US Catalog | December 2016 Miniature Circuit Breakers
Miniature circuit breakers Table of contents S(U)200 series miniature circuit breakers UL 489 series Description and features SU200M-C SU200M-K SU200M-Z SU200MR-K S200UDC-K S200UDC-Z Accessories Technical specifications Approximate dimensions 2 3 4 5 6 7 8 9 14 18 S200 series miniature circuit breakers UL 1077 series Description and features S200-B S200-C S200-D S200-K S200-Z S200P-B S200P-C S200P-D S200P-K S200P-Z S200MR-K S200MUC-C S200MUC-K S200MUC-Z Accessories Technical specifications S200MUC uses A
S(U)200 series—SU200M, SU200MR, and S200UDC UL 489 series Description The SU200M, SU200MR, and S200UDC miniature circuit breakers offer a compact solution for protection requirements. The SU200 series devices are current-limiting according to UL 489 and DIN rail mounted. SU200M, SU200MR, and S200UDC MCBs come in up to 3 trip curves to provide maximum circuit protection. For the worldwide market, the breakers carry UL, CSA, IEC, CE and many other agency approvals and certifications.
SU200M-C Branch circuit protection—UL 489, CSA 22.2 No. 5 Rated current Rated current In Number of poles A 0.5 1 1.6 2 3 4 5 6 7 8 10 1 13 15 16 20 25 30 32 35 40 50 60 63 0.5 1 1.6 2 3 4 5 6 7 8 10 2 13 15 16 20 25 30 32 35 40 50 60 63 In Catalog number SU201M-C0.5 SU201M-C1 SU201M-C1.
SU200M-K Branch circuit protection—UL 489, CSA 22.2 No. 5 Rated current Rated current In Number of poles A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 7 8 1 10 13 15 16 20 25 30 32 35 40 50 60 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 7 8 2 10 13 15 16 20 25 30 32 35 40 50 60 63 4 Miniature Circuit Breakers | US Catalog In Catalog number SU201M-K0.2 SU201M-K0.3 SU201M-K0.5 SU201M-K0.75 SU201M-K1 SU201M-K1.
SU200M-Z Branch circuit protection—UL 489, CSA 22.2 No. 5 Rated current Rated current In Number of poles A 0.5 1 1.6 2 3 4 5 6 7 8 10 1 13 15 16 20 25 30 32 35 40 50 60 63 0.5 1 1.6 2 3 4 5 6 7 8 10 2 13 15 16 20 25 30 32 35 40 50 60 63 In Catalog number SU201M-Z0.5 SU201M-Z1 SU201M-Z1.
SU200MR-K with ring tongue terminals Branch circuit protection—UL 489, CSA 22.2 No. 5 Rated current Rated current In Number of poles A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 1 13 15 16 20 25 30 32 35 40 50 60 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 2 13 15 16 20 25 30 32 35 40 50 60 63 6 Miniature Circuit Breakers | US Catalog In Catalog number SU201MR-K0.2 SU201MR-K0.3 SU201MR-K0.5 SU201MR-K0.75 SU201MR-K1 SU201MR-K1.
S200UDC-K Branch circuit protection—UL 489, CSA 22.2 No. 5 Rated current In Number of poles 1 2 A 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 Catalog number S201UDC-K1 S201UDC-K1.6 S201UDC-K2 S201UDC-K3 S201UDC-K4 S201UDC-K5 S201UDC-K6 S201UDC-K8 S201UDC-K10 S201UDC-K13 S201UDC-K15 S201UDC-K16 S201UDC-K20 S201UDC-K25 S201UDC-K30 S201UDC-K32 S201UDC-K40 S201UDC-K50 S201UDC-K60 S201UDC-K63 S202UDC-K1 S202UDC-K1.
S200UDC-Z Branch circuit protection—UL 489, CSA 22.2 No. 5 Rated current In Number of poles 1 2 A 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 Note: Standard UL 489 (only DC; please note polarity of device). 8 Miniature Circuit Breakers | US Catalog Catalog number S201UDC-Z1 S201UDC-Z1.
