Softstarters Type PST30...
This manual belongs to:
Softstarters Type PST30...
Installation and Commissioning Manual PST30...PSTB1050 1 General This is the Installation and commissioning manual for Softstarters PST30...PSTB1050 based on software version CU 05.02.xx (see STATUS INFORMATION menu) Document number: 1SFC132003M0201 Edition: 04 Revision: 03 Issue date: 2007-06-29 Data subject to change without notice. We reserve all rights to this document, even in the event that a patent is issued and a different commercial proprietary right is registered.
2 Safety This chapter describes warning and information signs used in this manual, which the user should pay attention to. The softstarter shall be installed by authorized personnel only. This manual is a part of the softstarter and should always be accessible to personnel working with this product. The manual shall always be read through before performing any installation or commissioning tasks. 3 Safety signs 3.
Chapter 1SFC132003M0201 Page 1 Introduction 9 2 Quickstart 15 3 Description 19 4 Mounting 35 5 Connection 41 6 Human-Machine Interface (HMI) 61 7 Settings and configuration 75 8 Fieldbus communication (option) 119 9 Maintenance 123 10 Functions 127 11 Trouble shooting 177 12 Diagrams 189 13 Index 193 Customer feedback report 197 7
Chapter Notes .................................................................................................................................. .................................................................................................................................. .................................................................................................................................. .....................................................................................................
Introduction Chapter 1 Introduction About the complete set of documentation for a softstarter................................ 11 About the installation and commissioning manual ............................................ 11 Intended audience ....................................................................................... 11 General ................................................................................................... 11 Requirements .....................................................
Introduction 10 1SFC132003M0201
Chapter 1 Introduction Chapter 1 Introduction 1:1 About the complete set of documentation for a softstarter For the softstarter, the following documents are available: PST30...
Chapter 1 Introduction 1:2.1.2 Requirements The installation personnel must have a basic knowledge in handling electric equipment. The commissioning and maintenance personnel must be well experienced in using this kind of equipment. 1:2.2 Chapters included • Introduction introduces the reader to this manual. • Quickstart contains information on how to, in the quickest way, install the softstarter and put it into operation. This chapter is intended for the experienced user.
Chapter 1 Introduction 1:2.4 Acronyms and abbreviations The following acronyms and abbreviations are used in this manual.
Chapter 1 Introduction 14 1SFC132003M0201
Quickstart Chapter 2 Quickstart Connection ........................................................................................................ 17 Configuration..................................................................................................... 18 Start of the motor ..............................................................................................
Quickstart 16 1SFC132003M0201
Chapter 2 Quickstart Chapter 2 Quickstart 1 2 This chapter is a short guide to how to connect, do the configuration and start the softstarter in the easiest way. Power on Fault U= 0% Menu Protection I=0.0A Warning! 3 1SFC132029F0001 Mounting, electrical connection and settings of the softstarter shall be made in accordance with existing laws and regulations and be performed by authorized personnel. Do not change any parameters in the Service Settings menu.
Chapter 2 Quickstart 2:2 Application Select Setting Back Configuration 1. Enter the Application Setting by pressing left selection key twice. Press Select using the left selection key. Figure 4. Figure 4: Application setting menu Centrifugal Store Set 2. Select the appropriate type of load using navigation keys. Figure 5. Pump Back 3. Press Store Set and Next to continue or Back to previous parameter using the selection keys. Figure 6. Figure 5: Centrifugal pump Centrifugal Next Pump Back 4.
Description Chapter 3 Description Overview ........................................................................................................... 21 Functions .......................................................................................................... 22 Markings and connections ................................................................................ 24 Type designation...............................................................................................
Description 20 1SFC132003M0201
Chapter 3 Description Chapter 3 Description This chapter describes the softstarter in general, specifications as well as available accessories and spare parts. 3:1 Overview The PST softstarter is a microprocessor-based softstarter designed with the latest technology for soft start and soft stop of squirrel cage motors. The softstarter has several advanced motor protection features as standard. The softstarter is designed to be used with or without a bypass contactor except for the larger sizes, PSTB370..
Chapter 3 Description 3:2 Functions The PST softstarter has several integrated protection and warning functions. Almost any type of fault can also be detected and displayed. All available protections, warnings, and fault indications are listed below.
Chapter 3 Description Fault Supervision functions • Phase loss • Fieldbus communication • Frequency out of range • Heat sink over-temperature • Thyristor short circuit • By-pass doesn’t open • By-pass doesn’t close • Connection fault • Non conducting thyristor • Line side fault • Kick-current fault • Internal softstarter fault Other functions • Jog • Real time clock • Event log • Keypad password 1SFC132003M0201 23
Chapter 3 Description 3:3 Markings and connections Line side connection By-pass connection (PST30...
Chapter 3 Description 3:4 Type designation } } } } } PSTB370-600-70 Supply Voltage 70 = 100 - 250 V 50/60 Hz Main Voltage 600 = 208 - 600V 50/60 Hz 690 = 400 - 690V 50/60 Hz Current rating 370 = 370A 720 = 720A etc.
Chapter 3 Description 3:6 Environmental influence The product is designed to minimize the environmental affects during manufacturing and use of the product. Most of the materials used, are of recycle type and shall be handled and recycled according to existing laws. Further information regarding used material and recycling of the product can be found at: www.abb.com/lowvoltage 3:7 26 Specifications Degree of protection (Main circuit) IP 10 for PST30...72 IP 00 for PST85...
Chapter 3 Description 3:8 Technical data 3:8.1 General General data Rated insulation voltage, Ui 690 V Rated operational voltage, Ue 208 - 600 V / 400 - 690 V Rated supply voltage, Us 100 - 250 V 50/60 Hz Rated frequency 50 / 60 Hz Voltage tolerances +10% to -15% Frequency tolerances ± 5% Rated impulse withstand voltage 2 kV Number of controlled phases 3 Programmable inputs 24 V DC, 10mA Output relays 250 V AC, Ith = 5A, Ie = 1.
Chapter 3 Description Softstarter type, 600 V and 690 V Bussmann fuses A Holders Type PSTB470 900 170M5015 170H3004 PSTB570 900 170M5015 170H3004 PSTB720 1250 170M5018 170H3004 PSTB840 1500 170M6018 170H3004 PSTB1050 xxx-600-70 1800 170M6020 170H3004 PSTB1050 xxx-690-70 1600 170M6019 170H3004 3:8.
Chapter 3 Description Type PST142 PST175 PST210 PST250 Connection type Line Delta Line Delta Line Delta Line Delta Rated current Ie (A) 142 245 175 300 210 360 250 430 Motor size 380 - 415V (kW) 75 132 90 160 110 184 132 220 Motor size 480V (hp) 100 150 125 200 150 250 200 300 Motor size 600V (hp) 125 200 150 250 200 300 250 350 AC-3 rating built in by-pass 400V (A) - - - - Power loss at rated current (W) 435 540 645 765 Power supply requirements (
Chapter 3 Description 3:8.4 Weights Type Weight in kg Weight in lbs PST30...50 4.8 10.6 PST60...72 5.0 11.0 PST85 11.2 24.7 PST105...142 13.0 28.7 PST175...210 21.5 47.4 PST250...300 23.0 50.7 PST370...470 31.0 68.3 PSTB570 52.0 114.6 PSTB720 55.0 121.3 PSTB840...1050 60.0 132.3 3:8.5 UL information Equipment suitable for use in a circuit with maximum available fault current as shown when protected by devices indicated.
Chapter 3 Description 3:8.6 Dimensions 1SFC132038F0001 PST30...72 Figure 2: Dimensions PST30...72 (mm) (1 mm = 0.0394 in) 1SFC132039F0001 PST85...142 Figure 3: Dimensions PST85...142 (mm) (1 mm = 0.
Chapter 3 Description 1SFC132130F0201 270 390 251 1SFC132131F0201 64,5 12 PST85...142 with marine pack 46,5 155 46,5 52,5 7 262 Figure 4: Dimensions PST85..142 with marine kit (mm) (1 mm = 0.0394 in) 7 1SFC132040F0001 12 PST175...300 Figure 5: Dimensions PST175..300 (mm) (1 mm = 0.
