Installation guide
The integration process
10 LonWorks
4 Wire the i-Vu Link's Port S2 to the SLTA-10's EIA-232 port using one of the following methods:
○ If you have an EIA-232/RS-232 straight-through cable with connectors and an S2-DB9 Adapter:
Connect the adapter to the control module's port. Then connect one end of the cable to the adapter
and the other end to the SLTA-10's
EIA-232 port.
○ If you have an 18-22 AWG, 4-conductor cable and a DB9 male adapter:
Wire one end of the cable to the control module's port and the other end to the adapter. See table
below. Then connect the adapter to the SLTA-10's EIA-232 port.
i-Vu Link's...
Tx
...to DB9
adapter pin
Rx
Signal Ground
3
2
5
5 Set the jumper for the control module's port to EIA-232.
6 Turn on the i-Vu Link's power.
7 Apply power to the SLTA-10.
6 Set up the driver properties
1 On i-Vu CCN's navigation tree, right-click on your custom equipment.
2 Select Driver Properties.
3 Expand Protocols and select LonWorks.
4 Select the i-Vu Link port S2 that connects to the SLTA-10.
5 In the Baud field, type 57600, the baud rate that you set on the SLTA-10 DIP switches.
6 Leave the default settings in the remaining fields under Port Configuration and the fields under
LonWorks Protocol Setup.
7 Under SLTA Domain Table, select Yes in the Define Domain Table field.
8 On the first line of the table (Index 0), enter appropriate values in each field. See table below.
9 In Windows Notepad, open the .log file that NodeUtil created. To see this file in the Open dialog box,
select
All Documents in the Files of type field.
Field
Notes
Select
Cloned
No
for most applications.
Locate this number in the .log file. The Domain Length is in the
Domain Length
Size
field highlighted in the following example.