Installation guide
  Appendix B - Common HVAC SNVT's 
LonWorks  19 
SNVT # 
SNVT Name 
Element # 
Measurement 
Value 
4 
1 = local 
5 
1 = limited 
6 
1 = chilled water flow 
7 
1 = conditioned water flow 
128  SNVT_tod_event  0 
current scheduled 
occupancy state 
0 = Area is occupied 
1 = Area is unoccupied 
2 = Area is temporarily occupied for the 
 bypass period 
3 = Area is temporarily unoccupied 
-1 = Value not available 
1 
next scheduled 
occupancy state  
0 = Area is occupied 
1 = Area is unoccupied 
2 = Area is temporarily occupied for the 
 bypass period 
3 = Area is temporarily unoccupied 
-1 = Value not available 
2  Minutes to next state  0 — 65,535  
138  SNVT_Volt_ac  0  Volt  0 — 65,535 
139  SNVT_amp_ac  0  Amp  0 — 65,535 
145  SNVT_hvac_type  0  enumerated 
0 = Generic 
1 = Fan coil 
2 = VAV Terminal 
3 = Heat Pump 
4 = Roof Top Unit 
5 = Unit Ventilator 
6 = Chilled ceiling 
7 = Radiator 
8 = Air Handling Unit 
9 = Self-contained unit 
153  SNVT_Enthalpy  0  J/Kg  -32,768 — 32,767 