Accessories SU200M, SU200MR, and S200UDC—UL 489, CSA 22.2 No. 5 Auxiliary contacts The auxiliary contacts will signal whether the breaker is in the ON or OFF position. Description For field mounting: right side Catalog number S2C-H6RU S2C-H6RU Bell alarm The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically, the contacts would be connected to an alarm or bell to signal the operator that an overcurrent trip has occurred.
Accessories SU200M, SU200MR, and S200UDC—UL 489, CSA 22.2 No. 5 2CSC400064F0201 Rotary operating mechanism For the actuation of 2-, 3- or 4pole miniature circuit-breakers in closed distribution boards for driveaxles of 5 or 6 mm2 (square) Catalog number S2C-DH S2C-DH Handles Handle IP 65, 65 x 65 mm, padlockable with max.
Accessories SU200M, SU200MR, and S200UDC—UL 489, CSA 22.2 No. 5 Connection drawings Bell alarm S2C-S6RU In ON and OFF position after hand operation Auxiliary contact S2C-H6RU Auxiliary contact in ON position Shunt trip S2C-A...U Shunt trip in OFF position In OFF position after tripping Auxiliary contact in OFF position Mounting Addition of a S2C-H6RU auxiliary contact Addition of a S2C-S6RU bell alarm contact Addition of a S2C-A...U shunt trip S200U-UP S2C-A....
Accessories SU200MR—UL 489, CSA 22.2 No.
Accessories SU200M, SU200MR, and S200UDC—UL 489, CSA 22.2 No. 5 Busbars for SU200M Busbars cannot be cut. 600 V AC/DC Amp rating* 80/115 PS2/6/16 BP 80/115 80/115 Number of poles Phases Busbar length (mm) Catalog number 6 1 103.2 PS 1/6/16BP 12 1 208.8 PS 1/12/16BP 18 6 1 2 314.4 103.2 PS 1/18/16BP PS 2/6/16BP 12 2 208.8 PS 2/12/16BP 18 6 2 3 314.4 103.2 PS 2/18/16BP PS 3/6/16BP 12 3 208.8 PS 3/12/16BP 18 3 314.4 PS 3/18/16BP *End/centerfed Busbar tooth covers for BS...
Accessories SU200M, SU200MR, and S200UDC—UL 489, CSA 22.2 No. 5 Busbars for SU200MR, can be cut to length Busbars PS…BP-CR for use with end caps PS-END 3 BP-C Number of Phase sequence phases 1 PS...BP-CR 2 3 1) L1-L1-L1… L1-Aux (free)-L1-Aux (free)…1) L1-L2-L1-L2… L1-L2-Aux (free)-L1-L2-Aux (free)…1) L1-L2-L3-L1-L2-L3… L1-L2-L3-Aux (free)-L1-L2-L3-Aux (free)…1) L1-Aux (free)-L2-Aux (free)-L3-Aux (free)…1) Number of pins Cross section Catalog number pcs.
Technical specifications SU200M, SU200MR, and S200UDC—UL 489, CSA 22.2 No. 5 Technical specifications Specifications SU200M UL 489, C 22.2 No. 5, IEC 60947-2 SU200MR UL 489, C 22.2 No.
Technical specifications SU200M, SU200MR, and S200UDC—UL 489, CSA 22.2 No. 5 Internal resistance and power loss per pole Internal resistance per pole in mV, power loss per pole in W. SU200M C, K characteristics Rated current In A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 Z characteristics Internal resistance per pole Ri mΩ 42500 18889 5600 2489 1400 703 450 178 113 50 56 23 21 14 11 9.8 6.3 5.1 3.9 3.6 3.3 2.8 1.8 1.4 1.4 Power loss Pv W 1.7 1.7 1.4 1.4 1.4 1.8 1.8 1.6 1.
Technical specifications SU200M, SU200MR, and S200UDC—UL 489, CSA 22.2 No. 5 Temperature derating SU200M and SU200MR Standard Rated current In A UL 489 1) 0.2 1) 0.3 1) 0.5 0.75 1) 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 Maximum operating current at ambient temperature T A - 40 °C 0.27 0.40 0.67 1.00 1.34 1.74 2.67 4.01 5.35 6.69 8.02 10.70 13.37 17.38 20.06 21.40 26.75 33.43 40.12 42.79 46.81 53.49 66.87 80.24 84.25 - 30 °C 0.26 0.39 0.64 0.97 1.29 1.68 2.58 3.87 5.16 6.45 7.74 10.