Chapter 3 Description 1SFC132041F0001 PSTB370...470 Figure 6: Dimensions PSTB370...470 (mm) (1 mm = 0.0394 in) 1SFC132042F0001 PSTB570...1050 243 162 Figure 7: Dimensions PSTB570...1050 (mm) (1 mm = 0.
Chapter 3 Description 34 1SFC132003M0201
Mounting Chapter 4 Mounting Receiving, unpacking and checking.................................................................. 37 Intermediate storage .................................................................................... 37 Mounting ........................................................................................................... 37 Handling when mounting ............................................................................. 37 Requirements...................................
Mounting 36 1SFC132003M0201
Chapter 4 Mounting Chapter 4 Mounting This chapter describes instructions on how to receive the softstarter and how to mount it in a proper way. 4:1 Receiving, unpacking and checking • Check that the package is turned with the correct side up, figure 1. • Check for transport damages. • Remove the transport casing. • Visually inspect the softstarter. 1SFC132043F0001 • Check that the serial number corresponds with the delivery documents.
Chapter 4 Mounting 4:2.2 Requirements See Chapter 3 “Description” for environmental requirements. 4:2.3 Minimum distance to wall/front 1SFC132044F0001 To have a suitable cooling, the softstarter has to be mounted vertically, and in such a way that the airways are not blocked, see figure 2. Follow the minimum distances to wall/front, figure 2 and the table below. The values are minimum distances. Softstarter type Figure 2: Airways A A (mm) B (mm) C (mm) PST30...72 100 10 20 PST85...
Chapter 4 Mounting 4:2.4 Minimum enclosure sizes In applications where the softstarter is installed in an enclosure, the following minimum enclosure sizes and fan capacities are recommended. Minimum enclosure dimensions Softstarter type W H D Fan capacity PST30...72 300 400 250 42 m3/h PST85...142 400 500 300 95 m3/h PST175...300 500 600 300 210 m3/h PSTB370...470 600 600 400 210 m3/h PSTB570...1050 750 900 400 210 m3/h (1mm = 0.
Chapter 4 Mounting 40 1SFC132003M0201
Connection Chapter 5 Connection General ............................................................................................................. 43 Electrical connection ......................................................................................... 43 Main circuit................................................................................................... 43 External By-Pass contactor..................................................................... 45 Protective earthing .........
Connection 42 1SFC132003M0201
Chapter 5 Connection Chapter 5 Connection This chapter describes the electrical connections as well as connections for communication devices that have to be made before you can use the softstarter. 5:1 General Caution! All wiring and connection must be carried out by a qualified electrician, and in accordance with installation standards and safety regulations. For quickly minimized connection, see Chapter 2 “Quickstart” 5:2 Electrical connection 5:2.1 Main circuit Softstarters PST30...
Chapter 5 Connection When used for marine applications, please use standard installation cables with concentric conductors for earth. This earth conductor shall be 360 degree connected to earth in the cable glands or in the near of the gland. Warning! Capacitors for power factor compensation are not allowed in between the softstarter and the motor, since this can cause current peaks which can burn the thyristors in the softstarter.
Chapter 5 Connection 5:2.1.1 External By-Pass contactor B3 B2 An external by-pass contactor can be used for softstarters size PST30...300 (built in for size PSTB370...1050). B1 Connect the contactor to terminals B1, B2, and B3 on the line side and terminals 2T1, 4T2, and 6T3 on the motor side. The terminal marking is printed on the front label.
Chapter 5 Connection PST 30...72 2 1 x 6 ...... 70 mm 2 x 6 ...... 35 mm 2 4 mm M8 AWG 1...8 1 x 6 ...... 70 mm 22 2 x 6 ...... 35 mm 2T1 4T2 6T3 6 Nm - 53 lb.in 14 1L1 B1 3L2 B2 5L3 B3 14 PST 85...142 1L1 B1 3L2 B2 5L3 B3 M8 Max. 24 mm Max. 22 mm Max. 8 mm 2T1 4T2 6T3 9 Nm - 80 lb.in PST 175...300 1L1 B1 3L2 B2 5L3 B3 M8 Max. 32 mm Max. 30 mm Max. 10 mm 2T1 4T2 6T3 18 Nm - 160 lb.in PSTB 370...470 1L1 3L2 5L3 M10 Max. 45 mm Max. 47 mm Max.
Chapter 5 Connection 5:2.2 Supply voltage and control circuit When used for marine applications, and if feeding from the outside of the enclosure, then please use a standard cable for feeding the supply voltage and for the control circuit, with an auxiliary bare conductor (earth conductor) and make a 360 degree connection to earth in the glands, or close to the glands.
Chapter 5 Connection 5:2.2.3 Start and Stop, terminals 4, 5, 8, 9, 10, 11 Internal control voltage 0V 100-25Hz 50/60 4 Stop 0 rt In Sta 7 In1 8 10 Vn Vc 11 12 Vp Vp 1SFC132054F0001 3 2 1 6 5 9 The softstarter has a built-in holding circuit which does not require any external power source for start and stop, see Figure 11. A conventional circuit with auxiliary relay is also possible, see Figure 12.
Chapter 5 Connection External control voltage The softstarter can, if required, also be used with an external 24 V DC source from a PLC or similar. Connect the cables according to Figure 14 or Figure 15 depending on which type of control method is used. Warning! Terminal 4, 5, 6, 7, 8, 9, 10, and 11 should be connected using 24V DC only. Other voltages may damage the softstarter and the warranty may no longer be valid.
Chapter 5 Connection 5:2.2.4 Programmable inputs, terminals 6 and 7 The softstarter has two programmable inputs. In0, default reset event. In1, default reset event. See Chapter 7 “Settings and configuration” for programming. 1. Connect the cables according to Figure 18 or Figure 19 depending on whether internal or external source is used. 0V 100-25Hz 50/60 4 Stop 5 Start In0 7 In1 9 8 Vn Vc 11 12 Vp Vp 1SFC132059F0001 3 2 1 6 10 Wiring for sequence start, see next page.
Chapter 5 Connection Programmable inputs (Sequence start) When sequence start is going to be used, the wiring should be according to Figure 21 or Figure 22. The start command (terminal 5, 6, and 7) must be maintained during the complete start sequence and run otherwise a direct stop will be performed. 2nd Start seq. 3rd Start seq. Stop 1st Start seq. 3rd Start seq. 1st Start seq. 2nd Start seq.
Chapter 5 Connection 5:2.2.5 Programmable output relay K4, terminals 12, 13, and 14 The output relay gives signal depending on the selected function. Default: Run See Chapter 7 “Settings and configuration” for programming. 1. Connect the cables to terminal 12, 13, and 14. 20 18 17 16 0 8 Vc Vn 10 11 15 K6 K5 K4 1SFC132062F0001 7 In1 9 12 14 13 19 Vp Vp Figure 24: Terminals 12, 13, 14 5:2.2.
Chapter 5 Connection 5:2.2.7 Programmable output relay K6, terminals 18, 19, and 20 The output relay gives signal depending on the selected function. Default: Event See Chapter 7 “Settings and configuration” for programming. 1. Connect the cables to terminal 18, 19, and 20. 20 18 17 16 0 8 Vc Vn 11 12 14 15 K6 K5 K4 1SFC132064F0001 7 In1 9 10 13 19 Vp Vp Figure 27: Terminals 18, 19, 20 5:2.2.
Chapter 5 Connection 5:2.2.9 Analog output If the analog output is used, the cables shall be connected to terminals 23 and 24, see Figure 30. See Chapter 7 “Settings and configuration” for programming. 1S FA IEC 894 0 07 Us : 10 947 R1 0-4 Ie: 002 37-7 250V -2 AC 2A /DC UL 7 508 Ue 2: Mad Uc : AC : 10 e in In lin 0-25 220- -53 Sw Ove e FL 0V ed 23 a: A: rload AC en 37-6 18,5 0 38 8-1 /D Ca CA 8A C 0-40 .
