Installation guide
Appendix B - Common HVAC SNVT's   
14  LonWorks 
SNVT # 
SNVT Name 
Element # 
Measurement 
Value 
39  SNVT_temp  0  °C  -274 — 6,279.5 
83  SNVT_state  0 
0 — 65,535 
Each bit must be parsed out using control program 
logic.  
84  SNVT_time_stamp  0  year  0 — 3,000 
1  month 
1 — 12 = January — December 
0 = month not specified 
2  day 
1 — 31  
0 = day not specified  
3  hour  0 — 23 
4  minute  0 — 59 
5  second  0 — 59 
85  SNVT_zerospan  0  zero offset   -163.84% — 163.835% 
1  span multiplier   0 — 32.7675 
87  SNVT_elapsed_tm  0  day  0 — 65,535 
1  hour  0 — 23 
2  minute  0 — 59 
3 
second 
0 — 59 
4  millisecond  0 — 999 
88  SNVT_alarm  0 — 5  location 
0 — 255 (decimal ASCII value)  
location of node number,  
description of characters used  
6  object ID (in node)  0 — 65,535 
Appendix B - Common HVAC SNVT's 