Technical specifications Busbars PS...BP-C/CR and accessories Electrical data Busbars PS…BP-C/CR Standards V Hz kV UL508 EN 60947-1 / IEC 60947-1:2004 600 V AC/DC 50 Hz (IEC) / 60 Hz (UL) ≥ 10 kV A A kA 100 A 200 A 10 kA 3 cycles @ 600 V / 140 kA Fuse Class J 200 A Rated voltage Ue Rated frequency Rated impuls withstand voltage Uimp.
Approximate dimensions SU200M, SU200MR, and S200UDC—UL 489, CSA 22.2 No. 5 SU200M S200UDC SU200MR S2C-H6RU, S2C-S6RU S2C-A..
S200 series Supplementary protective devices—UL 1077 series Description The S200 UL 1077 family of supplementary protectors offers a compact solution for protection requirements. The S200 devices are DIN rail mounted. The S200 family is available with application-specific trip characteristics to provide maximum circuit protection. The supplementary protectors offer thermal magnetic trip protection according to B, C, D, K and Z characteristics.
S200-B Supplemental protectors—UL 1077, CSA 22.2 No.
S200-C Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 1 + NA 2 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 In Catalog number Number of poles S201-C0.5 S201-C1 S201-C1.6 S201-C2 S201-C3 S201-C4 S201-C6 S201-C8 S201-C10 S201-C13 S201-C16 S201-C20 S201-C25 S201-C32 S201-C40 S201-C50 S201-C63 S201-C0.5NA S201-C1NA S201-C1.
S200-D Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 1 + NA 2 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 In Catalog number Number of poles S201-D0.5 S201-D1 S201-D1.6 S201-D2 S201-D3 S201-D4 S201-D6 S201-D8 S201-D10 S201-D13 S201-D16 S201-D20 S201-D25 S201-D32 S201-D40 S201-D50 S201-D63 S201-D0.5NA S201-D1NA S201-D1.
S200-K Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 1 + NA 2 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 In Catalog number Number of poles A Catalog number S201-K0.5 S201-K1 S201-K1.6 S201-K2 S201-K3 S201-K4 S201-K6 S201-K8 S201-K10 S201-K13 S201-K16 S201-K20 S201-K25 S201-K32 S201-K40 S201-K50 S201-K63 S201-K0.5NA S201-K1NA S201-K1.
S200-Z Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 2 In Catalog number Number of poles A Catalog number 0.5 S201-Z0.5 0.5 S203-Z0.5 1 S201-Z1 1 S203-Z1 1.6 S201-Z1.6 1.6 S203-Z1.
S200P-B Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 2 In Catalog number Number of poles A Catalog number 0.5 S201P-B0.5 0.5 S203P-B0.5 1 S201P-B1 1 S203P-B1 1.6 S201P-B1.6 1.6 S203P-B1.
S200P-C Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 2 In Catalog number Number of poles A Catalog number 0.5 S201P-C0.5 0.5 S203P-C0.5 1 S201P-C1 1 S203P-C1 1.6 S201P-C1.6 1.6 S203P-C1.
S200P-D Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 2 In Catalog number Number of poles A Catalog number 0.5 S201P-D0.5 0.5 S203P-D0.5 1 S201P-D1 1 S203P-D1 1.6 S201P-D1.6 1.6 S203P-D1.
S200P-K Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 2 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 In Catalog number Number of poles A Catalog number S201P-K0.2 S201P-K0.3 S201P-K0.4 S201P-K0.75 S201P-K1 S201P-K1.6 S201P-K2 S201P-K3 S201P-K4 S201P-K6 S201P-K8 S201P-K10 S201P-K13 S201P-K16 S201P-K20 S201P-K25 S201P-K32 S201P-K40 S201P-K50 S201P-K63 S202P-K0.2 S202P-K0.
S200P-Z Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 2 In Catalog number Number of poles A Catalog number 0.5 S201P-Z0.5 0.5 S203P-Z0.5 1 S201P-Z1 1 S203P-Z1 1.6 S201P-Z1.6 1.6 S203P-Z1.
