10 Click Next.
11 Equipment Name - type a new equipment name if desired.
12 Save Location - browse to a location where you would like to save the new custom equipment.
Click Save.
To format a LonWorks address
All Lonworks addresses should be assigned to "lonworks://" only when setting up address strings in
ApplicationBuilder. The
LonWorks Integration Tool is used to define these addresses.
To format a CCN address
There are three different methods for defining the CCN address strings.
1 They can be manually typed in ApplicationBuilder.
2 You can use Copy table point in i-Vu CCN's table interface to copy CCN point information directly from a
CCN table to ApplicationBuilder's "ccn://" address field.
3 You can use Map to Point in i-Vu CCN's table interface to map the CCN points from your custom
equipment file directly to CCN table data.
NOTE Your custom equipment must already be downloaded in the i-Vu Link to use this method. (Proceed
to Assign and download custom equipment in i-Vu CCN first).
Method 1: Type the address manually in ApplicationBuilder
1 If you are actively reading or writing a point on a CCN device, then manually type in the CCN device's
address,
Table Name, and Point Name that you wish to read or write.
ccn://link/<Table Name>/<Point Name> ("link" indicates the CCN device that the custom equipment
has been mapped to)
or
ccn://<bus, element>/<Table Name>/<Point Name>
Examples:
ccn://link/HWP01-32/TEMP
ccn://0,2/HWP01-32/TEMP
2 If the point is a CCN passive point (i.e, it's just being exposed to the CCN network), then type:
ccn://passive/<point name>, where <point name> is the name that you have chosen for this CCN point.