Chapter 5 Connection 100-250V 50/60 Hz X9 Figure 32: Connection when the contactor is operated from the keypad (factory wiring) M3 Figure 33: Connection when the by-pass contactor is operated separately (emergency DOL) 3,5x0,6 0,14 ... 2,5 mm 2 AWG 12 ... 22 1. . . . . . . . . . . . . . . . . . . . . . . . 20 0,14 ... 2,5 mm2 0,5 Nm - 4,3 lb.in 1SFC132053F0001 X9 Figure 34: Tightening torques and cable dimensions (1 mm=0.
Chapter 5 Connection 5:3 5:3.1 Fieldbus communication 20 19 18 17 Connection of communication devices (optional) K6 16 1 L 5 4 3 2 N 6 10 9 8 7 12 15 14 K5 K4 Vp Vp Vn Vc In1 Stop Start In0 1SFC132066F0001 Hz 0V 100-25 , 50/60 AC/DC 11 13 The fieldbus communication plug shall be connected to the communication interface on the front of the PST, see Figure 35. Make sure that the plug is in correct position and tighten the screw with 0.8 Nm (7.
Chapter 5 Connection 5:3.2 External keypad An external keypad for door mounting can be connected to the softstarter. A 3-meter cable including both the serial communication and the power supply to the keypad makes the connection. The cable shall be connected to the external keypad connection at the bottom of the softstarter. The external keypad can also be used for transferring parameters from one softstarter to another during commissioning (temporarily handheld).
Chapter 5 Connection 5:3.3 Transferring of parameters To transfer(copy) parameters from one softstarter to another, connect the keypad to the chosen softstarter and follow the sequence below. 5:3.3.1 Uploading of parameters Enter the menu Transfer par. Select To Keypad and confirm by pressing Select. A text Load to keypad will be displayed. Continue by pressing Execute and then Yes when the text Are you sure is displayed.
Chapter 5 Connection 5:3.3.
Chapter 5 Connection 60 1SFC132003M0201
Human-Machine Interface (HMI) Chapter 6 Human-Machine Interface (HMI) Overview ........................................................................................................... 63 Application ................................................................................................... 63 Design.......................................................................................................... 64 Password .................................................................................
Human-Machine Interface (HMI) 62 1SFC132003M0201
Chapter 6 Human-Machine Interface (HMI) Chapter 6 Human-Machine Interface (HMI) This chapter describes how the human-machine interface (keypad and display) works. 6:1 Overview 6:1.1 Application The Human-Machine Interface is used for several purposes such as programming the softstarter, i.e. setting up inputs and outputs, protection functions, warning levels, fieldbus communication etc. The HMI is also used for monitoring, local control and status information of the softstarter.
Chapter 6 Human-Machine Interface (HMI) 6:1.2 Design 1 2 The HMI consists of: • Status indication LED indicators • LCD display Power on Fault • Selection and Navigation keys Protection U= 0% Menu I=0.0A The LED indicators work as follows: LED 4 Figure 1: Human-Machine Interface 1 2 3 4 Status indication LEDs LCD display Selection keys Navigation keys Setting Change Power on Setting Store Fault Ie Fault Ie Description Power on Green Supply voltage connected. Fault Indicates faults.
Chapter 6 Human-Machine Interface (HMI) The functionality of the keypad is illustrated by the following example: Changing the Rated motor current (Setting Ie). 1. You will find the setting as well as a short explanation and the path to it in Chapter 10 “Functions” . Path in menu: Menu/SETTINGS/Functional Settings/ Start/Stop /Setting Ie U= 0% Menu I=0.0A 2. The top level of the softstarter start menu looks as in figure 3. Press the left selection key to enter the menu.
Chapter 6 Human-Machine Interface (HMI) 6:1.3 Password To lock the keypad from control and change of settings, a password can be set. When the keypad is locked, all menus are available but no changes can be done nor any actions can be taken. 6:1.3.1 Setting password The password at delivery is always 1. Change Select Password Back Figure 11: Change password New Password 1 Store Back Figure 12: New password New Password Next 1.
Chapter 6 Human-Machine Interface (HMI) 6:1.4 Locking/unlocking the keypad 1. Press the upper navigation key twice to enter the parameter Keypad is, figure 16. Keypad is Lock Active Back Figure 16: Keypad is menu Keypad is Unlocked Locked Back Figure 17: Locked keypad menu 1SFC132003M0201 2. The keypad is unlocked if the display is indicating Active in the upper right corner. 3. Lock the keypad. 4. Select Lock. Enter the correct password Select Enter. Keypad is now locked.
Chapter 6 Human-Machine Interface (HMI) 6:2 Menu tree 6:2.
Chapter 6 Human-Machine Interface (HMI) 6:2.2 Top level Top level Top Level contains general softstarter information, and the menus can be reached from here. The selections are presented one by one on the top row. Use navigation keys to present all selections. Press Select to enter a function. Press Back to return to previous state. Settings Local Control Event Log Status Information Function Description Settings Set up softstarter parameters. Local Control Control the softstarter.
Chapter 6 Human-Machine Interface (HMI) 6:2.4 Local Control menu Top level Settings Local Control Start/Stop Jog The Local Control menu is used to start or stop the motor from the keypad. When a type of local control is selected the softstarter can only be controlled by the keypad. The softstarter operation state (stopped/running) remains when selecting local control until it is changed there. Previous type of control is activated again when the local control is exited.
Chapter 6 Human-Machine Interface (HMI) 6:2.4.2 Jog Top level Settings Local Control Start/Stop Jog Enter the Jog menu, figure 23. Select Jog. The motor will start and accelerate to rated speed according to the set parameters as long as the Jog command is activated. The motor stops immediately as soon as the command is released. DOL Start Event Log Status Information Reset Events Figure 23: Jog menu 6:2.4.3 DOL start (PSTB370...
Chapter 6 Human-Machine Interface (HMI) 6:2.5 Event Log menu Top level Settings Local Control The Event Log menu is used to check the event log in the softstarter. When entering this menu the 21 latest events in the log are presented, in chronological order with the latest event as No. 1, the second latest as No. 2 etc. The events are presented with “type of event”, date and time. Use navigation keys to view all entries in the event log.
Chapter 6 Human-Machine Interface (HMI) 6:2.7 Reset Events menu Top level Settings Local Control The Reset Events menu is entered automatically when a fault has occurred or a protection is activated. It can also be entered via the main menu. Use navigation keys to view if there are several events to reset.
Chapter 6 Human-Machine Interface (HMI) 74 1SFC132003M0201
Setting and configuration Chapter 7 Settings and configuration Settings ............................................................................................................. 77 Overview of all accessible settings (different menus) .................................. 78 Parameter list............................................................................................... 81 Description of menus ........................................................................................
Setting and configuration 76 1SFC132003M0201
Chapter 7 Settings and configuration Chapter 7 Settings and configuration 7:1 Settings Settings can be done in three different ways: • Keypad • Fieldbus communication • External keypad (option) With the keypad, settings can be done as individual parameter setting or selection of predefined parameters for different applications. The unit has one complete set of parameters but some parameters have extra sets for sequence start.
Chapter 7 Settings and configuration 7:1.
Chapter 7 Settings and configuration Setting/parameter Top Application Basic Functional Presentation All Reset all level Setting Settings Settings Settings Settings Settings Low current warning Low current warning level Overload warning Overload warning level Thyristor (SCR) overload warning Phase loss fault, type of operation Fieldbus fault, type of operation Frequency fault, type of operation Heat sink over-temperature fault, type of operation Thyristor short circuit fault, type of operation X X X X X
Chapter 7 Settings and configuration Setting/parameter Dual current limit time Dual current limit level 80 Top Application Basic Functional Presentation All Reset all level Setting Settings Settings Settings Settings Settings X X 1SFC132003M0201
Chapter 7 Settings and configuration 7:1.2 Parameter list Param. Description number Display text Setting range Default value 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 Setting Ie Start Ramp Stop Ramp Init Volt End volt Step down Current Lim Kick Start Kick Level Kick Time Start Range Stop Range Overload OL Class OL Class S OL Class R OL Op Locked Rotor Lock R Lev Lock R Time Lock R Op Underload Underl Lev Underl Time Underl Op Phase Imb Ph Imb Lev Ph Imb Op 9.0...