S200MR-K with ring tongue terminals Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles 1 2 10000 6000 4000 I1 I1 = 1.03 x In I2 600 400 R = 40°C 1 = Tripping curve from cold state 2000 1000 I2 = 1.25 x In 1 1 A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 In Catalog number Number of poles S201MR-K0.2 S201MR-K0.3 S201MR-K0.5 S201MR-K0.
S200MUC-C Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles 1 2 32 Miniature Circuit Breakers | US Catalog In A 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 Catalog number S201MUC-C0.5 S201MUC-C1 S201MUC-C1.6 S201MUC-C2 S201MUC-C3 S201MUC-C4 S201MUC-C6 S201MUC-C8 S201MUC-C10 S201MUC-C13 S201MUC-C16 S201MUC-C20 S201MUC-C25 S201MUC-C32 S201MUC-C40 S201MUC-C50 S201MUC-C63 S202MUC-C0.5 S202MUC-C1 S202MUC-C1.
S200MUC-K Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles 1 2 A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 In Catalog number S201MUC-K0.2 S201MUC-K0.3 S201MUC-K0.5 S201MUC-KO.75 S201MUC-K1 S201MUC-K1.
S200MUC-Z Supplemental protectors—UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles 1 2 34 Miniature Circuit Breakers | US Catalog A 0.5 1 1.6 2 3 4 5 6 8 10 15 16 20 25 30 32 35 40 50 60 63 0.5 1 1.6 2 3 4 5 6 8 10 15 16 20 25 30 32 35 40 50 60 63 In Catalog number S201MUC-Z0.5 S201MUC-Z1 S201MUC-Z1.
Accessories S200, S200P, S200MR, and S200MUC—UL 1077, CSA 22.2 No. 235 Auxiliary contacts The auxiliary contacts will signal whether the breaker is in the ON or OFF position. Description For field mounting: right side Auxiliary contact 1CO Auxiliary contact 1NO/1NC S2C-H6... Catalog number S2C-H6R S2C-H6-11R Auxiliary contact 2NO S2C-H6-20R Auxiliary contact 2NC S2C-H6-02R Bell alarm— signal contact The bell alarm includes a set of contacts that will only signal when the breaker has tripped.
Accessories S200, S200P, S200MUC, and S200MR—UL 1077, CSA 22.2 No. 235 Accessory overview H Auxiliary contact S2C-H6R H-R Auxiliary contact S2C-H6-...R S/H Signal/auxiliary contact S2C-S/H6R S/H (H) Signal/auxiliary contact S2C-S/H6R used as auxiliary contact SU200MR Instructions for use 36 Miniature Circuit Breakers | US Catalog ST Shunt trip S2C-A...
Accessories S200, S200P, and S200MUC UL 1077, CSA 22.2 No. 235 (suitable for cutting) Busbars (suitable for cutting) UL 1077 suitable for MCBs S200 and S200P 1-phase busbars, pin distance 17.6 mm, end caps PS-END 0 Number of pins Phases mm2 Catalog number 60 1 10 PS 1/60 SP 60 1 16 PS 1/60/16 SP 1-phase busbars, connection of 1-pole devices with auxiliary, PS-END 0 Number of pins Phases mm2 Catalog number 38 1 10 PS 1/38H SP 38 1 16 PS 1/38/16H SP 2-phase busbars, pin distance 17.
Accessories S200, S200P, and S200MUC UL 1077, CSA 22.2 No. 235 (suitable for cutting) Busbars (suitable for cutting) UL 1077 suitable for MCBs S200 and S200P 4-phase busbars, connection of 1+N and RCBO, end caps PS-END 1 SP Number of pins Phases mm2 Catalog number 58 4 16 PS4/58/16N SP mm2 Catalog number Shock-protection caps for PS...SP (UL 1077) Number of pins Phases 5 parts BSK SP Feeder terminals for PS...SP (UL 1077) Terminal, insulated with pin contact Conn.
