Installation guide
The integration process
LonWorks 7
Method 2: Copy table point in i-Vu CCN
1 Launch i-Vu CCN.
2 Select the desired equipment in the navigation tree.
3 Expand the tables underneath that equipment.
4 Find the specific table and point that you want to read or write.
5 Click Copy in the table interface.
6 Inside of ApplicationBiuilder, hit CTRL-V to copy the CCN address from the table to the "ccn://" address
field.
Method 3: Map to point in i-Vu CCN
1 Launch i-Vu CCN.
2 Select the desired equipment in the navigation tree.
3 Expand the tables underneath that equipment.
4 Find the specific table and point that you want to read or write.
5 In the table interface, navigate to the Map to Point column.
6 From the drop-down menu, select the point in the custom equipment that should be mapped.
7 Click OK.
2 Assign and download the Lonworks driver
1 In the navigation tree, right-click on the i-Vu Link and select Driver Properties.
2 Right-click on the Driver node and select Configure.
3 In the Driver Version drop-down menu, select drv_ivulink_lon <latest version>.
4 Click OK and the driver will be automatically downloaded.