Chapter 7 Settings and configuration Param.
Chapter 7 Settings and configuration Param.
Chapter 7 Settings and configuration Param. Description number Display text Setting range Default value 127 128 Analog output, voltage range max Analog output, active power range max kW U Range Max kW Range Max 10...1000V 1...3000kW 129 Analog output, active power range max hp hp Range Max 1...4000hp 130 Analog output, reactive power range max Q Range Max 1...3000kVAr 131 Analog output, apparent power range max S Range Max 1...
Chapter 7 Settings and configuration U= 0% Menu 7:2 Description of menus I=0.0A Uin Change Password Select Back OK Back For detailed description of each function, see Chapter 10 “Functions” . 7:2.1 Top level Motor Temp. 0% Back 11:08 Back SCR Temp. 60% Back In= 0000 Out= 0000 Back Start Mode Volt Back Keypad is Lock 2003-01-30 Active Back Stop Mode This level contains information about output voltage and current, heat sink temperature, real time clock and more.
Chapter 7 Settings and configuration Start mode Start Mode Volt Back Figure 6: Start mode The start mode of the motor is displayed. The possible options are: • Volt • Torque Stop mode Stop Mode Torque Back The stop mode of the motor is displayed. The possible options are: • Volt Figure 7: Stop mode • Torque Status of inputs/outputs In= 0000 Out= 0000 Back The status of the Programmable inputs and outputs is displayed with “0” for not activated or “1” for activated.
Chapter 7 Settings and configuration 7:2.2 Application Setting Top level Application Setting Settings Basic Settings Functional Settings The Application setting menu consists of predefined parameters for the selected application and should be used if an easy and quick set-up is required. Only a few parameters have to be set before start of the motor is possible. All necessary input data will show up in an automatic loop.
Chapter 7 Settings and configuration Setting Ie Setting Ie Store 100A Set the current that the softstarter will be exposed to i.e. rated motor current if the unit is connected In Line. Figure 16: Setting Ie menu For units connected Inside Delta the Setting Ie must be set according to the current in the delta circuit = 58% ( 1 ⁄ ( 3 ) ) of the rated motor current. Press Store to save the data after setting the current.
Chapter 7 Settings and configuration Tuning parameters Nine parameters can be tuned individually if a more specific adjustment is required. Each parameter is described in Chapter 10 “Functions” .
Chapter 7 Settings and configuration 7:2.3 Basic Settings Top level Settings Application Settings Basic Settings Functional Settings Presentation Settings Service Settings The Basic settings menu consists of the most common start/ stop parameters required for the set-up. Each parameter can be adjusted separately. For a deep description of each parameter, see Chapter 10 “Functions” . Enter the Basic settings Enter the menu by selecting Basic Settings.
Chapter 7 Settings and configuration Start ramp Set the ramp time for start. Press Store to save the time for the start ramp. Stop ramp Set the ramp time for stop (softstop). Note that this function shall only be used for applications with small flywheel masses, for example pumps and conveyors (in case fragile material is transported). Press Store to save the time for the stop ramp. Initial voltage (Init Volt) Set the initial voltage level. Press Store to save the initial voltage.
Chapter 7 Settings and configuration 7:2.4 Functional Settings Top level Settings Application Settings The Functional setting menu consists of groups with parameters arranged by function such as protection, warning, fault, fieldbus communication etc. This menu should be used if a more advanced set-up is required. For a detailed description of each parameter, see Chapter 10 “Functions” .
Chapter 7 Settings and configuration Kick Start Activate the Kick Start function by entering this menu. Press Store to save the selection. Kick Level Set the required level of the Kick Start. Press Store to save the data. This menu will only be visual if Kick Start is activated. Kick Time Set the required time for the kick start. Press Store to save the data. This menu will only be visual if Kick Start is activated. Start Range The ramp time for start can be set between 1 and 30 seconds as default.
Chapter 7 Settings and configuration 7:2.4.2 Torque control Settings Functional Settings Start/Stop To set parameters related to torque control, enter the Torque control group. Start mode Torque control Protections Select which type of ramp that shall be used during start. The possible options are: • Volt Warnings Faults Inputs Outputs Analog Output • Torque Press Store to save the selected start mode. Stop mode Select which type of ramp that shall be used during stop.
Chapter 7 Settings and configuration 7:2.4.3 Protections Settings Functional Settings Start/Stop To set parameters related to the protections, enter the Protections group. Torque control Protections Warnings Faults Caution! The motor may start unexpectedly if there is a start signal present when the softstarter has tripped for a protection and a reset is performed.
Chapter 7 Settings and configuration If overload “Dual” is selected, the following settings will be available: Overload start class (OL Class S) Select the required class for overload relay during start condition. Following classes are available: • 10A • 10 • 20 • 30 Press Store to save the selected class. Overload run class (OL Class R) Select the required class for overload relay during continuous run. Following classes are available: • 10A • 10 • 20 • 30 Press Store to save the selected class.
Chapter 7 Settings and configuration Locked rotor protection (Locked Rotor) Activate the protection if required by changing to Yes. If “Yes” is selected, the following settings will be available: Locked rotor level (Lock R Lev) Set the level of the locked rotor protection. Available only if the protection is selected. Locked rotor time (Lock R Time) Set the time for the locked rotor protection. Available only if the protection is selected.
Chapter 7 Settings and configuration Underload protection (Underload) Activate the protection if required by changing to Yes. If “Yes” is selected, the following settings will be available: Underload level (Underl Lev) Set the level of the underload protection. Available only if the protection is selected. Underload time (Underl Time) Set the time for the underload protection. Available only if the protection is selected.
Chapter 7 Settings and configuration Phase imbalance protection (Phase Imb) Activate the protection if required by changing to Yes. If “Yes” is selected, the following settings will be available: Phase imbalance level (Ph Imb Lev) Set the level of the phase imbalance protection. Available only if the protection is selected.
Chapter 7 Settings and configuration Phase reversal protection (Phase Rev) Activate the phase reversal protection if required by changing to Yes. If “Yes” is selected, the following setting will be available: Phase reversal type of operation (Ph Rev Op) Select what operation shall be asserted if the phase reversal protection is activated: Stop–M The motor will stop and a manual reset is required. Stop–A The motor will stop and automatic reset is performed. Ind Only indication will be given.
Chapter 7 Settings and configuration 7:2.4.4 Warnings Settings Functional Settings Start/Stop To set parameters related to the warnings, enter the Warnings group: Torque control High current warning (Warn I=High) Protections Warnings Activate the warning function if required by changing to Yes. Press Store to save the selected operation High current warning level (Wa I=H Lev) Faults Inputs Set the level of the high current warning. Available only if the function is selected.
Chapter 7 Settings and configuration 7:2.4.5 Faults Settings Functional Settings Start/Stop Torque control Caution! Protections Warnings Faults Inputs Outputs The motor may start unexpectedly if there is a start signal present when the softstarter has tripped for a fault and a reset is performed. This reset can be either manual (StopM) or automatic (Stop-A).
Chapter 7 Settings and configuration Stop–A The motor will stop and an automatic reset is performed. Press Store to save the selected operation. Thyristor short circuit fault, type of operation (SCR SC Op) Select what operation shall be asserted if a fault occurs with shorted thyristor: Stop–M The motor will stop and a manual reset is required. Stop–A The motor will stop and an automatic reset is performed. Press Store to save the selected operation.
Chapter 7 Settings and configuration 7:2.4.6 Inputs Settings Functional Settings Start/Stop Torque control Protections Warnings Faults Inputs To set parameters related to the programmable inputs, enter the Inputs group. First programmable input (In0) Select the required function for the input In0. Press Store to save/activate the selected function. One of the following functions can be selected: None No specific function (not activated). Reset Reset of an event.
