Hardware manual

Fieldbus control description
15
51.02 NODE NUMBER 0...126 2 Each device on the Profibus network must
have an unique node number. This
parameter is used to define a node
number for the drive it is connected to.
51.03 BAUD RATE 12000
6000
3000
1500
500
187
93
45
19
9
12000 This paremeter indicates the detected
communication speed in kbit/s.
12000 = 12 Mbit/s
6000 = 6 Mbit/s
3000 = 3 Mbit/s
1500 = 1.5 Mbit/s
500 = 500 kbit/s
187 = 187.5 kbit/s
93 = 93.75 kbit/s
45 = 45.45 kbit/s
19 = 19.2 kbit/s
9 = 9.6 kbit/s
51.04 TELEGRAM TYPE (1) PPO 1
(2) PPO 2
(3) PPO 3
(4) PPO 4
(5) PPO 5
(6) PPO 6
(7) ST1
5 This parameter indicates the selected
telegram type for the Profibus
communication. Telegram type is
automatically detected.
51.05 PROFILE (0) PROFIdrive
(1) ABB Drives
(2) Transparent 16
(3) Transparent 32
1 This parameter is used to select which
communication profile is used.
51.06 T16 SCALE 1...65536 100 Reference multiplier/actual value divisor
for the FPBA-01. The parameter is only
effective when Transparent 16 profile is
selected and the drive is using FBA/DCU
communication profile.
51.07 FBA PAR7 These parameters are not in use.
• • •
51.26 FBA PAR26
51.27 FBA PAR
REFRESH
(0) DONE
(1) REFRESH
1 Validates any changed adapter module
configuration parameter settings.
51.28 PAR TABLE VER Displays the parameter table revision of
the fieldbus adapter module mapping file
stored in the memory of the drive.
51.29 DRIVE TYPE
CODE
Displays the drive type code of the
fieldbus adapter module mapping file
stored in the memory of the drive.
51.30 MAPPING FILE
VER
Displays the fieldbus adapter module
mapping file revision stored in the
memory of the drive.
Parameter Setting for fieldbus control
Application-
specific setting
Function/Information