User`s manual

200 Parameter listing and descriptions
ACH550-01 User's Manual
Group 15: ANALOGUE OUTPUTS
This group defines the drive’s analogue (current signal) outputs.
The drive’s analogue outputs can be:
any parameter of Group 01: OPERATING DATA
limited to programmable minimum and maximum values of
output current
scaled (and/or inverted) by defining the minimum and
maximum values of the source parameter (or content).
Defining a maximum value (parameter 1503 or 1509) that is
less than the content minimum value (parameter 1502 or
1508) results in an inverted output.
•filtered.
Code Description Range
1501 AO1 CONTENT SEL 99…178
Defines the content for analogue output AO1.
99 =
EXCITE PTC – Provides a current source for sensor type PTC.
Output = 1.6 mA. See Group 35: MOTOR TEMP MEAS.
100 =
EXCITE PT100 – Provides a current source for sensor type PT100.
Output = 9.1 mA. See Group 35: MOTOR TEMP MEAS.
101…178 – Output corresponds to a parameter in Group 01:
OPERATING DATA.
Parameter defined by value (e.g. value 102 = parameter 0102)