Chapter 7 Settings and configuration Second programmable input (In1) Select the required function for the input In1. One of the following functions can be selected: None No specific function (not activated). Reset Reset of an event. Enable When the In1=0 the softstarter stops immediately. When In1=1 the softstarter is in normal operation. Overrides all other inputs, except LOCAL CONTROL. Jog Performs a start ramp until command is released, then the motor stops immediately.
Chapter 7 Settings and configuration 7:2.4.7 Outputs Settings Functional Settings Start/Stop To set parameters related to the programmable outputs, enter the Outputs group. Torque control Output relay K4 (Relay K4) Protections Warnings Select the required function for the output relay K4. One of the following functions can be selected: Run Run indication. TOR Top of ramp indication.
Chapter 7 Settings and configuration Output relay K6 (Relay K6) Select the required function for the output relay K6. One of the following functions can be selected: Run Run indication. TOR Top of ramp indication. Event Indication of selected event(s), see relay K4. Press Store to save/activate the selected function. Software output V7 (SW Outp V7) Select the required function for the fieldbus communication output SW Outp V7. One of the following functions can be selected: Run Run indication.
Chapter 7 Settings and configuration 7:2.4.8 Analog output Settings Functional Settings Start/Stop Torque control Protections Warnings Faults To set parameters related to the analog output, enter the Analog output group. Analog output (Analog Out) Activate the analog output by changing to Yes. Since the analog output uses the same terminals as the PTC protection, it is not possible to use both of these functions at the same time.
Chapter 7 Settings and configuration • Current of the motor (I Amp) • Main voltage (U Volt) • Active power kW (P kW) • Active power hp (P hp) • Reactive power (Q kVAr) • Apparent power (S kVA) • Calculated temperature of the motor (TmpMot) • Calculated temperature of the SCR (TmpSCR) • Power factor (cosPhi) Press Store to save the type of value to output.
Chapter 7 Settings and configuration 7:2.4.9 Fieldbus Settings Functional Settings Start/Stop To set parameters related to the fieldbus communication, enter the Fieldbus group. Torque control Fieldbus control (Fieldb Ctrl) Protections Warnings Faults Inputs Outputs Activate the fieldbus control of the softstarter by changing to Yes. Press Store to save the selected function. Fieldbus type (Fieldb Type) Select what fieldbus type is used. AS-Interface Used for AS-Interface protocol.
Chapter 7 Settings and configuration 7:2.4.10 Sequence start Settings Functional Settings Start/Stop Torque control Protections The sequence start function can be used for starting several motors or multiple speed motors with different parameter sets such as individual ramp times, initial voltages, current limits etc. Up to three individual parameter sets can be used simultaneously. Warnings Faults Inputs Outputs Analog Output The LOCAL CONTROL menu can not be entered if Sequence start is selected.
Chapter 7 Settings and configuration Third sequence setting current (3rd Set Ie) Set the current for the third parameter group. Press Store to save the value. This parameter will only be displayed if parameter No of Seq is set to 3. Function of first programmable input (In0) This parameter will automatically be set as Start2. Function of second programmable input (In1) This parameter will automatically be set as Start3. Overload The overload protection is not activated when sequence start is selected.
Chapter 7 Settings and configuration Second sequence parameters (2nd Seq .Param.) To set parameters related to the second sequence, enter the 2nd Seq. Param. group. Following parameters can be adjusted: 2nd Set Ie Setting current. Start Ramp2 Ramp time for start. Init Volt2 Initial voltage. Curr Lim2 Current limit. Press Store to save the selected parameter. Third sequence parameters (3rd Seq .Param.) To set parameters related to the third sequence, enter the 3rd Seq. Param. group.
Chapter 7 Settings and configuration 7:2.5 Presentation Settings Top Level Settings Application Settings Basic Settings Functional Settings The Presentation setting menu consists of parameters for the LCD set-up. The presentation language can be chosen among 13 different languages. The real-time clock for the softstarter can be set in this menu. Enter the Presentation settings Enter the menu by selecting Presentation Set.
Chapter 7 Settings and configuration LCD Auto Off The LCD will be switched off automatically by a pre-set time between 1 - 255 minutes. If the display has switched off, a touch on any of the keys will switch it on again. Date Type The date can be presented in three different ways.
Chapter 7 Settings and configuration 7:2.6 Service Settings Top Level Settings The service setting menu consists of parameters used for maintenance and repair. This menu shall never be used by anybody but authorized service personnel. Application Settings Basic Settings Functional Settings Warning! Presentation Settings If parameters are changed the consequences can be malfunction but also damage to the softstarter and the warranty may not be valid any longer.
Chapter 7 Settings and configuration 7:2.7.1 Changed Settings Top Level Settings Application Settings The Changed settings menu consists of the parameters that have been changed in contrast to the factory default setting. If no parameters have been changed, the LCD will display No Changed Settings. Basic Settings Functional Settings Presentation Settings Service Settings All Settings Changed Settings Reset all Settings Operation Mode Figure 39: Changed Settings menu 7:2.7.
Chapter 7 Settings and configuration 7:2.7.3 Operation mode Top Level Settings Application Settings Basic Settings Functional Settings The Operation mode makes it possible to switch between two different modes in the softstarter, a demo mode and the regular operation mode. By entering the demo mode, programmable inputs/outputs, start and stop circuits, by-pass contactor etc. can be tested before the unit is taken into operation.
Fieldbus communication (option) Chapter 8 Fieldbus communication (option) Overview ......................................................................................................... 121 Required accessories ................................................................................ 121 Instructions.................................................................................................
Fieldbus communication (option) 120 1SFC132003M0201
Chapter 8 Fieldbus communication (option) Chapter 8 Fieldbus communication (option) 8:1 Overview The PST softstarter has an interface on the front for connecting the ABB fieldbus plug used for fieldbus communication. Through this interface it is possible to control the softstarter, achieve status information, as well as up and down-load of parameters. The interface between the softstarter and the fieldbus plug is always the same.
Chapter 8 Fieldbus communication (option) 8:1.2 Instructions To do the set-up of input/output telegrams, parameter settings etc. following instructions are available at www.abb.
Maintenance Chapter 9 Maintenance Regular maintenance ...................................................................................... 125 Service and repair ...........................................................................................
Maintenance 124 1SFC132003M0201
Chapter 9 Maintenance Chapter 9 Maintenance This chapter describes the maintenance required for the softstarter. In principle, the product is maintenance free but some items should be checked regularly. Caution! Do not open the softstarter or touch any live parts when the main and supply voltage is connected. 9:1 Regular maintenance • Check that all mounting bolts/screws are fastened. Tighten if necessary. • Check that all connections of main, control- and supply circuits are fastened.
Chapter 9 Maintenance 126 1SFC132003M0201
Function Chapter 10 Functions Setting current................................................................................................. 131 Start mode ...................................................................................................... 132 Stop mode....................................................................................................... 133 Tune torque control ......................................................................................... 134 Start ramp ....
Function External by-pass ............................................................................................. 151 High current warning ....................................................................................... 152 High current warning level............................................................................... 152 Low current warning........................................................................................ 152 Low current warning level ..........................
Chapter LCD automatic switch-off ................................................................................ 172 Password ........................................................................................................ 173 Date type......................................................................................................... 173 Year ................................................................................................................ 174 Month ............................
Chapter 130 1SFC132003M0201
Chapter 10 Functions Chapter 10 Functions This chapter describes all settings and functions possible in the softstarter, as well as the easiest way of finding them. The respective default values, setting ranges and parameter texts shown in the display are also stated. 10:1 Setting current Path in menu: Menu/SETTINGS/Functional Settings/ Start/Stop / Setting Ie The setting of this parameter shall be according to the current the softstarter is exposed to.
