Datasheet

40 Miniature Circuit Breakers | US Catalog
S200 and S200P
Type Rated current Device series Device series Device series
I
n
B, C, D
1)
K Z
S200 and S200P
A mΩ W mΩ W mΩ W
0.5 5500 1.4 6340 1.6 10100 2.5
1 1440 1.4 1550 1.6 2270 2.3
1.6 630 1.6 695 1.8 1100 2.8
2 460 1.8 460 1.9 619 2.5
3 150 1.3 165 1.5 202 1.8
4 110 1.8 120 2.0 149 2.4
6 55 2.0 52 1.9 104 3.7
8 15 1.0 38 1.5 53.9 3.45
10 13.3 1.3 12.6 2.0 17.5 1.7
13 13.3 2.3 12.6 1.26
16 7.0 1.8 7.7 2.0 10.9 2.8
20 6.25 2.5 6.7 2.7 6.0 2.4
25 5.0 3.2 4.6 2.9 4.1 2.6
32 3.6 3.7 3.5 3.6 2.8 2.9
40 3.0 4.8 2.8 4.5 2.5 4.1
50 1.3 3.25 1.25 2.9 1.8 4.4
63 1.2 4.8 0.7 5.2 1.3 5.2
1)
Current intensities 0.5-4 apply exclusively to C-type trip characteristics.
S200MR
Rated current Internal resistance
per pole
Power loss
per pole
A mΩ W
0.2 25300 1.01
0.3 13700 1.23
0.5 4740 1.19
0.75 2067 1.16
1 1270 1.27
1.5 610 1.56
2 442 1.77
3 140 1.26
4 109 1.75
5 50 1.26
6 54 1.94
8 22 1.41
10 18.2 1.82
13 14.8 2.50
15 8.1 1.83
16 11.1 2.83
20 8.5 3.40
25 5.5 3.43
30 3.8 3.39
32 4.6 4.70
35 3.9 4.76
40 2.8 4.40
50 1.7 4.25
60 1.7 6.18
63 1.9 7.56
B, C, D, K, and Z Ambient temperatures T (Cº/Fº)
-40/-40 -30/-22 -20/-4 -10/14 0/32 10/50 20/68 30/86 40/104 50/122 60/140 70/158
Amps
0.67 0.65 0.62 0.60 0.58 0.55 0.53 0.50 0.47 0.44 0.41 0.37
1.33 1.29 1.25 1.20 1.15 1.11 1.05 1.00 0.94 0.88 0.82 0.75
2.13 2.07 2.00 1.92 1.85 1.77 1.69 1.60 1.51 1.41 1.31 1.19
2.67 2.58 2.49 2.40 2.31 2.21 2.11 2.00 1.89 1.76 1.63 1.49
4.0 3.9 3.7 3.6 3.5 3.3 3.2 3.0 2.8 2.6 2.4 2.2
5.3 5.2 5.0 4.8 4.6 4.4 4.2 4.0 3.8 3.5 3.3 3.0
8.0 7.7 7.5 7.2 6.9 6.6 6.3 6.0 5.7 5.3 4.9 4.5
10.7 10.3 10.0 9.6 9.2 8.8 8.4 8.0 7.5 7.1 6.5 6.0
13.3 12.9 12.5 12.0 11.5 11.1 10.5 10.0 9.4 8.8 8.2 7.5
17.3 16.8 16.2 15.6 15.0 14.4 13.7 13.0 12.3 11.5 10.6 9.7
21.3 20.7 20.0 19.2 18.5 17.7 16.9 16.0 15.1 14.1 13.1 11.9
26.7 25.8 24.9 24.0 23.1 22.1 21.1 20.0 18.9 17.6 16.3 14.9
33.3 32.3 31.2 30.0 28.9 27.6 26.4 25.0 23.6 22.0 20.4 18.6
42.7 41.3 39.9 38.5 37.0 35.4 33.7 32.0 30.2 28.2 26.1 23.9
53.3 51.6 49.9 48.1 46.2 44.2 42.2 40.0 37.7 35.3 32.7 29.8
66.7 64.5 62.4 60.1 57.7 55.3 52.7 50.0 47.1 44.1 40.8 37.3
84.0 81.3 78.6 75.7 72.7 69.6 66.4 63.0 59.4 55.6 51.4 47.0
112.6 107.2 102.1 97.2 92.6 88.2 84.0 80.0 76.0 72.2 68.6 65.2
140.7 134.0 127.6 121.6 115.8 110.3 1050 100.0 95.0 90.3 85.7 81.5
175.9 167.5 159.5 151.9 114.7 137.8 131.3 125.0 118.8 113.8 107.2 101.8
Technical specifications
S200, S200P, and S200MR—UL 1077, CSA 22.2 No. 235
Internal resistance and power loss per pole
Internal resistance per pole in mV, power loss per pole in W.
Temperature derating
Max operating current depending on the ambient temperature of a circuit breaker characteristics type B, C and D