Cut Sheet

18 ABB general purpose drives, ACS580, Catalog
Ratings, types and voltages
Wall-mounted drives, ACS580-01
3-phase,
U
N
= 440, 460, 480 V
Type code
Frame
Size
Max.
output
current
Light overload use Heavy-duty use
I
max
(A)
I
Ld
(A)
P
Ld
(hp)
I
Hd
(A)
P
Hd
(hp)
ACS580 -01-02A1- 4 R1
2.9
2.1 1 1.6 0.75
ACS580-01-03A0-4 R1
3.8
3 1.5 2.1 1
ACS580-01-03A5-4 R1
5.4
3.5 2 3 1.5
ACS580-01-04A8-4 R1
6.1
4.8 3 3.4 2
ACS580-01-06A0-4 R1
7.2
6 3 4 3
ACS580-01-07A6-4 R1
8.6
7.6 5 4.8 3
ACS580-01-012A-4 R1
11.4
12 7.5 7.6 5
ACS580-01-014A-4 R2
19.8
14 10 11 7.5
ACS580-01-023A-4 R2
25.2
23 15 14 10
ACS580-01-027A-4 R3
37.8
27 20 21 15
ACS580-01-034A-4 R3
48.6
34 25 27 20
ACS580-01-044A-4 R3
61.2
44 30 34 25
ACS580-01-052A-4 R4
76
52 40 40 30
ACS580-01-065A-4 R4
104
65 50 52 40
ACS580-01-077A-4
R4
122
77 60 65 50
ACS580-01-078A-4 R5
122
77 60 65 50
ACS580-01-096A-4 R5
148
96 75 77 60
ACS580 -01-124A-4 R6
178
124 100 96 75
ACS580-01-156A-4 R7
247
156 125 124 100
ACS580-01-180A-4 R7
287
180 150 156 125
ACS580-01-240A-4 R8
350
240 200 180 150
ACS580-01-260A-4 R8
418
260 200 240* 150
ACS580-01-302A-4
R8
TBD
302 250 260 200
ACS580 -01-361A-4 R9
542
361 300 302 250
ACS580-01-414A-4 R9
542
414 350 361** 300
Coming soon
Nominal ratings
I
N
Rated current available continuously without overloadability at 40 °C.
P
N
Typical motor power in no-overload use.
Maximum output current
I
max
Maximum output current. Available for 2 seconds at start, then as long as allowed
by drive temperature.
Light-overload use
I
Ld
Continuous current allowing 110%
I
Ld
for 1 minute every 10 minutes at 40 °C.
P
Ld
Typical motor power in light-overload use.
Heavy-duty use
I
Hd
Continuous current allowing 150%
I
Hd
for 1 minute every 10 minutes at 40 °C.
* Continuous current allowing 130%
I
Hd
for 1 minute every 10 minutes at 40 °C.
** Continuous current allowing 125%
I
Hd
for 1 minute every 10 minutes at 40 °C.
P
Hd
Typical motor power in heavy-duty use.
The ratings apply for the frames R1 to R9 up to +40 °C in enclosure class 21.
For derating at higher altitudes, temperatures, switching frequencies or enclosure classes, see the HW manuals,
document codes: 3AXD50000018826 and 3AXD50000015497.