Datasheet

93
Heating Controllers
TAC 2112
The TAC 2112 offers control of hot water heating systems. The radiator
circuit is controlled according to an outdoor temperature-compensated reset
curve and reference sensor.
Simple symbols, a clear LCD display and a minimum number of buttons
makeiteasytoreadandchangethevalues.Therearethreeadjustablecurve
pointswhereyoucanadjusttheresetcurveexactlytosuitdifferentheating
systems.
FUNCTIONAL FEATURES
Automaticadjustmentofthe
reset curve
Ramp limitation of supply
setpoint
Control of room temperature
via reference sensor
Weekly program for night
setback
Separate weekly program for
external equipment
Holiday program
Variable night setback and
morning heating
Optimized changeover from
daytime operation to night
setback
Pump control with exercise
function
Externalsetpointadjustment
(SPC control)
Extended daytime operation
and forced night setback from
an external unit
Alarm
SPECIFICATIONS
Power supply. . . . . . . . . . . . . . . . . . . . . . . 24 V AC +20%, 5060 Hz
Power consumption. . . . . . . . . . . . . . . . . . 3W
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 144 x 96 x 96mm
(5.7”x3.8”x3.8”)
Ambient Temperature
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . –20 °C to +50 °C
(4 °F to +122 °F)
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 °C to +50 °C (32 °F to +122 °F)
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . max. 90% RH non-condensing
Real Time Clock
Accuracy at +25°C (77º F) . . . . . . . . . . . . ±12 minutes/year
Backup memory . . . . . . . . . . . . . . . . . . . . 48 hours
Thermistor Inputs
Type of thermistor. . . . . . . . . . . . . . . . . . . 1800 ohm/ 25°C (+77º F )
Measurement range . . . . . . . . . . . . . . . . . 50°C to +120°C
(-58º F to + 248º F)
Relay Outputs
Max. voltage. . . . . . . . . . . . . . . . . . . . . . . 250 V AC
Max. current . . . . . . . . . . . . . . . . . . . . . . . 2 A
Inputs
Sensor inputs B1-B4, U1, U4 thermistor input (see above)
Setpointadjustment(SPC),U2 . . . . . . . . . 0–10 V DC
Additional connection to outdoor temp., Y2 010 V DC
Enclosure rating. . . . . . . . . . . . . . . . . . . . . IP 40, front IP 54
DESCRIPTION
200-2201-000 TAC 2112 Swedish Controller
200-2202-000 TAC 2112 Danish Controller
200-2203-000 TAC 2112 Swedish/Finnish Controller
200-2204-000 TAC 2112 GB Controller
CAT-VISTA-A4.indd 93 6/18/2009 1:51:25 PM