Technical specifications S200, S200P, S200MR, S200MUC—UL 1077, CSA 22.2 No. 235 Technical specifications S200 S200P S200MR S200MUC Number of poles 1, 2, 3, 4 1, 2, 3, 4 1, 2, 3, 4 1, 2, 3, 4 Trip curves B, C, D, K, Z B, C, D, K, Z K C, K, Z Rated current 0.5-63 A 0.2-63 A 0.2-63 A 0.
Technical specifications S200, S200P, and S200MR—UL 1077, CSA 22.2 No. 235 Internal resistance and power loss per pole Internal resistance per pole in mV, power loss per pole in W. S200MR S200 and S200P Type S200 and S200P 1) Rated current Device series Device series Device series In A 0.5 1 1.6 2 3 4 6 8 B, C, D mΩ 5500 1440 630 460 150 110 55 15 W 1.4 1.4 1.6 1.8 1.3 1.8 2.0 1.0 K mΩ 6340 1550 695 460 165 120 52 38 W 1.6 1.6 1.8 1.9 1.5 2.0 1.9 1.5 Z mΩ 10100 2270 1100 619 202 149 104 53.
Miniature circuit breaker S200MUC Use of MCBs in direct current circuits S200MUC miniature circuit breakers can be used in the 1 pole version at 250 VDC, and in the 2-pole or 4-pole version with series connection of two poles up to 500 VDC. S200MUC differs from the standard S200 type. It is equipped with permanent magnets that assist in the forced extinguishing of the arc.
Approximate dimensions S200, S200P, S200MR, and S200MUC—UL 1077, CSA 22.2 No.
Application guide—Miniature circuit breaker Introduction The circuit breaker plays an important role in providing overcurrent protection and a disconnect means in electrical networks. Recent advancements in circuit breaker technology has increased breaker performance and protection. Breaker definition A breaker is a device designed to isolate a circuit during an overcurrent event without the use of a fusible element.
Circuit breaker construction Thermal/Magnetic trip units definition ABB Current Limiting Breakers use an electromechanical (Thermal/Magnetic) trip unit to open the breaker contacts during an overcurrent event. The thermal trip unit is temperature sensitive and the magnetic trip unit is current sensitive. Both units act independently and mechanically with the breaker’s trip mechanism to open the breaker’s contacts.
Circuit breaker construction Arc runners/arc chutes The arc runner guides the electric arc away from the open contacts into the arc chute where it is extinguished. During an overload or short circuit event, the contacts of the breaker separate, and an electrical arc is formed between the contacts through air. The arc is moved into the arc chute by “running” the arc down the interior of the breaker along the arc runner. When the arc reaches the arc chute, it is broken into small segmented arcs.
Circuit breaker current limitation Current limiting definitions All ABB miniature circuit breakers are UL tested and certified as current limiting protective devices. Current limiting circuit breakers provide a higher level of circuit protection than typical zero point external breakers.
Circuit breaker current limitation Current limiting and zero crossing breakers During the initial stages of a short circuit, a breaker’s contacts open to interrupt the circuit. After the contacts open, an arc forms in the air between the contacts on both the current limiting and zero crossing breaker contacts. What distinguishes a current limiting breaker from a zero, crossing breaker is what each breaker does after an arc is formed between the open contacts.
Selective coordination and series ratings Definition of selective coordination Coordination between the operating characteristics of two or more overcurrent protection devices, so that when an over-current within established limits occurs, the device designated to operate within those limits trips whereas the other devices does not trip.
Selective coordination and series ratings Selective coordination Selective coordination is achieved when there is a short circuit on a branch circuit breaker, the branch breaker opens and isolates the fault, and the main breaker remains closed. The rating is usually a value above the “stand alone” interrupting rating of the branch breaker and the “stand alone” rating of the main breaker. The series rating combination of two breakers is equal to the “stand alone” interrupting value of the main breaker.
Miniature circuit breaker cutaway Electromagnetic protection Upper terminal Tripping lever Thermal protection (bimetal) Operating mechanism Operator Arc chamber Fixed contact Space for identification marker Moving contact DIN rail holder Lower terminal 50 Miniature Circuit Breakers | US Catalog
S800U series High performance circuit breakers—UL 489 series Description The S800U high performance MCB offers a compact solution to circuit protection. The S800U devices are DIN rail mounted. The S800U is available with application-specific trip characteristics to provide maximum circuit protection. The breakers offer thermal-magnetic trip protection according to Z and K characteristics. Features − − Energy limiting − − Fast breaking time (2.3-2.
