Cooling and fuses
Cooling
ACS580 drives are fitted with variable-speed cooling
air fans. The cooling air must be free from corrosive
materials and not exceed the maximum ambient
temperature of 40°C for frames R1 to R9 (50°C with
derating). The speed-controlled fans cool the drive
only when needed, which reduces overall noise level
and energy consumption.
Fuse connections
Standard fuses can be used with ABB general
purpose drives. For input fuses, see the table below.
Cooling air flow and recommended input protection fuses for 380 to 415 V units
Type designation Frame size Cooling Air Flow 380 to 480V units Reccomended UL Input Protection fuses
Heat dissipation* Air flow Max.
noise level**
I
N
Voltage
rating
Bussmann
type***
UL class
W BTU/Hr m3/h ft3/hr dBA A V
ACS580 -01-02A1- 4 R1
45 155 34 20 55 15 600 JJS-15 T
ACS580-01-03A0-4 R1
55 187 34 20 55 15 600 JJS-15 T
ACS580-01-03A5-4 R1
66 224 34 20 55 15 600 JJS-15 T
ACS580-01-04A8-4 R1
84 288 34 20 55 15 600 JJS-15 T
ACS580-01-06A0-4 R1
106 362 50 29 55 15 600 JJS-15 T
ACS580-01-07A6-4 R1
133 454 50 29 55 15 600 JJS-15 T
ACS580-01-012A-4 R1
174 593 50 29 55 15 600 JJS -15 T
ACS580-01-014A-4 R2
228 777 128 75 66 30 600 JJS-30 T
ACS580-01-023A-4 R2
322 1100 128 75 66 30 600 JJS-30 T
ACS580-01-027A-4 R3
430 1469 179 105 70 40 600 JJS-40 T
ACS580-01-034A-4 R3
525 1791 179 105 70 50 600 JJS-50 T
ACS580-01-044A-4 R3
619 2114 179 105 70 60 600 JJS-60 T
ACS580-01-052A-4 R4
835 2852 134 79 69 80 600 JJS-80 T
ACS580-01-065A-4 R4
1024 3497 134 79 69 90 600 JJS-90 T
ACS580-01-077A-4
‡
R4
1240 4235 139 82 63 110 600 JJS-110 T
ACS580-01-078A-4 R5
1240 4235 139 82 63 110 600 JJS-110 T
ACS580-01-096A-4 R5
1510 5157 139 82 63 150 600 JJS-150 T
ACS580 -01-124A-4 R6
1476 5041 435 256 67 200 600 JJS-200 T
ACS580-01-156A-4 R7
1976 6748 450 265 67 225 600 JJS-225 T
ACS580-01-180A-4 R7
2346 8012 450 265 67 300 600 JJS-300 T
ACS580-01-240A-4 R8
3336 11393 550 324 65 350 600 JJS-350 T
ACS580-01-260A-4 R8
3936 13422 550 324 65 400 600 JJS-400 T
ACS580-01-302A-4
‡
R8
4836 16516 1150 677 68 500 600 JJS-500 T
ACS580 -01-361A-4 R9
4836 16516 1150 677 68 500 600 JJS-500 T
ACS580-01-414A-4 R9
6036 20614 1150 677 68 600 600 JJS-600 T
‡
Coming soon
* Heat dissapation value is a reference for cabinet thermal design
** The maximum noise level is at full fan speed. When the drive is not operating at full load and at maximum ambient temperature the noise level is lower.
***ABB does not require Bussmann brand fuses. Fuses which meet the appropriate UL class type, current rating, and are rated at 600V, 200 kA may be used.
—