402 Parameters
96.101 Confirm user pass
code
(Visible when user lock is open)
Confirms the new user pass code entered in 96.100 Change
user pass code.
10000000
99999999
Confirmation of new user pass code. -
96.102 User lock
functionality
(Visible when user lock is open)
Selects the actions or functionalities to be prevented by the
user lock. Note that the changes made take effect only when
the user lock is closed. See parameter 96.02 Pass code.
000b
000b…111b Selection of actions to be prevented by user lock. -
96
97 Motor control
Motor model settings.
97.03 Slip gain Defines the slip gain which is used to improve the estimated
motor slip. 100% means full slip gain; 0% means no slip gain.
The default value is 100%. Other values can be used if a
static speed error is detected despite having the setting at full
slip gain.
Example (with nominal load and nominal slip of 40 rpm): A
1000 rpm constant speed reference is given to the drive.
Despite having full slip gain (= 100%), a manual tachometer
measurement from the motor axis gives a speed value of 998
rpm. The static speed error is 1000 rpm - 998 rpm = 2 rpm. To
compensate the error, the slip gain should be increased to
105% (2 rpm / 40 rpm = 5%).
100%
0 … 200% Slip gain. 1 = 1%
No. Name/Value Description Def/FbEq16
Bit Name Information
0 Disable ABB access
levels
1 = ABB access levels (service, advanced programmer, etc.; see
96.03) disabled
1 Freeze parameter
lock state
1 = Changing the parameter lock state prevented, ie. pass code
358 has no effect
2 Disable file
download
1 = Loading of files to drive prevented. This applies to
firmware upgrades
safety functions module (FSO-xx) configuration
parameter restore
loading of adaptive or application programs
changing home view of control panel
editing drive texts
editing the favorite parameters list on control panel
configuration settings made through control panel such as
time/date formats and enabling/disabling clock display.
3…15 Reserved