Installation guide
The integration process   
8  LonWorks 
3 Assign and download custom equipment in i-Vu CCN 
1  Open i-Vu CCN. 
2  In the navigation tree, right-click the area where you want to place the custom equipment. Select Add 
Equipment from the drop-down menu.  
3  Make the following entries: 
Field
Notes 
Display Name
  Type an equipment name (i.e. ABB Drive). 
Associate with
  If your i-Vu Link is connected to CCN devices: 
○  Enable CCN Device and fill in the bus and element 
number of the CCN device that this custom 
equipment will be linked to.  
NOTE
 This "association" is what allows you to use the 
term "link" in CCN address strings for this custom 
equipment rather than manually typing in the bus, 
element number into each CCN address string. 
If your i-Vu Open Link is NOT connected to CCN devices 
(only LonWorks devices): 
○  Enable CCN Link and pick the i-Vu Link that is 
physically connected to the LonWorks network. 
Equipment
  Click 
Add.  
Browse to the .equipment file that was generated in 
ApplicationBuilder.  
Click 
Continue
.  
When message appears "File uploaded successfully", 
click 
Close
.  
4  If you have already created a custom equipment graphic for this third party device in ViewBuilder, you 
can also add that graphic from this screen. Under 
Views, click Add and browse to your .view file. Click 
Continue. When message appears File added successfully, click Close. The custom equipment should 
now appear in the navigation tree.  
5  Click Exit Setup and the custom equipment will be downloaded to the i-Vu Link. 
4 Configure LonWorks points using LonWorks Integration tool 
1  Log in to i-Vu CCN. 
2  In the navigation tree, right-click on the custom equipment and click Configure. 
3  Navigate to the Integration Points section at the bottom of the screen and click Export. 