User`s manual

196 Parameter listing and descriptions
ACH550-01 User's Manual
14 = AT SET POINT – Energise the relay when the output frequency is
equal to the reference frequency.
15 =
FAULT(RST) – Energise the relay when the drive is in a fault
condition and will reset after the programmed auto-reset delay.
• See parameter 3103
DELAY TIME.
16 =
FLT/ALARM – Energise the relay when a fault or alarm occurs.
17 =
EXT CTRL – Energise the relay when external control is selected.
18 =
REF 2 SEL – Energise the relay when EXT2 is selected.
19 =
CONST FREQ – Energise the relay when a constant speed is
selected.
20 =
REF LOSS – Energise the relay when the reference or active control
location is lost.
21 =
OVERCURRENT – Energise the relay when an overcurrent alarm or
fault occurs.
22 =
OVERVOLTAGE – Energise the relay when an overvoltage alarm or
fault occurs.
23 =
DRIVE TEMP – Energise the relay when a drive or control board
overtemperature alarm or fault occurs.
24 =
UNDERVOLTAGE – Energise the relay when an undervoltage alarm
or fault occurs.
25 =
AI1 LOSS – Energise the relay when AI1 signal is lost.
26 =
AI2 LOSS – Energise the relay when AI2 signal is lost.
27 =
MOTOR TEMP – Energise the relay when a motor overtemperature
alarm or fault occurs.
28 =
STALL – Energise the relay when a stall alarm or fault exists.
30 =
PID SLEEP – Energise the relay when the PID sleep function is
active.
31 = PFA – Use the relay to start/stop motor in PFA control (See Group
81: PFA CONTROL).
• Use this option only when PFA control is used.
• Selection activated / deactivated when the drive is not running.
32 =
AUTOCHANGE – Energise the relay when PFA autochange operation
is performed.
• Use this option only when PFA control is used.
33 =
FLUX READY – Energise the relay when the motor is magnetised
and able to supply nominal torque (the motor has reached nominal
magnetising).
34 =
USER MACRO 2 – Energise the relay when User Parameter Set 2 is
active.
Code Description Range