Installation guide

The integration process
LonWorks 11
Field
Notes
Locate this number in the .log file. The Domain ID is 1
2-character segment, 3 segments, or 6 segments. In the following
example, the highlighted Domain ID is 1 2-character segment.
Domain ID
In i-Vu CCN, type -00 after the ID as many times as needed so that
the
Domain ID
field has 6 2-character sections.
Locate this number in the .log file. The Subnet ID is highlighted in
the following example.
Subnet ID
In this field, you are giving the SLTA/Router or Link an ID number on
the LonWorks network. Type any value in the range 1127, but it
Node ID
cannot
be the same as the Node ID of any LonLonWorks device on
the LonLonWorks network. 99 is typically a good number to use.
Do not change these values for most applications.
Authentication Key
i-Vu CCN uses this authentication code if the third-party device
requests authentication.
10 Click the Properties button to refresh the page. Verify the following values in the SLTA Node Status
section:
SLTA Comm Established: Yes
(SLTA-10 and Carrier controller are communicating.)
SLTA Node Online: Yes
(SLTA-10 and LonWorks network are communicating.)
SLTA Node Configured: Yes
(SLTA-10 has been commissioned.)
Address Domain: (As displayed in the SLTA Domain Table)
11 On the navigation tree, select Protocols.
12 In the Protocol Status table, verify that the LonWorks protocol shows Running on port S2.
If the status shows Not running or the wrong port, verify port selection and DIP switch settings for that
port on the control module.