Technical data
1MRS751108-MUM
REX 521
29
Protection Relay
Technical Reference Manual, General
A051902
Fig. 5.1.8.1.-1 High-speed double-pole power output (HSPO)
The high-speed power output HSPO1 can also be connected as a single-pole power
output where the object to be controlled (for example a circuit breaker) is electrically
connected in series with the two relay contacts, see the Fig. 5.1.8.1.-2 below.
A051903
Fig. 5.1.8.1.-2 High-speed single-pole power output (HSPO)
5.1.8.2. Single-pole power outputs (PO)
The single-pole power outputs PO1...3 are outputs where the object to be controlled
is connected in series with two heavy-duty output relay contacts, see the
Fig. 5.1.8.2.-1 below. These outputs can be used for tripping purposes and for circuit
breaker and disconnector control. Two singe-pole outputs may be used to obtain
another double-pole output.
A051904
Fig. 5.1.8.2.-1 Single-pole power outputs (PO1...3)
+
-
HSPO1
CB
+
-
CB
HSPO1
+
-
CB
PO1...3