Installation guide

Appendix B - Common HVAC SNVT's
18 LonWorks
SNVT #
SNVT Name
Element #
Measurement
Value
112
SNVT_hvac_status
0
mode
0 = Controller automatically changes between
application modes
1 = Heating only
2 = Application-specific morning warm-up
3 = Cooling only
4 = Application-specific night purge
5 = Application-specific pre-cool
6 = Controller not controlling outputs
7 = Equipment being tested
8 = Emergency heat mode (heat pump)
9 = Air not conditioned, fan turned on
10 = Cooling with compressor not running
11 = Ice-making mode
12 = Max Heat
13 = Economy
14 = Dehumid
15 = Calibrate
16 = Emergency Cool
17 = Emergency Steam
18 = Max Cool
19 = HVC Load
20 = No Load
-1 = Value not available
1 % primary heat output -163.84% 163.83
2 % secondary heat output -163.84% 163.83
3 % cool output -163.84% 163.83
4 % econ output -163.84% 163.83
5 % fan output -163.84% 163.83
6 % in alarm 0 255
113
SNVT_press_p
0
Pa(Pascal)
-32,768 32,768
127 SNVT_chlr_status 0 chiller run mode
0 = Overwrite this scene with new data
1 = Delete this scene from the list
2 = Display this sceneís data
3 = Report the number of programmed
scenes
4 = Report the number of free scene
storage spaces
-1 = Value not available
1 chiller operation mode
0 = Controller automatically changes modes
1 = Heating only
2 = Morning warm-up
3 = Cooling only
4 = Night purge
5 = Pre-cool
6 = Controller not controlling outputs
7 = Equipment being tested
8 = Emergency heat pump
9 = Air not conditioned, fan turned on
10 = Cooling with compressor not running
11 = Ice-making mode
12 = Max Heat
13 = Economy
14 = Dehumidify
15 = Calibrate
16 = Emergency Cool
17 = Emergency Steam
18 = Max Cool
19 = HVC Load
20 = No Load
-1 = Value not available
2 chiller state 1 = in alarm
3
1 = run is enabled