S800U-K, 240 VAC Branch circuit protection—UL 489 Rated current Rated current In Number of poles 1 2 10 000 1000 100 10 seconds 1 0.1 0.
S800U-Z, 240 VAC Branch circuit protection—UL 489 Rated current Rated current In Number of poles 1 2 A 10 15 20 25 30 40 50 60 70 80 90 100 10 15 20 25 30 40 50 60 70 80 90 100 In Catalog number S801U-Z10 S801U-Z15 S801U-Z20 S801U-Z25 S801U-Z30 S801U-Z40 S801U-Z50 S801U-Z60 S801U-Z70 S801U-Z80 S801U-Z90 S801U-Z100 S802U-Z10 S802U-Z15 S802U-Z20 S802U-Z25 S802U-Z30 S802U-Z40 S802U-Z50 S802U-Z60 S802U-Z70 S802U-Z80 S802U-Z90 S802U-Z100 Number of poles 3 4 A 10 15 20 25 30 40 50 60 70 80 90 100 10 15
S804U-PVS5 The S804U-PVS5 is for GFDI applications (Ground-Fault Detector Interrupter) in photovoltaic systems. In case of a ground fault, the breaker will trip and the PV generator will not be damaged. The breaker is tested acc. to UL 489B for 1000 VDC. Technical specifications Standard UL 489B Characteristic PV-S Rated current Ie [A] 5 Rated voltage U e [V] 1000 DC 4 No. of poles Short-circuit current rating acc.
S804U-PVS5 Tested and listed wirings 1-ft 1-ft 1-ft 1-ft 1-ft 1-ft Line and load migth be r + - LOAD + LOAD - LOAD 1-ft LOAD 1-ft - LOAD 1-ft + 1-ft Ampere Rating [A] 1-ft Conductor Type AWG, Wire Range 10–32 Single conductor per terminal – copper only, 60/75°C wire 14 AWG–2 AWG Cu, solid or stranded 40–63 Single conductor per terminal – copper only, 60°C wire only 1/0 AWG–8 AWG Cu, solid or stranded 1 30.5 1 30.
S804U-UCZ This breaker is specially designed for networks up to 600 VDC, i.e., a data center. It is available as 4-pole version with a short-circuit current rating of 10 kA acc. to UL 489. Technical specifications UL 489 Standard Z Characteristic Rated current Ie [A] 10–80 Rated voltage U e [V] 600 DC 4 No. of poles jumper jumper Short-circuit current rating acc. to UL 489 [kA] 10 Tightening torque [Nm] 3.5 (31 in.
S804U-UCZ Tested and listed wirings jumper jumper jumper jumper jumper jumper Line and load migth be reversed + - LOAD + + LOAD - jumper LOAD - jumper jumper LOAD LOAD jumper jumper jumper 10–32 40–63 70–80 Single conductor per terminal – Single conductor per terminal – copper only, 60 ºC wire only Single conductor per terminal – copper only, 60 ºC wire only AWG, wire range 14 AWG–2 AWG Cu, solid or stranded 1/0 AWG–8 AWG Cu, solid or stranded 1/0 AWG–8 AWG Cu, solid or stranded
S803W-SCL-SR UL Short circuit current limiter, self-resetting UL version short circuit current limiter, self-resetting, 3 pole Description Catalog number 32A Self-resetting current limiter S803W-SCL32-SR 63A Self resetting current limiter S803W-SCL63-SR 100A Self resetting current limiter S803W-SCL100-SR Technical specifications Rated voltage 600 VAC per UL508 Short circuit current rating according to UL508, CSA 22.
Approximate dimensions S803W-SCL-SR UL508 Short circuit current limiter, self-resetting Minimum cable length between S803W-SCL-SR and downstream devices (Connection has to be short-circuit proofed acc. to IEC 61439-1) MS/M0325 MS/M0132 S800 S800-SCL-SR 32 A 63 A 100/125 A min. length X 80 mm 80 mm 250 mm min.