Chapter 10 Functions 10:2 Start mode U Path in menu: Menu/SETTINGS/Functional Settings/ Torque control/ Start Mode Start Using the PST softstarter it is possible to choose between two different types of start ramps. These are voltage ramp and torque ramp. Time rpm When using the voltage ramp, the voltage is increased linearly from the start level to full voltage during start. Since the torque depends on both the voltage and the current, the torque curve does not always follow the voltage curve.
Chapter 10 Functions 10:3 Stop mode U Path in menu: Menu/SETTINGS/Functional Settings/ Torque control/ Stop Mode Stop Using the PST softstarter it is possible to choose between two different types of stop ramps. These are voltage ramp and torque ramp. Time Voltage ramp When using the voltage ramp, the voltage is decreased linearly from full voltage to the end voltage during stop. Since the torque depends on both the voltage and the current, the torque curve does not always follow the voltage curve.
Chapter 10 Functions 10:4 Tune torque control Path in menu: Menu/SETTINGS/Functional Settings/Torque control/ Tune T-Ctrl With this parameter it is possible to change the speed of the regulator that regulates the voltage so that the torque will follow a predefined torque curve. In most cases, this parameter will not have to be changed from its default value which is 100%. If a dip occurs in the torque curve during stop, increasing this parameter can solve the problem.
Chapter 10 Functions 10:6 Stop ramp 1SFC132096F0001 Path in menu: Menu/SETTINGS/Functional Settings/ Start/Stop / Stop Ramp Stop Figure 6: Stop ramp When a stop signal is given, the softstarter performs a stop ramp by controlling the output voltage to the motor so that either the voltage or the torque decreases from full voltage to end voltage, depending on which ramp type is selected. If the ramp time is set to 0, the softstarter will cut the voltage directly when the stop command is given.
Chapter 10 Functions 10:8 End voltage Path in menu: Menu/SETTINGS/Functional Settings/ Start/Stop / End Volt U 100% 1SFC132098F0001 70% This parameter makes it possible to set the voltage level where the stop ramp ends. The voltage or the torque will decrease from full voltage to this level and then cut the power to the motor. This function will be active only if parameter Stop ramp is used.
Chapter 10 Functions 10:10 Current limit Path in menu: Menu/SETTINGS/Functional Settings/ Start/Stop / Current Lim U 100% Fvoltage FixedFixed Reached set level of current limit 30% t2 t1 I 5 It is possible to limit the starting current by using this function. When the current limit is reached, the output voltage stays stable until the current level falls below the limit, then the ramping continues.
Chapter 10 Functions 10:12 Kick start 1SFC132101F0001 Path in menu: Menu/SETTINGS/Functional Settings/ Start/Stop / Kick Start Figure 12: Kick start In some applications it can be necessary to kick loose the motor i.e. initial friction, and therefore a kick start can be used. With this function a selectable fix voltage is applied during a settable time. Note that the current limit function is not working during kick start.
Chapter 10 Functions 10:15 Start ramp range Path in menu: Menu/SETTINGS/Functional Settings/ Start/Stop / Start Range The time of the start ramp is settable up to 30 seconds as default, but if required the range could be extended up to 120 seconds by this parameter. A too long ramp time will increase the risk of tripping the overload protection.
Chapter 10 Functions 10:17 Overload protection type Path in menu: Menu/SETTINGS/Functional Settings/ Protections/Overload This parameter makes it possible to set the required function of the integrated motor overload protection. Too high motor temperature causes a stop of the motor and a reset is necessary before a restart is possible. The motor overload protection has three different modes: No The protection is not activated. Normal The protection is in normal operation.
Chapter 10 Functions 10:19 Overload protection, dual type, start class Path in menu: Menu/SETTINGS/Functional Settings/ Protections/Overload/Dual Class S This parameter makes it possible to set the required class of the overload protection during start. When full voltage is reached there will be a switch-over to run class after 30 seconds. (see below).
Chapter 10 Functions 10:21 Overload protection, type of operation Path in menu: Menu/SETTINGS/Functional Settings/ Protections/Overload/OL Op This parameter makes it possible to select between three different actions by the softstarter when the protection is activated. It is active only if the motor overload protection is selected. 142 Stop–M The motor stops and a manual reset is required before restart. Stop–A The motor stops and an automatic reset is performed when the fault disappears (motor temp.
Chapter 10 Functions 10:22 Locked rotor protection Path in menu: Menu/SETTINGS/Functional Settings/ Protections/Locked Rotor If the motor current exceeds the set level and the set time when the motor is running at full voltage, this protection is activated. The protection starts monitoring when full voltage is applied to the motor.
Chapter 10 Functions 10:24 Locked rotor protection time Path in menu: Menu/SETTINGS/Functional Settings/ Protections/Locked Rotor/Lock R Time This parameter makes it possible to set the delay time from detection until activation of the protection. It is active only if Locked rotor protection is selected. Parameter Default value Setting range text Description Lock R Time Trip time for locked rotor protection 1.0 s 0.2...10.
Chapter 10 Functions 10:26 Underload protection Path in menu: Menu/SETTINGS/Functional Settings/ Protections/Underload If the motor current falls below the set level and the set time when the motor is running at full voltage, the protection is activated. The protection starts monitoring when full voltage is applied to the motor. This protection could be used to avoid for example a pump running dry, detect a broken belt or similar.
Chapter 10 Functions 10:28 Underload protection time Path in menu: Menu/SETTINGS/Functional Settings/ Protections/Underload/Underl Time This parameter makes it possible to set the delay time from detection until the protection is activated. It is active only if underload protection is selected. Parameter Default value Setting range text Description Underl Time Trip time for Underload protection 10 s 1...
Chapter 10 Functions 10:30 Phase imbalance protection Path in menu: Menu/SETTINGS/Functional Settings/ Protections/Phase Imb If the current in one phase differs from another phase with more than the set level the protection is activated. The protection starts monitoring 30 seconds after full voltage, and trips after 10 seconds of imbalance.
Chapter 10 Functions 10:32 Phase imbalance protection, type of operation Path in menu: Menu/SETTINGS/Functional Settings/ Protections/Phase Imb/Phase Imb Op This parameter makes it possible to select between three different actions of the softstarter when the protection is activated. It is active only if the phase imbalance protection is selected. Stop–M The motor stops and a manual reset is required before restart. Stop–A The motor stops and an automatic reset is performed when the fault disappears.
Chapter 10 Functions 10:34 High current protection, type of operation Path in menu: Menu/SETTINGS/Functional Settings/ Protections/High I/High I Op This parameter makes it possible to select between three different actions of the softstarter when the protection is activated. It is active only if the high current protection is selected. Stop–M The motor stops and a manual reset is required before restart. Stop–A The motor stops and an automatic reset is performed when the fault disappears.
Chapter 10 Functions 10:36 Phase reversal protection, type of operation Path in menu: Menu/SETTINGS/Functional Settings/ Protections/Phase Rev/Ph Rev Op This parameter makes it possible to select between three different actions of the softstarter when the protection is activated. It is active only if the phase reversal protection is selected. Stop–M The motor stops and a manual reset is required before restart. Stop–A The motor stops and an automatic reset is performed when the fault disappears.
Chapter 10 Functions 10:38 PTC protection, type of operation Path in menu: Menu/SETTINGS/Functional Settings/ Protections/PTC/PTC Op This parameter makes it possible to select between three different actions of the softstarter when the protection is activated. It is active only if the PTC protection is selected. Stop–M The motor stops and a manual reset is required before restart. Stop–A The motor stops and an automatic reset is performed when the fault disappears.
Chapter 10 Functions 10:40 High current warning Path in menu: Menu/SETTINGS/Functional Settings/ Warnings/Warn I=High If the function is selected, a warning signal will be given provided that the current during full voltage is higher than the set value. The measurement starts 30 seconds after full voltage is reached.
Chapter 10 Functions 10:43 Low current warning level Path in menu: Menu/SETTINGS/Functional Settings/ Warnings/Warn I=Low/Wa I=L Lev This parameter makes it possible to set the indication level of the low current warning function. Parameter text Default value Setting range Wa I = L Lev 0.8 x Ie 0.4...1.
