Technical data

14
1MRS751108-MUM
Protection Relay
Technical Reference Manual, General
REX 521
3.2. Application
The REX 521 is designed for protection of incoming and outgoing feeders in
medium voltage distribution substations. Further, the relay can, for example, be
applied to back-up protection of power transformers and back-up for high voltage
line protection relays.
Table 3.2.-1 Standard configurations for REX 521
HW versions Basic Medium High/Sensor
Standard configurations B01 B02 M01 M02
H01
a
H02H03H04H05H06H07
H08
bc
H09
bc
H50
b
H51
b
IEC
symbol
ANSI
device
number
FB name
(CD-ROM)
Protection
3I> 51-1 NOC3Low x x x x x x x x x x x x x x
3I>> 51-2 NOC3High x x x x x x x x x x x x x x
3I>>> 51-3 NOC3Inst x x x x x x x x x x x x x
Io> 51N-1 NEF1Low x x
x
d
xxxxxx
Io>> 51N-2 NEF1High x x
x
d
xxxxxx
Io>>> 51N-3 NEF1Inst x x
x
d
xxx
Io>-->
e
67N-1 DEF2Low x x x x x x x x x
Io>>-->
e
67N-2 DEF2High x x x x x x x x x
Io>>>-->
e
67N-3 DEF2Inst x x x x x x
3I>--> 67-1 DOC6Low
x
f
x
f
x
f
x
f
3I>>--> 67-2 DOC6High
x
f
x
f
x
f
x
f
3U> 59-1 OV3Low x x x x x x x
3U>> 59-2 OV3High x x x x x x
3U< 27-1 UV3Low x x x x x x x
3U<< 27-2 UV3High x x x x x x
3I2f> 68 Inrush3 x x x x x x x x x x x x
Iub> 46 CUB3Low x x x x x x x x
3Ith> 49F TOL3Cab x x x x x x x x
O-->I 79 AR5Func x x x x x x x x
Uo> 59N-1 ROV1Low x x x x x x
Uo>> 59N-2 ROV1High x x x x x
Uo>>> 59N-3 ROV1Inst x x x x
f1 81-1 Freq1St1 x x x x x x x
f2 81-2 Freq1St2 x x x x
SYNC1 25-1 SCVCSt1 x x
Is2t n< 48 MotStart x x
3I() 46R PREV3 x x
I2> 46-1 NPS3Low x x
I2>> 46-2 NPS3High x
3I< 37-1 NUC3St1 x
FUSEF 60 FuseFail x x
3Ithdev> 49M/G/T Tol3Dev x x x x
U1U2<>_1 47-1 PSV3St1 x x x