Parameters 327
50.16 FBA A status word Displays the raw (unmodified) status word sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
00000000h …
FFFFFFFFh
Status word sent by fieldbus adapter A to master. -
50.17 FBA A actual value
1
Displays raw (unmodified) actual value ACT1 sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648
2147483647
Raw ACT1 sent by fieldbus adapter A to master. -
50.18 FBA A actual value
2
Displays raw (unmodified) actual value ACT2 sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648
2147483647
Raw ACT2 sent by fieldbus adapter A to master. -
50.21 FBA A timelevel sel Selects the communication time levels.
In general, lower time levels of read/write services reduce
CPU load. The table below shows the time levels of the
read/write services for cyclic high and cyclic low data with
each parameter setting.
* Cyclic high data consists of fieldbus Status word, Act1 and
Act2.
** Cyclic low data consists of the parameter data mapped to
parameter groups 52 FBA A data in and 53 FBA A data out,
and acyclic data.
Control word, Ref1 and Ref2 are handled as interrupts
generated on receipt of cyclic high messages.
Normal
Normal Normal speed. 0
Fast Fast speed. 1
Very fast Very fast speed. 2
Monitoring Low speed. Optimized for PC tool communication and
monitoring usage.
3
No. Name/Value Description Def/FbEq16
Selection Cyclic high * Cyclic low **
Monitoring 10 ms 2 ms
Normal 2 ms 10 ms
Fast 500 µs 2 ms
Very fast 250 µs 2 ms