Chapter 10 Functions 10:46 Thyristor (SCR) overload warning Path in menu: Menu/SETTINGS/Functional Settings/ Warnings/Warn SCR OL If this function is selected, a warning signal will be given that the thyristor overload protection will be activated, if the current does not decrease. The warning level is 90%.
Chapter 10 Functions Parameter Default value Setting range text Description FB Fault Op Type of operation for fieldbus fault Stop–M Stop–M, Stop–A 10:49 Frequency fault, type of operation Path in menu: Menu/SETTINGS/Functional Settings/ Faults/Freq F Op This parameter makes it possible to select between two different actions of the softstarter if the frequency is out of range (frequency fault). Stop–M The motor stops and a manual reset is required before restart.
Chapter 10 Functions 10:51 Thyristor short circuit fault, type of operation Path in menu: Menu/SETTINGS/Functional Settings/ Faults/SCR SC Op If one or several thyristors are shorted, this parameter makes it possible to select between two different actions of the softstarter. Stop–M The motor stops and a manual reset is required before restart. Stop–A The motor stops and an automatic reset is performed when the fault disappears.
Chapter 10 Functions 10:53 By-pass doesn't close fault, type of operation Path in menu: Menu/SETTINGS/Functional Settings/Faults/BP Open Op This parameter makes it possible to select between two different actions of the softstarter if the by-pass contactor does not close in a proper way. Stop-M The motor stops and a manual reset is required before restart. Stop-A The motor stops and an automatic reset is performed when the fault disappears.
Chapter 10 Functions • Switching from one type of control to another (fieldbus control / hardwire control) • Re-programming of the programmable inputs • Reset all Settings (programmable input set to Enable) Warning! Terminal 4, 5, 6, 7, 8, 9, 10, and 11 should be connected using 24V DC only. Other voltages may damage the softstarter and the warranty may no longer be valid.
Chapter 10 Functions 10:55 Programmable output relays, K4, K5, and K6 Path in menu: Menu/SETTINGS/Functional Settings/ Outputs/Relay K4 / K5 / K6 Switch over relays The softstarter has three programmable output relays that can be used for different purposes depending on the selected function, independently of each other. Relay K4 has default setting Run, relay K5 has default setting Top of Ramp and relay K6 has default setting Event. Run signal is given during start ramp, running, and stop ramp if used.
Chapter 10 Functions Description 2 fault groups can be selected. If any of the faults in a fault group occurs, a fault signal is given.
Chapter 10 Functions 10:56 Programmable software output V7 Path in menu: Menu/SETTINGS/Functional Settings/ Outputs/SW Outp V7 If the softstarter is used with fieldbus communication, a fourth output is available. This is a software output only and the signal can be taken only through the fieldbus interface. (See 50 “Programmable output relays, K4, K5, and K6” for further explanations. Parameter Default value Setting range text Description SW Outp V7 Function of programmable software output V7.
Chapter 10 Functions 10:58 Analog output, reference Path in menu: Menu/SETTINGS/Functional Settings/ Analog Output /Anl Ref With this parameter it is possible to set the unit and the range of the signal to output. This selected range will be the physical output from the softstarter. This range should be selected to suit the analog meter or the PLC that uses this signal as its input.
Chapter 10 Functions Parameter Default value Setting range text Description Anl Type The type of value to output from the analog output I Amp I Amp, U Volt, P kW, P hp, Q kVAr, S kVA, TmpMot, TmpSCR, cosPhi 10:60 Analog output, range max Path in menu: Menu/SETTINGS/Functional Settings/ Analog Output/ I/U/P/Q/S Range Max With this parameter it is possible to set the value that will be represented as the maximum value by an analog meter or by a PLC.
Chapter 10 Functions Parameter Default value Setting range text Description I Range Max PST(B) size dependent 10...20000 A Upper limit for the current for the analog output U Range Max 600 V 10...1000 V Upper limit for the voltage for the analog output kW Range Max PST(B) size dependent 1...3000 kW Upper limit for the active power for the analog output hp Range Max PST(B) size dependent 1...
Chapter 10 Functions • Switching from one type of control to another (fieldbus control / hardwire control) • Re-programming of the programmable inputs • Reset all Settings (programmable input set to Enable) Parameter Default value Setting range text Description Fieldb Ctrl No Control of the softstarter with fieldbus.
Chapter 10 Functions 10:63 Fieldbus address Path in menu: Menu/SETTINGS/Functional Settings/ Fieldbus/Fieldb Addr With this parameter it is possible to set a fieldbus address for the softstarter. Select a suitable, not occupied number as the address. Parameter Default value Setting range text Description Fieldb Addr 0 Fieldbus address 0...1000 10:64 Fieldbus auto disable Path in menu: Menu/SETTINGS/Functional Settings/ Fieldbus/FB Auto Dis This parameter enables the function fieldbus auto disable.
Chapter 10 Functions 10:65 Sequence start, number of sequences Path in menu: Menu/SETTINGS/Functional Settings/ Seq Start/No of Seq The softstarter can start motors with up to three different parameter sets (1st parameter set, 2nd parameter set and 3rd parameter set). This function can be used for starting motors in a sequence (one by one) and also for starting two or three speed motors where different starting parameters are required for each speed.
Chapter 10 Functions 10:67 Initial voltage, first sequence Path in menu: Menu/SETTINGS/Functional Settings/ Seq Start/1st Seq. Param./Init Volt1 This parameter makes it possible to set the initial voltage for the first parameter set Parameter Default value Setting range text Description Init Volt1 First sequence, initial voltage for start ramp 30% 30...70% 10:68 Current limit, first sequence Path in menu: Menu/SETTINGS/Functional Settings/ Seq Start/1st Seq. Param.
Chapter 10 Functions 10:70 Start ramp, second sequence Path in menu: Menu/SETTINGS/Functional Settings/ Seq Start/2nd Seq. Param./Start Ramp2 This parameter makes it possible to set the start ramp time for the second parameter set. Parameter Default value text Setting range Description Start Ramp2 1...30s, 1...120s Second sequence, time for start ramp 10 s 10:71 Initial voltage, second sequence Path in menu: Menu/SETTINGS/Functional Settings/ Seq Start/2nd Seq. Param.
Chapter 10 Functions 10:73 Setting current, second sequence Path in menu: Menu/SETTINGS/Functional Settings/ Seq Start/2nd Seq. Param./2nd Set Ie This parameter makes it possible to set the rated motor current for the second parameter set. Parameter Default value Setting range text 2nd Set Ie Ir Description 9...1207A divided Second into 19 overlap- sequence, motor ping ranges rated current 10:74 Start ramp, third sequence Path in menu: Menu/SETTINGS/Functional Settings/ Seq Start/3rd Seq. Param.
Chapter 10 Functions 10:76 Current limit, third sequence Path in menu: Menu/SETTINGS/Functional Settings/ Seq Start/3rd Seq. Param./Curr Lim3 This parameter makes it possible to set the current limit level for the third parameter set. Parameter Default value text Setting range Description Curr Lim3 2.0...7.0 x Ie Third sequence, current limit 4 x Ie 10:77 Setting current, third sequence Path in menu: Menu/SETTINGS/Functional Settings/ Seq. Start/3rd Seq. Param.
Chapter 10 Functions 10:78 Language Path in menu: Menu/SETTINGS/Presentation Set./Language The text on the LCD display can be presented in 13 different languages.
Chapter 10 Functions 10:80 Password Path in menu: Top level Press Upper navigation key once. This parameter makes it possible to set a password when locking the keypad from controlling and changing the settings. All menus are available when the keypad is locked but no changes or actions can be done. Parameter text Default value Setting range Description Change Password No Password for display No, 1...255 10:81 Date type Path in menu: Menu/SETTINGS/Presentation Set.
Chapter 10 Functions 10:82 Year Path in menu: Menu/SETTINGS/Presentation Set./Date Year This parameter makes it possible to set the current year for the real time clock. Parameter Default value text Setting range Description Date Year 1901...2038 Year Individual 10:83 Month Path in menu: Menu/SETTINGS/Presentation Set./Date Month This parameter makes it possible to set the current month for the real time clock.
