Datasheet

US Catalog | Miniature Circuit Breakers 55
S804U-PVS5
1-ft 1-ft 1-ft 1-ft
1-ft 1-ft
1-ft
1-ft1-ft1-ft1-ft
1-ft
1-ft 1-ft
Line and load migth be reversed
1-ft
+
LOAD
LOAD
+
-
LOAD
+
-
+
-
LOAD
LOAD
LOAD
+
+
-
+
-
Ampere Rating [A]
10–32
Conductor Type
Single conductor per terminal –
copper only, 60/75°C wire
AWG, Wire Range
Jumper Length [cm]
Jumper Length [ft]
14 AWG–2 AWG
Cu, solid or stranded
1
30.5
40–63
Single conductor per terminal –
copper only, 60°C wire only
1/0 AWG–8 AWG
Cu, solid or stranded
1
30.5
70–80
Single conductor per terminal –
copper only, 60°C wire only
1/0 AWG–8 AWG
Cu, solid or stranded
2
61
Dimension S804U-PVS5
Tested and listed wirings
Trip curve for S804U-PVS5
Tripping behavior acc. to UL 489
Thermal release: 1.13 1.30 x I
n
Magnetic release: 6 x I
n
95
142
45
35
79.5
53
26.5
1P 2P 3P 4P
106
2CCC413012Z0001
76.5
46
82.56