Installation Manual
ACS550-PD Packaged Drive with Disconnect 19
Technical Data
Input Power Connections and Power Connection Terminals
(Supplement to ACS550-U1 User’s Manual)
3-Phase 240V
HP ABB Product Code
Drive Input Fuse
Rating
Incoming Power Connections
Ground
Lugs
UL Type
3R/
NEMA 3R
Output Connections to Motor
Amps
(600V)
Bussman
Type
Minimum
Wire Size
Maximum
Wire Size
Tightening
Torque
(lb/ft)
Minimum
Wire Size
Maximum
Wire Size
Tightening
Torque
(lb/ft)
25 ACS550-PD-075A-2+C192 100 JJS-100 #8 1/0 55
#2
50in-lbs
10 1/0 4
30 ACS550-PD-088A-2+C192 110 JJS-110 #8 1/0 55 10 1/0 4
40 ACS550-PD-114A-2+C192 150 JJS-150 #4 300MCM 200 10 1/0 4
50 ACS550-PD-143A-2+C192 200 JJS-200 #4 300MCM 200
#2/0
275in-lbs
3/0 350MCM 30
60 ACS550-PD-178A-2+C192 250 JJS-250 #4 300MCM 200 3/0 350MCM 30
75 ACS550-PD-221A-2+C192 300 JJS-300 #4 300MCM 200
350MCM
100in-lbs
3/0 350MCM 30
100 ACS550-PD-248A-2+C192 350 JJS-350 #2 600MCM 375 3/0 350MCM 30
NOTE:Forinformationregardingmotorterminals.referto“DrivesPowerConnectionTerminals”intheACS550-U1UserManual.