Installation Manual

20 ACS550-PD Packaged Drive with Disconnect
Technical Data
Input Power Connections and Power Connection Terminals
(Supplement to ACS550-U1 Users Manual)
3-Phase 480V
HP ABB Product Code
Drive Input Fuse
Rating
Incoming Power Connections
Ground
Lugs
UL Type
3R/
NEMA 3R
Output Connections to Motor
Amps
(600V)
Bussman
Type
Minimum
Wire Size
Maximum
Wire Size
Tightening
Torque
(lb/ft)
Minimum
Wire Size
Maximum
Wire Size
Tightening
Torque
(lb/ft)
40 ACS550-PD-059A-4+C192 80 JJS-80 #8 1/0 55
#2
50in-lbs
10 1/0 4
50 ACS550-PD-072A-4+C192 90 JJS-90 #8 1/0 55 10 1/0 4
60 ACS550-PD-078A-4+C192 100 JJS-100 #8 1/0 55 10 1/0 4
75 ACS550-PD-097A-4+C192 125 JJS-125 #4 300MCM 200 10 1/0 4
100 ACS550-PD-125A-4+C192 175 JJS-175 #4 300MCM 200 3/0 350MCM 30
125 ACS550-PD-157A-4+C192 200 JJS-200 #4 300MCM 200
#2/0
375in-lbs
3/0 350MCM 30
150 ACS550-PD-180A-4+C192 250 JJS-250 #2 600MCM 375 3/0 350MCM 30
200 ACS550-PD-246A-4+C192 350 JJS-350 #2 600MCM 375
350MCM
100in-lbs
3/0 350MCM 30
NOTE:Forinformationregardingmotorterminals.referto“DrivesPowerConnectionTerminals”intheACS550-U1UserManual.
*Shippingcrateaddsapproximately170lbs.