S800W-RSU Remote switching unit UL 489 Remote switching unit Description Remote switching unit Catalog number S800W-RSU S800-RSU cable including plug Description Catalog number 3 meter cable 0.5 mm2 (AWG20) including 10-pole S800-RSU-CP Micro-Fit 3.
Accessories S800U Shunt trip For remote tripping of breaker, a shunt trip device can be added to the MCB. The device opens the breaker after control voltage is applied. Description (for field mounting, left side) Shunt operation release 24 VAC/DC Catalog number S800-SOR24 Shunt operation release 48...130 VAC/DC S800-SOR130 Shunt operation release 110...
Accessories S800U Rotary operating mechanism Allows “through the door” operation.
Technical specifications S800 S800U Characteristics K, Z [A] Rated operational current Ie 10...100 1...
Technical specifications S800U Typical internal resistances and power losses at 25 ºC ambient temperature Rated current I n Internal resistance R i Power loss P v [A] [mΩ] [W] K, Z K, Z 10 15.2 1.5 15 12.1 2.7 20 8.7 3.5 25 6.8 4.2 30 3.1 2.8 40 2.3 3.7 50 1.7 4.3 60 1.6 5.8 70 1.0 6.4 80 1.0 6.4 90 0.8 6.5 100 0.8 8.
Technical specifications S800U-UL Auxiliary contact S800-AUX Continuous thermal current I n S800-AUX AC15 400/2 A-UL AC15 240/ -UL DC13 250/0.55 A125 V/1.1A-IEC DC13 125 V/1.1A DC13 60 V/2A DC13 24 V/4A 6A Rated insulation voltage U i 690 V Number of contacts 2 Surge U test (1.2/50μs) 6 kV Degree of protection 3 Function of contact Changeover contacts Connection CU Tightening torque 1 x 2.5 mm2 2 x 1.5 mm2 1 Nm Ensured contacts during shake test 5g, 20 frequency cycle acc.
Technical specifications S800U-UL Combined auxiliary and bell alarm Continuous thermal current In AC15 400/2 A-UL AC15 240/6A-UL DC13 250/0.55 A125 V/1.1A-IEC DC13 125 V/1.1A-IEC DC13 60 V/2A DC13 24 V/4A 6A Rated insulation voltage U i 690 V Number of contacts 2 (1x AUX, 1 x AUX/ALT) Surge U test (1.2/50μs) 6 kV Degree of protection 3 Function of contact Changeover contacts Connection CU Tightening torque 1 x 2.5 mm2 2 x 1.
Approximate dimensions S800U-UL S800U 106 6 82.5 79.5 76.5 53 46 2CCC413010Z0001 95 35 45 26.5 1P 2P 3P 4P S800-SOR and S800-UVR 6 26.5 82.5 76.
Approximate dimensions S800U-UL S800-AUX 9 6 82.5 76.5 46 2CCC413017Z0001 95 35 45 T S800-AUX/ALT 9 6 82.5 76.5 46 2CCC413018Z0001 95 35 45 T RT S800-RD AND S800-RHE 81 67 76 48 76 max.
S500 series UL 1077 Description The S500 high performance MCB offers a compact solution to circuit protection. The S500 devices are UL tested current limiting and DIN rail mounted. The S500 is available with applicationspecific trip characteristics to provide maximum circuit protection. The breakers offer thermal-magnetic trip protection according to B and K characteristics. For the worldwide market, the breakers carry CSA, IEC, CE and many other agency approvals.
S500-K Supplemental protectors—UL 1077, CSA 22.2, IEC Rated current Rated current In Number of poles 1 2 10,000 5000 1000 500 100 50 seconds 10 5 1 0.5 AC 0.1 0.05 0.01 1 2 3 5 8 10 12 20 30 multiple of rated current 70 Miniature Circuit Breakers | US Catalog A 0.1-0.15 0.14-0.21 0.2-0.3 0.28-0.42 0.38-0.58 0.53-0.8 0.73-1.1 1-1.5 1.4-2.1 2-3 2.8-4.2 3.8-5.8 5.3-8 7.3-11 10-15 14-20 18-26 23-32 29-37 34-41 38-45 0.1-0.15 0.14-0.21 0.2-0.3 0.28-0.42 0.38-0.58 0.53-0.8 0.73-1.1 1-1.5 1.4-2.
