Specifications

©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
2
BDS0032 rev 3
INSTALLATION
ADDRESSING
1. Install a 4 core cable (maximum length 1,600 ft. / 500 m) from the associated controller
sensor bus and sensor power connections to a flush-mounting wall box compatible with the
mounting plate (see previous page)
2. Connect the field controller to the terminals of the power case according to the wiring
diagrams below. Set the address of the FusionAir device (see
Addressing
below).
3. Attach the mounting plate to the flush-mounting box. Make sure the mounting screw heads
do not stand out more than 0.2” (5 mm) off the surface of the mounting plate.
4. Align the body of the FusionAir device with the clips on the mounting plate and press gently
until the front part is fully connected.
Each FusionAir device connected on a controller’s Sensor
bus must be assigend a unique address. This is set on the
DIP switch visible on the back of the device
1
6
2
7
3
8
4
9
5
10
The address must be between 1 and the maximum number of
FusionAir devices supported by the controller to which it is connected:
1 …4 (e.g. CBX, CBV, CBT-2U1R, CBT-3T6-5R), or
1 … 10 (e.g FBXi, CBXi, FBVi)
See the controller datasheet for more information.
The address must be within the controller’s range, but gaps in
the addressing of multiple devices are allowed.
Note: The FusionAir device reads the dip switch settings
when power is applied. Changing the DIP switch while
it is running will not take effect until the device
unplugged and plugged back in.
WIRING
Single FusionAir per controller
Connect terminals 14 to the Sensor port
on the CBX / CBXi / FLXeon controller.
Optionally connect terminals 5…7 to
external digital signals such as Occupancy
or Room Key Card.
Multiple FusionAir per controller
Daisy-chain terminals 1…4 as shown below.
Note: To allow for
potential current
requirements for
multiple sensors
when accent lights
are used, it is
recommended that
the power lines
(terminals 1 and 2)
are connected to
the Controller’s 24 V
power supply.
FA-T (Passive
sensor)
The FA-T’s temperature
sensor and side switch can
be connected directly to 4
terminals on the Controller
as shown, one analog input
and one digital input.
Alternatively they can be connected
to a single analog input and logic in
the Controller Strategy can derive
the switch position.
The digital input is a push-button on
the side of the FusionAir device, and
can be used for example to over-ride
a schedule for 1hr or override until
next value change.