Hardware manual
Fieldbus control description
15
51.02 NODE NUMBER 0...126 2 Each device on the Profibus network must
have an unique node number. This
parameter is used to define a node
number for the drive it is connected to.
51.03 BAUD RATE 12000
6000
3000
1500
500
187
93
45
19
9
12000 This paremeter indicates the detected
communication speed in kbit/s.
12000 = 12 Mbit/s
6000 = 6 Mbit/s
3000 = 3 Mbit/s
1500 = 1.5 Mbit/s
500 = 500 kbit/s
187 = 187.5 kbit/s
93 = 93.75 kbit/s
45 = 45.45 kbit/s
19 = 19.2 kbit/s
9 = 9.6 kbit/s
51.04 TELEGRAM TYPE (1) PPO 1
(2) PPO 2
(3) PPO 3
(4) PPO 4
(5) PPO 5
(6) PPO 6
(7) ST1
5 This parameter indicates the selected
telegram type for the Profibus
communication. Telegram type is
automatically detected.
51.05 PROFILE (0) PROFIdrive
(1) ABB Drives
(2) Transparent 16
(3) Transparent 32
1 This parameter is used to select which
communication profile is used.
51.06 T16 SCALE 1...65536 100 Reference multiplier/actual value divisor
for the FPBA-01. The parameter is only
effective when Transparent 16 profile is
selected and the drive is using FBA/DCU
communication profile.
51.07 FBA PAR7 These parameters are not in use.
• • •
51.26 FBA PAR26
51.27 FBA PAR
REFRESH
(0) DONE
(1) REFRESH
1 Validates any changed adapter module
configuration parameter settings.
51.28 PAR TABLE VER – Displays the parameter table revision of
the fieldbus adapter module mapping file
stored in the memory of the drive.
51.29 DRIVE TYPE
CODE
– Displays the drive type code of the
fieldbus adapter module mapping file
stored in the memory of the drive.
51.30 MAPPING FILE
VER
– Displays the fieldbus adapter module
mapping file revision stored in the
memory of the drive.
Parameter Setting for fieldbus control
Application-
specific setting
Function/Information