Chapter 10 Functions 10:85 Hour Path in menu: Menu/SETTINGS/Presentation Set./Time Hour This parameter makes it possible to set the current hour for the real time clock. Parameter Default value Setting range text Description Time Hour Hour Individual 0...23 10:86 Minutes Path in menu: Menu/SETTINGS/Presentation Set./Time Min This parameter makes it possible to set the current minutes for the real time clock.
Chapter 10 Functions 10:87 Dual current limit time U Path in menu: Menu/SETTINGS/All Settings/C Lim Y Time 100% With this softstarter it is possible to use two different current limits: one which is active initially and a second one which is controlled by a timer and goes active when the timer runs out. This variable makes it possible to set the timer and thereby decide after how long time the current limit should switch from the normal current limit to the second current limit.
Trouble shooting Chapter 11 Trouble shooting General ........................................................................................................... 179 Overview of indications ................................................................................... 179 General problems and faults ........................................................................... 180 Start up faults ..................................................................................................
Trouble shooting 178 1SFC132003M0201
Chapter 11 Trouble shooting Chapter 11 Trouble shooting 11:1 General This chapter is a guide that can be used in case problems should arise with the softstarter or the application. The softstarter normally indicates a fault with LED Fault, and the LCD displays what type of fault it is. When a protection is activated it will be indicated with LED Protection and the LCD displays what type of protection is active. Faults not displayed in the softstarter can also be found in this chapter.
Chapter 11 Trouble shooting 11:3 General problems and faults Status Possible cause Solution Motor humming / starts without given start signal. Shorted thyristor. • Check and replace. By-pass contactor stuck in closed position. • Check and correct the reason. Bad motor sound during start and operation. Inside Delta connection wrong. • Check and correct the wiring. Bad motor sound during stop. Wrong ramp time for stop.
Chapter 11 Trouble shooting 11:4 Start up faults Status Power on Fault Possible cause Solution LCD Auto shut off the keypad. • Touch any key on the keypad. Protection Supply voltage is not connected. • Connect the Supply voltage according to the circuit diagram. Power on Fault Protection 11:5 Fault indication Status Possible cause Solution Phase loss fault The main contactor or circuit breaker is open • Check and close contactor / breaker or any external switching device. Fuse blown.
Chapter 11 Trouble shooting Status Possible cause Solution Frequency fault The frequency is out of range. (47.5 - 52.5Hz or 57 - 63Hz) • Check and correct the frequency. The main voltage is not correct on the line side. • Check and correct voltage on the line side.
Chapter 11 Trouble shooting Status Possible cause Solution Fieldbus fault The fieldbus communication is not working. • Check that the fieldbusplug is connected correctly. Power on Fault • Check that correct type of fieldbusplug is used. Protection Fault FB Timeout Reset Back By-pass doesn’t open fault Power on Fault • Check that the parameter Fieldbus Type is set according to the present fieldbus type. The by-pass contactor is not opening properly.
Chapter 11 Trouble shooting Status Possible cause Solution Internal faults An internal communication fault of the softstarter has occurred. • Disconnect and reconnect the supply voltage (Us) and make a restart. Power on Fault Fault Intern 1 Reset Power on Fault Fault Intern 2 Reset Power on Fault Fault Intern 3 Reset Power on Fault Fault Intern 4 Reset Power on Fault Fault Intern 5 Reset 184 Protection • If same fault remains, contact your ABB sales office.
Chapter 11 Trouble shooting 11:6 Protection indication Status Possible cause Overload protection The motor has been exposed to In Line an overload condition because At start the current over a certain time is • Check and correct the reason for the too high. overload. Check that current limit level is (The load on the motor shaft is not set too low. too high) Power on Fault Protection Prot Motor OL Reset Back Solution • Check that the ramp time for start is not too long.
Chapter 11 Trouble shooting Status Possible cause Solution Underload protection The motor current is below set level and time. • Check and correct the reason for the underload. Power on Fault • Check that the settings are according to the operation conditions. Protection Prot Underload Reset Back Locked rotor protection Power on Fault Protection The motor is running stiff by • Check the bearings of the motor and some reason. load.
Chapter 11 Trouble shooting Status Possible cause PTC protection An over-temperature is detected • Check that the PTC circuit is closed and by the PTC thermistors in the that the inputs are connected. motor. • Check and correct the reason for the overheating. Power on Fault Prot PTC Reset Protection Back Thyristor overload protection The softstarter is too small. Too many starts / hour. The ramp time for start is too Power on Fault Protection long.
Chapter 11 Trouble shooting 188 1SFC132003M0201
Diagrams Chapter 12 Diagrams Circuit diagram PST30..PST300 ..................................................................... 191 Circuit diagram PSTB370...PSTB1050 ...........................................................
Diagrams 190 1SFC132003M0201
Chapter 12 Diagrams Chapter 12 Diagrams 12:1 Circuit diagram PST30..PST300 High Voltage Board Figure 1: Circuit diagram PST30...300 (IEC version) Terminal 3 is a function earth, it is not a protection earth. It shall be connected to the mounting plate.
Chapter 12 Diagrams 12:2 Circuit diagram PSTB370...PSTB1050 Figure 3: Circuit diagram PSTB370...PSTB1050 (IEC version) Terminal 3 is a function earth, it is not a protection earth. It shall be connected to the mounting plate.
Index Chapter 13 Index Numerics 1st Seq. Param. 112, 167, 168 1st Set Ie 111, 168 2nd Seq .Param. 113 2nd Seq. Param. 169, 170 2nd Set Ie 111, 170 3rd Seq .Param. 113 3rd Seq. Param.
Index Extended start range 22, 139 Extended stop range 22, 139 External By-Pass 18, 92, 151 Connection 45 Contactor 88, 90 External By-Pass contactor 45 External control voltage 49 External keypad 21 F Fans 21 Fault 64 Fault Supervision 23 Faults 102, 180 Faults indication 181 FB Fault Op 102, 154 Fieldb Addr 110, 166 Fieldb Ctrl 110, 164 Fieldb Type 110, 165 Fieldbus 21, 110, 121 Address 166 Communication 23 Connection 56 Control 110, 164 Fault 183 Type 110, 165 Fieldbus communication 23 Fieldbus fault Ty
Index Menu tree 68 Menus, description 85 Minimum distance to wall/front 38 Minimum enclosure sizes 39 Minutes 115, 175 Mixer 87 Modbus 121 Month 174 Motor overload protection 22, 95, 140 OL Class 88, 140 OL Op 95, 142 Overload class 18, 95 Run class 96 Start class 96 Type of operation 95, 142 Motor overload warning 22, 153 Motor side 43 Motor sound 180 Motor temperature 85 Motor underload protection 22, 145 Mounting 37 N Navigation keys 64 No of Seq 111, 167 No.
In d e x Function of second programmable input 112 Number of sequences 111, 167 Second sequence setting current 111 Third sequence setting current 112 Service settings 69, 116 Setting current 88, 131 First sequence 112, 168 Second sequence 113, 170 Third sequence 113, 171 Setting Ie 18, 65, 88, 90, 92, 131 Settings 77 Settings menu 69 Shorted SCR 181 Softstarter types 28 Software output V7 107 Specifications 26 Standard connection 17 Start 18 Start and Stop Connection 48 Start Mode 89 Start mode 92, 94, 13
Customer feedback report Product: ABB would appreciate your comments on this product. Please grade the following questions by selecting one alternative per category. Your answer will enables us to improve our products.
Suggestions for improvements: ___________________________________________________________________ ___________________________________________________________________ ___________________________________________________________________ ___________________________________________________________________ ___________________________________________________________________ ___________________________________________________________________ ___________________________________________________________________ _____
ABB Automation Products AB, Cewe-Control, SE-721 61 Västerås, Sweden, Telephone +46 21 32 07 00, Telefax +46 21 12 60 01 Manual 1SFC132003M0201 June 2007 ABB Automation Technologies AB, Cewe-Control