Installation guide

The integration process
LonWorks 9
4 Click Save.
5 Browse to a location on your PC to save the file. (The file will have a .erl extension.)
6 Start the LonWorks Integration Tool (Lonworks_Integration_Tool.jar).
7 Click to start the wizard
8 Follow the wizard's instructions to create your LonWorks addresses.
9 Click
to save the file to your PC. (The file will be saved with a .erl extension.)
10 Return to i-Vu CCN.
11 In the navigation tree, right-click on the custom equipment and click Configure.
12 Navigate to Integration Points at the bottom of the screen and click Import.
13 Browse to the .erl file that you saved in the LonWorks Integration Tool.
14 Click Open and then Continue to upload the file.
15 Click Close. The LonWorks addresses are now set.
To edit an integration or CCN point address
You can edit an integration or CCN point address in the following places:
In ApplicationBuilder
In i-Vu CCN on the custom equipment's Properties page > Equipment tab
In i-Vu CCN on the custom equipment's Properties page> Network Points tab
In the LonWorks Integration Tool
5 Connect an SLTA-10 to each i-Vu Link on the LonWorks network
segment
CAUTION!
You will damage the SLTA-10 if it does not have its own isolated power supply. Do not share power with the i-
Vu Link.
1 Turn off the i-Vu Link’s power.
2 Remove power from the SLTA-10.
3 Set SLTA-10 DIP switches 18 as shown below. Switches 68 set the baud rate to 57600 for
communications between the control module and the SLTA-10 .