: Safe torque off (STO) What this appendix contains The appendix describes the basics of the Safe torque off function (STO) for the ACS355. In addition, application features and technical data for the safety system calculation are presented. Basics The drive supports the Safe torque off (STO) function according to standards EN 61800-5-2; EN/ISO 13849-1:2006, IEC/EN 60204-1:1997; EN 61508:2002, EN 1037:1996, and IEC 62061:2005 (SILCL 3). Appendix: Safe torque off (STO) ACS355 +24 V X1C:1 OUT1 X1C:2 OUT2 Safety circuit (switch, relays, etc.) X1C:3 IN1 X1C:4 IN2 UDC+ Control circuit Output stage (1 phase shown) UDC- U2/V2/W2 Notes: • The contacts of the safety circuit must open/close within 200 ms of each other. • The maximum cable length between the drive and the safety switch is 25 m (82 ft). WARNING! The STO function does not disconnect the voltage of the main and auxiliary circuits from the drive. Appendix: Safe torque off (STO) 401 STO inputs have been energized, and any of the drive reactions have been reset. Drive event can be parametrized according to the table below. Parameter 3025 STO OPERATION Selection values (1) ONLY FAULT Explanation Drive event on successful STO operation is fault SAFE TORQUE OFF. The fault bit is updated. (2) ALARM&FAULT Drive event on successful STO operation is alarm SAFE TORQUE OFF when stopped and fault SAFE TORQUE OFF when running. Appendix: Safe torque off (STO) STO function activation and indication delays STO activation delay is below 1 ms. STO indication delay (time from the deenergization of any STO input to the updating of the status bit) is 200 ms. Note: If any STO channel is toggled very fast, it is possible that the drive trips to overcurrent or short circuit. Installation Connect the cables as shown in the diagram below. Appendix: Safe torque off (STO) 403 24 V auxiliary voltage load (I/O, panel load, used fieldbus or STO circuits; max. 200 mA) of the drive supplying the STO circuit (see section Control connection data on page 369). When using external supply, all analog grounds (AGND) of the drives must be chained together. Note: Daisy chaining lowers the total system safety integrity level, which needs to be calculated case by case for each system. Appendix: Safe torque off (STO) Data related to safety standards SIL IEC 61508 3 PFH HFT SFF EN/ISO 13849-1 PL e 6.48E-09 (6. Further information Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/drives and selecting Sales, Support and Service network. Product training For information on ABB product training, navigate to www.abb.com/drives and select Training courses. ABB Oy Drives P.O. Box 184 FI-00381 HELSINKI FINLAND Telephone +358 10 22 11 Fax +358 10 22 22681 www.abb.com/drives ABB Inc. Automation Technologies Drives & Motors 16250 West Glendale Drive New Berlin, WI 53151 USA Telephone 262 785-3200 800-HELP-365 Fax 262 780-5135 www.abb.com/drives ABB Beijing Drive Systems Co. Ltd. No. 1, Block D, A-10 Jiuxianqiao Beilu Chaoyang District Beijing, P.R. China, 100015 Telephone +86 10 5821 7788 Fax +86 10 5821 7618 www.abb. |