Installation guide
The integration process   
4  LonWorks 
Follow the steps in this document to integrate one or more third party LonWorks devices into an i-Vu CCN 
system using an i-Vu Link. To install and network the i-Vu Link, see the i-Vu Link Installation and Start-up 
Guide. 
1 Create custom equipment in ApplicationBuilder 
1  Start ApplicationBuilder. 
2  Select equipment type:  
○  CCN Values Only - to read and write values on the CCN network and to display those points on a 
graphic 
○  Integration Values Only - to read and write values from the third party network and to display those 
points on a graphic  
○  CCN Link Integration - to share values from the third party network with the i-Vu Link on the CCN 
network and to display those points on a graphic 
3  Click Next. 
4  Type a name for the custom equipment (i.e., Hot Water System).  
NOTE The name must not exceed 21 characters! 
5  Enable English or Metric units. 
6  Choose engineering options for your application (Schedule and Setpoint, Runtime, etc..) 
7  Click Next. 
8  Add Elements to your application.  
NOTE Elements are a collection of input/output points that perform a specific operation. The 
input/output point that is reading or writing to the LonWorks network is called an integration point. 
Integration points may be used in conjunction with CCN points to share data between the LonWorks 
network and the CCN network.  
The available Elements that you can add to your custom equipment in ApplicationBuilder are: 
Point type 
Used for 
Read CCN Point  Reading an analog or binary value from the CCN network 
In: CCN Values, Link Integration 
Carrier Text Point  Reading Text value from a CCN device  
In: CCN Values, Link Integration 
Setpoint Write  Allows CCN setpoint value to be “edited” directly from 
graphic 
In: CCN Values, Link Integration 
The integration process 