Installation guide

LonWorks 1
LonWorks Integration with the i-Vu Link
You can integrate LonWorks devices into an i-Vu CCN system with a i-Vu Link acting as a master device.
Carrier
i-Vu Link
i-Vu Link
LonWorks port S2
Module driver drv_ivulink_lon_<latest version>.driver*
Read/write capability Can read from and write to the third-party equipment
Third party points supported
500
Third party
Supported equipment Any device that supports the LonWorks protocol using
SNVT's**
Network media type EIA-232 to SLTA-10 network adapter
Quantity of devices you can
physically connect to the i-Vu Link
1 LonWorks network segment with up to 64 LonWorks
devices, daisy-chained
*The i-Vu Link driver supports LonWorks devices connected to Port S2 and BACnet or Modbus devices
connected on the Ethernet port simultaneously. The third party point count for the i-Vu Link is the total of the
2 ports.
** UNVT's are proprietary and not supported.