Hardware manual
Communication profiles
35
5 OFF_3_STA 1 OFF3 inactive.
0 OFF3 ACTIVE.
6SWC_ON_
INHIB
1 SWITCH-ON INHIBITED
0–
7 ALARM 1 Warning/Alarm.
0 No warning/alarm.
8AT_
SETPOINT
1 OPERATION. Actual value equals reference = is within tolerance limits, i.e.
in speed control, speed error is 10% max. of nominal motor speed.
0 Actual value differs from reference = is outside tolerance limits.
9 REMOTE 1 Drive control location: REMOTE (EXT1 or EXT2).
0 Drive control location: LOCAL.
10 ABOVE_
LIMIT
1 Actual frequency or speed equals or exceeds supervision limit (set by drive
parameter). Valid in both directions of rotation.
0 Actual frequency or speed within supervision limit.
11 EXT_CTRL_
LOC
1 External Control Location EXT2 selected.
0 External Control Location EXT1 selected.
12 EXT_RUN_
ENABLE
1 External Run Enable signal received.
0 No External Run Enable signal received.
13 to 14 Drive-specific (For information, see the drive documentation.)
15 FBA_ERROR 1 Communication error detected by fieldbus adapter module.
0 Fieldbus adapter communication OK.
Bit Name Value STATE/Description