Hardware manual

Installation and parameter setup for communication profiles
53
TRANSMITTED DATA SELECTION FROM DRIVE TO PLC
52.01 FBA DATA IN1 ... 52.12
FBA DATA IN12
Defines the data transmitted from drive to fieldbus
controller and further to the PLC. Parameters are set
according to the virtual address area of the drive.
Note: If the length of the selected data is 32 bits, two
parameters are reserved for the transmission.
52.01 FBA DATA IN1 4 Status word (16-bit). Mapping: PZD1
52.02 FBA DATA IN 2 5 Actual value 1 (16-bit). Mapping: PZD2
TRANSMITTED DATA SELECTION FROM PLC TO DRIVE
53.01 FBA DATA OUT 1 … 53.12
FBA DATA OUT 12
Defines the data transmitted from fieldbus controller to
drive.
Note: If the length of the selected data is 32 bits, two
parameters are reserved for the transmission.
53.01 FBA DATA OUT 1 1 Control word (16-bit). Mapping: PZD1
53.02 FBA DATA OUT 2 2 Reference 1 (16-bit). Mapping: PZD2
Note: In the User’s Manual of the fieldbus adapter module, the parameter group number is 3 or C for parameters
52.01…52.12 and 2 or B for parameters 53.01…53.12.
51.27 FBA PAR REFRESH (1) REFRESH Validates any changed adapter module configuration
parameter settings.