Fault tracing 499
64B2 User set fault Loading of user parameter set
failed because
requested set does not exist
set is not compatible with
control program
drive was switched off
during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
64E1 Kernel overload Operating system error. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
6581 Parameter system Parameter load or save failed. Try forcing a save using parameter 96.07
Parameter save manually. Retry.
65A1 FBA A parameter
conflict
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups 50
Fieldbus adapter (FBA) and 51 FBA A
settings.
65A2 FBA B parameter
conflict
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups 50
Fieldbus adapter (FBA) and 54 FBA B
settings.
65B1 Reference source
parametrization
A reference source is
simultaneously connected to
multiple parameters with
different units.
See A6DA Reference source
parametrization (page 479).
6681 EFB comm loss
Programmable fault:
58.14 Communication loss
action
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the XD2D
connector on the control unit.
6682 EFB config file Embedded fieldbus (EFB)
configuration file could not be
read.
Contact your local ABB representative.
6683 EFB invalid
parameterization
Embedded fieldbus (EFB)
parameter settings
inconsistent or not compatible
with selected protocol.
Check the settings in parameter group 58
Embedded fieldbus.
6684 EFB load fault Embedded fieldbus (EFB)
protocol firmware could not be
loaded.
Contact your local ABB representative.
Version mismatch between
EFB protocol firmware and
drive firmware.
6881 Text data overflow Internal fault. Reset the fault. Contact your local ABB
representative if the fault persists.
6882 Text 32-bit table
overflow
Internal fault. Reset the fault. Contact your local ABB
representative if the fault persists.
6883 Text 64-bit table
overflow
Internal fault. Reset the fault. Contact your local ABB
representative if the fault persists.
6885 Text file overflow Internal fault. Reset the fault. Contact your local ABB
representative if the fault persists.
7080 Option module comm
loss
Communication between drive
and an option module is lost.
See A798 Encoder option comm loss
(page 481).