S500UC-B Supplemental protectors—UL 1077, CSA 22.
S500UC-K Supplemental protectors—UL 1077, CSA 22.2, IEC Rated current Rated current In Number of poles A 0.1-0.15 0.14-0.21 0.2-0.3 0.28-0.42 0.38-0.58 0.53-0.8 0.73-1.1 1-1.5 1.4-2.1 2-3 2.8-4.2 1 3.8-5.8 5.3-8 7.3-11 10-15 14-20 18-26 23-32 29-37 34-41 38-45 0.1-0.15 0.14-0.21 0.2-0.3 0.28-0.42 0.38-0.58 0.53-0.8 0.73-1.1 1-1.5 1.4-2.1 2-3 2.8-4.2 2 3.8-5.8 5.3-8 7.3-11 10-15 14-20 18-26 23-32 29-37 34-41 38-45 10,000 5000 1000 500 100 50 seconds 10 5 1 0.5 0.1 0.05 DC 0.
Accessories S500 UL 1077 Auxiliary contacts The auxiliary contacts will signal whether the breaker is in the ON or OFF position. Description For field mounting: left side Catalog number 1 N.O/1 N.C. S500-H11 2 N.O. S500-H20 S500-H Bell alarm—signal contact The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically, the contacts would be connected to an alarm or bell to signal the operator that an overcurrent trip has occurred.
Technical specifications S500-K and S500UC-B, K Auxiliary contact S800-AUX S500-K S500UC-B, K UL 1077 1077 CSA C22.2-No. 235 C22.2-No. 235 Number of poles 1, 2, 3 1, 2, 3, 4 Tripping characteristic K B, K Rated current 0.1 to 45 A B: 6-63 A; K: 0.
Approximate dimensions S500 and accessories S500 2.95 75 1.97 50 0.98 25 3.64 92.5 1.73 44 3.15 1.77 45 80 CL 2.22 3.62 92 2.95 75 56.5 1.14 29 0.24 6 S500 S500-H11, S500-H20, S500-S11, and S500-S20 92 80 56.5 45 75 91 6 35 12.5 S500-RD3 Handle mechanism 3.15 80 1.60 40.7 S500 Front kit S500mounting handle mechanism C 4.41 2.91 112 74 2.00 51 L 6D C 1.81 46 0.24 D CUT-OUT L "L" L + 0.51 13 L L + 1.02 26 3.31 84 0.
Electronic Protection Device EPD24-TB-101 For use on the load side of 24 V DC switch mode power supplies Description The protection devices EPD24 extend the ABB product range of Modular DIN Rail Components by electronic overcurrent protection modules for selective protection of 24 V DC load circuits. This protection is achieved by a combination of active electronic current limitation in the case of a short circuit and an overload deactivation from 1.1 x IN upwards.
EPD24 Ordering information Electronic protection devices Rated current IN Weight Packing unit Catalog number A 0.5 1 2 3 4 6 8 10 12 1 piece in kg 0.065 0.065 0.065 0.065 0.065 0.065 0.065 0.065 0.065 4 4 4 4 4 4 4 4 4 EPD24-TB-101-0.5A EPD24-TB-101-1A EPD24-TB-101-2A EPD24-TB-101-3A EPD24-TB-101-4A EPD24-TB-101-6A EPD24-TB-101-8A EPD24-TB-101-10A EPD24-TB-101-12A Catalog number Weight Packing unit EPD-BB500 EPD-SB21 1 piece in kg 0.20 0.
Notes 78 Miniature Circuit Breakers | US Catalog
Notes US Catalog | Miniature Circuit Breakers 79
ABB Electrification Products 8155 T&B Boulevard Memphis, TN 38125 www.abb.us/lowvoltage Customer Service: 800-816-7809 7:00 a.m. - 5:30 p.m., CST, Monday-Friday elec_custserv@tnb.com Technical Support: 888-385-1221, Option 1 7:00 a.m. - 5:00 p.m., CST, Monday-Friday lvps.support@us.abb.com We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders and/or contracts, the agreed particulars shall prevail.